34
O
UTPUTS
One or more UPS events (active status) and/or one or more inputs can be associated with the eight
outputs. These UPS events are described in the table below:
EVENT
ACTIVE STATUS
NON ACTIVE STATUS
DEFAULT
Output powered
Output voltage present
Output voltage not
present
OUTPUT 4
UPS locked
Inverter blocked for
failure/fault
Normal inverter
operation
-
Battery working
UPS in battery mode
UPS powered by mains
OUTPUT 1
Battery low
Batteries low warning
Batteries not discharged
OUTPUT 2
UPS on bypass
Load powered by
bypass line
Load powered by
inverter (if the UPS is
on)
OUTPUT 3
UPS failure
Anomaly detected
No anomalies
OUTPUT 7
Overload alarm
Output overload
Normal output load
OUTPUT 5
Overtemperature alarm
Internal overtemperature
Normal internal
temperature
OUTPUT 6
Bypass line not good
Bypass line outside
tolerance values
Normal bypass line
-
Bypass command active
Bypass command
present
No bypass command
present
-
Batteries charged
Batteries fully charged
Batteries not charged
OUTPUT 8
Replace batteries
Batteries need replacing Batteries still efficient
-
Shutdown active
Scheduled shutdown
active
Scheduled shutdown not
active
-
Shutdown imminent
Shutdown warning
active
Shutdown warning not
active
-
Test in progress
UPS test in progress
No test in progress
-
Communication lost
Communication with
UPS is lost
Communication with
UPS is normal
-