23
20098687
GB
Installation
5.11.2
Modulating operation
In the event the RWF output power regulator kit is connected or
the converter 0...10V / 4...20mA, 3-point signal, the TR thermo-
stat/pressure switch should be removed.
In addition, the function Q13 - Q14 of the regulator RWF can sub-
stitute the TL thermostat/pressure switch terminals T2 and T1 of
the socket X7. In this case, the thermostat/pressure switch TL
connected to the X7 must be removed.
On the contrary, if you want to maintain the thermostat/pressure
switch TL, it must be adjusted so as not to interfere with the work-
ing of the regulator RWF.
NOTE:
The TR and TL remote controls are not necessary when the RWF
is connected for modulating operation; their function is carried out
by the regulator itself.
After carrying out maintenance, cleaning or
checking operations, reassemble the cover and
all the safety and protection devices of the burner.