31
20098687
GB
Start-up, calibration and operation of the burner
6.13
Final checks (with burner operating)
Tab. K
➤
Disconnect a wire of the minimum gas pressure switch
➤
Open the thermostat/pressure switch TL
➤
Open the thermostat/pressure switch TS
➮
The burner must stop
➤
Disconnect the common wire P of the air pressure
switch
➤
Disconnect the wire of the ionisation probe
➮
The burner must stop in lockout
WARNING
Make sure that the mechanical locking systems
on the various adjustment devices are fully tight-
ened.