3
20138365
GB
Installation
The MO550-BUWG control box is installed on the burners with
exclusive use of the 2-wire flame sensors, of the FD01 range.
Burner equipment
Control box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . No. 1
Safety lockout device SER . . . . . . . . . . . . . . . . . . . . . . . . . No. 1
Safety lockout device V2 . . . . . . . . . . . . . . . . . . . . . . . . . . No. 1
Safety lockout device RS and connection . . . . . . . . . . . . . No. 1
Bridge socket . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . No. 1
Instruction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . No. 1
To install the new MO550 - BWG control box, it is necessary to
use the diagram below.
Key to layout (Fig. 2)
K
- Thermostat enabling start-up after pre-heating (only for
suitable applications)
PH
- Oil heater (only for suitable applications)
MV
- Fan motor
V1
- Oil valve 1st stage
F
- Flame
sensor
V2
- Oil valve 2nd stage
SER
- Safety lockout device
RS
- Remote reset
To install, proceed as follows:
unscrew the fixing screws and remove the burner cover.
disconnect all connections, the 7-pin plug, the probe con-
nector, the high voltage cables and the earth wire from the
control box.
disconnect the control box from the burner by loosening the
screw
A
) (Fig. 3) and pulling in the direction of the arrow.
Install the new control box supplied, fixing it to the burner
with the screw
A
)(Fig. 3) and using a tightening torque of
1 - 1.2 Nm.
reconnect all connections, the 7-pin plug and the earth wire.
2
Installation
MO 550 - MWG
MO 550 - BWG
MO 550 - BWG
DANGER
All the installation, maintenance and dismantling
operations should be performed voltage free.
The replacement of the control box must be per-
formed by qualified personnel, as indicated in this
manual and in accordance with standards and
regulations in force.
WARNING
The bridge socket must be installed on the con-
trol box only for burners not equipped with a light
oil heater.
WARNING
Connecting the remote reset
Make the connection with the
RS
lead supplied
with the burner.
Connect a button at a max. distance of 20 metres.
Fig. 1
S9675
Fig. 2
S9674
N
L2
R
C
N
2
A
M
B
N
1
S
E9288
SER
F
PH
MV
V2
V1
RS
K
Fig. 3
E9275
A