If an output is associated with one of the events listed in the table above, the relays for that output
switches when an active state occurs. If an output is associated with one of the inputs that is configured
as a digital input, the relay of the output in question switches when the input goes high. If an output is
associated with one of the inputs that has been configured as an analog input or temperature sensor, the
relay of the output in question switches when the signal on the input falls outside the predetermined
values.
Several UPS events and/or inputs can be associated with a single output. In this case, the relay of the
output switches when at least one of the associated events occurs.
EXAMPLE 1 - if you set an output in this way:
Associeted Events
Logic
Battery working
Normal OFF
the relative contact will be:
UPS powered by mains
UPS powered by batteries
EXAMPLE 2 - if you set an output in this way:
Associeted Events
Logic
Battery working
Normal ON
the relative contact will be:
UPS powered by mains
UPS powered by batteries
F
IRMWARE
U
PGRADE
The user can reprogram the accessory in order to upgrade the firmware. The upgrade files and relevant
instructions can be found
on the manufacturer’s web site.