TECHNICAL ASSISTANCE SERVICE
60
PUMP PRIMING FUNCTION
During a lockout, the burner can be purged for 30 seconds to eliminate any air from the pipes and filters of the fuel oil
supply pipes.
To avoid damaging the pump, do not repeat this procedure more than 5 times.
Pump priming sequence
Colour codes for burner reset button LED
The remote reset button must be pressed and held for over 6
seconds, and then released
Green / Orange / Red flashing
Press the remote reset button but release it within 3 seconds to
activate the pump priming cycle
Green / Orange / Red
The fan motor starts after 2 seconds.
The pump priming cycle can be stopped before the end of the "Pump priming time" (30 secs) by pressing the button
again for 1 to 2 seconds.
While the button is pressed, the fan motor will not start.
DE-ACTIVATING AUTOMATIC PRE-HEATING
The automatic pre-heating functioning can be de-activated by pressing the remote reset button.
Pre-heating de-activation sequence
Colour codes for
burner reset button
LED
Permit de-activation of pre-heating only if no lockout or errors are present.
-
Permit de-activation of pre-heating only from the remote reset button.
-
Switch on the burner and simultaneously hold down the remote reset button for 3 seconds.
RED
Release the remote reset button within 3 seconds.
OFF
The burner will start de-activation of pre-heating only if the remote reset button is released
within 3 seconds.
-
Pre-heating remains de-activated until:
- a lockout occurs;
- mains power fails;
- intermittent functioning occurs.
POST-PURGING
Post-purging is a function that allows you to maintain the air purging even after the burner is switched off in the absence
of the heat request for a pre-set time.
The burner switches off the flame when the heat request thermostat opens, cutting off the fuel supply to the valves.
The post-purging function is not performed:
- after a lockout;
- if the heat request is interrupted during pre-purging.
Post-purging occurs:
- if the heat request is interrupted during the safety time;
- if the heat request is interrupted during normal operation.
NOTE:
If during post-purging there is an extraneous light or a parasite flame the burner goes into lockout after 25 seconds.
If during post-purging there is a new heat request, the post-purging time is halted, the fan motor
i
stops and a new burner
operating cycle starts.