Battery charger stage
Rated voltage
240Vdc
Maximum recharging current
(5)
25A
Battery charger algorithm
Two levels with temperature compensation
Technology
Analogue switching current mode under the control of the
P
(PWM regulation of charging current and voltage)
Input voltage tolerance range for recharging at
maximum current
345-480Vac
UPS models
100 kVA
120 kVA
Dimensions and weights
Width x Depth x Height
750 x 855 x 1900 mm
Type of structural work
Tower type with wheels, movement with transpallet, display fixed to the top of the
door. Door at the top for access to switches and connections
Weight (without batteries)
370 kg
380 kg
Modes and levels of efficiency
Operating modes
True on line double conversion
ECO mode
Smart Active mode
Stand-by Off (Emergency power supply)
Frequency Converter
AC/AC efficiency in on line mode
94%
94%
AC/AC efficiency in Eco mode
98%
Maximum power dissipation
6900 W
7200 W
Environment of installation
Max relative humidty during operation
90 % (without condensation)
Max installation height
1000 m at rated power
(-1% power for every 100 m above 1000 m)
max 4000 m
Fan flow rate in place of installation to disperse
heat
(9)
3600 mc³/h
3800 m³/h
Protection rating
IP20
Cable entry
back/front
Other
Noise level
≤70dB(A)
≤70dB(A)
Colour
RAL 7016
Ambient temperature
(7)
0
– 40 °C
(1)
In order to ensure the output voltage remains within the range of precision shown, it may be necessary to recalibrate after a long
period of operation
(2)
If the mains frequency is within ± 5% of the selected value, the UPS is synchronised with the mains. If the frequency is outside the
tolerance range or in battery operation mode, the frequency is as se0.1%
(3)
Mains/Battery @ load 0% -100%
(4)
@ Mains / battery / main @ resistive load 0% / 100% / 0%
(5)
The recharging current is regulated automatically in the basis of the capacity of the battery installed
(6)
The
“-” symbol replaces an alphanumerical code for internal use
(7)
20
– 25 °C for longer battery life
(8)
@ 100% load & THDv ≤ 1%
(9)
The table shows an example of the flow rate (at - et)=5°C and with resistive rated load (pf=0.9)