36
Faults:
These are more critical problems compared to the “Anomalies”, as if they persist they may bring the UPS to
a halt even in a very short time.
CODE
DESCRIPTION
F01
Internal communication error
F03
Phase1 input fuse blown
F04
Phase2 input fuse blown or input relay locked (will not close)
F05
Phase3 input fuse blown or input relay locked (will not close)
F09
Precharge of positive branch condensers failed
F10
Precharge of negative branch condensers failed
F11
BOOST stage anomaly
F14
Inverter Phase1 sine curve distorted
F17
Inverter stage anomaly
F19
Positive battery overvoltage
F23
Output overload
F26
Phase1 output relay locked (will not open)
F29
Phase1 output fuse broken or output relay locked (will not close)
F32
Battery charger stage anomaly
F33
Battery measures error
F34
Heat sink overtemperature
F37
Battery charger overtemperature
F39
VDC Bus measures error
F40
Fan failure
F41
Redundant Bypass failure
Locks:
these codes indicate that the UPS, or one of its parts, is locked. Usually, they are preceded by an alarm signal.
In case of faults and consequent locking of the inverter, the latter will be turned off and the load will be powered via
the bypass line (this procedure is excluded for locks caused by serious and persistent overloads and for those caused
by a short circuit).
CODE
DESCRIPTION
L01
Incorrect auxiliary power supply
L02
One or more internal cables disconnected
L03
Phase1 input fuse broken
L04
Phase2 input fuse broken or input relay locked (will not close)
L05
Phase3 input fuse broken or input relay locked (will not close)
L06
BOOST stage overvoltage positive
L07
BOOST stage overvoltage negative
L08
BOOST stage undervoltage positive
L09
BOOST stage undervoltage negative
L10
Static bypass switch fault
L11
L1 bypass output locked
L14
Phase1 inverter overvoltage
L17
Phase1 inverter undervoltage
L20
Continuous voltage at inverter output or Sine curve of Phase1 inverter distorted
L23
Phase1 output overload
L26
Short circuit at Phase1 output
L34
Phase1 heat sink overtemperature
L37
Battery charger overtemperature
L38
Temperature probe 1 damaged
L39
Temperature probe 2 damaged
L41
Battery charger temperature probe damaged
L49
Inverter capacitor damaged