20146119
22
GB
Installation
5.13 Table of times
Tab. F
5.13.1 Operating status indication
Tab. G
Key to layout
Tab. H
Symbol
Description
Value (sec.)
t0
Standby: the burner is waiting for the heat request, the closure of the gas pressure switch, the open-
ing of the air pressure switch
-
t1
Standby time for an input signal: reaction time, control box remains in waiting mode for t1
2
t1l
Flame or flame simulation detected before demand for heat: the control box remains idle.
25
t2
Initialisation standby time: checking time following the main power start-up
4.5
t2l
Checks extraneous light or parasite flame during t2: waiting mode for t2l, then lockout: the motor
does not start
25
t2a
Check whether the air pressure switch has already been moved to the work position before the
required heat: the control box remains in standby status, a lockout follows if the air pressure switch
remains switched for the
T2a
time.
max 120
t3
Pre-purging time: the fan motor is running, then the gas valve is activated
40
t3l
Checks extraneous light or parasite flame during pre-purging: control box goes into lockout at the
end of t3l
1
t3a
Time for checking the switching of the air pressure switch in the operating position during the pre-
purging time: if the pressure switch does not change over within
t3a
there is a lockout.
max 15
t3r
A recycle attempt is made if there is an air pressure drop during the pre-purging stage: there is then
a lockout in the event of a second loss of air pressure between the 16th second and the 29th; is a
loss of pressure between the 30th second and the 40th, the control box goes immediately into lockout
mode.
-
ts
Safety time
5
t4i
Total spark ignition time
5
t4a
Air pressure drop checking time during the
ts
time and the normal operation:
the control box locks out immediately.
1
t4l
Reaction time to achieve safety deactivation due to flame loss
1
-
Minimum time to reset the control box using reset button
0.4
Minimum time to reset the control box using remote reset
0.8
tr
Re-cycles: max. 3 repeats of the complete start-up sequence in the case of flame loss during opera-
tion; the final action at the last attempt following flame failure is a lockout
3
re-cycles
tsm
Standby time for servomotor opening of the electric damper opener
~
4
Status
Reset button
colour
Seconds
Colour code
Waiting fr a heat request, waiting for the closure of the gas
pressure switch, waiting for the opening of the air pressure
switch
-
-
-
-
Awaiting heat request with continuous purging
ORANGE
Blink
0.5
2.5
Pre-purging, or awaiting air pressure switch closure, or
long pre-purging
ORANGE
Blink
0.5
0.5
Safety time without flame
GREEN
Blink
0.5
0.5
Safety time with flame
GREEN
-
-
Normal operating position
GREEN
-
-
ON
OFF
Colour code
RED
ORANGE
GREEN