38
OTHER DATA
Leakage current towards ground
[mA]
< 1.5
≤
1.7
Room temperature
(7)
[°C]
0 – 40
Humidity
< 90% without condensation
Protection devices
excessive battery discharge - over current - short circuit - over
voltage - under voltage - thermal
Dimensions W x D x H
[mm]
250x698x500
Dimensions W x D x H
(only for ER versions)
[mm]
250x698x500
Weight
[Kg]
62 63 78 84
Weight (only for ER versions)
25
28
BATTERY BOX MODEL
KSTW180-A------
KSTW180-L------
KSTW180-M------
KSTW180-V------
KSTW240-A------
KSTW240-L------
KSTW240-M------
KSTW240-V------
Rated battery voltage
[Vdc]
180
240
Dimensions W x D x H
[mm]
250 x 698 x 500
Weight [Kg]
57
87
67
107
The “-” symbol replaces an alphanumeric code for internal use.
For additional details regarding technical data refer to website
(1)
For the input technical data of the three-phase input models configured as single-phase input “1
~
”, refer to the “SINGLE-
PHASE INPUT” section in the table
(2)
@ rated load, rated voltage of 220 VAC towards Neutral, battery charging
(3)
In the Bypass operating mode, all the load current is absorbed by the Phase 1 input line
(4)
The recharging current is regulated automatically according to the capacity of the battery installed. Derating of the current
delivered with a load greater than 80%.
(5)
To maintain output voltage within the accuracy range specified, recalibration may be necessary after a long period of
operation.
(6)
If the mains frequency is within ± 5% of the selected value, the UPS is synchronized with the mains. If the frequency is out
of tolerance range or in battery operation, the frequency is that selected ± 0.1%.
(7)
20 - 25 °C for maximum battery life.