background image

2623

7

GB

4.3

COMBUSTION HEAD SETTING, 

(see fig. 12, page 6)

It depends on the output of the burner and is carried out by rotating clockwise or counterclockwise the setting
screw (6) until the set-point marked on the regulating rod (7) is level with the outside plane of the nozzle-holder
assembly (1).

In the sketch the combustion head is set for an output of 4.00 GPH at 15 bar.
The set-point 2 of the regulating rod (7) is at the same level with the outside plane of the nozzle-holder
assembly (1) as shown in the schedule.

4.4

ELECTRODES ADJUSTMENTS, 

(see fig. 13)

        

4.5

PUMP PRESSURE AND AIR OUTPUT

The burner, in order to guarantee good smooth
starts, irrespective of the type of boiler, is fitted
with a hydraulic device which, independently of
the control-box, reduces the fuel- and air-flow.
At ignition, the pressure at the nozzle is 9 bar. 
After 3 - 9 seconds, it automatically increases to
15 bar.
The air-flow, initially adjusted to the low setting,
is, at the change-over of pressure, automatically
brought to the air-flow required for the big flame.

SETTING FOR THE LOW IGNITION-FLAME

(See fig. 14)

ADJUSTMENT OF AIR SHUTTER

Unloosen the screw (8), by approximately one full
turn; in this way, the burner remains permanently
on low flame. 
Unloosen the nut (5), turn the screw (4) until the
indicator (6) reaches the position desired. 
Then lock the nut (5) and tighten the screw (8).

ADJUSTMENT START DELAYING DEVICE

This is set at 9 bar at the factory. 
The pressure gauge must be mounted in place of
plug (4, fig. 7, page 4).  Should it be necessary to
re-set or alter such pressure, this can be done,
by adjusting screw (7), always after having loos-
ened screw (8). For the adjustment, follow what
indicated in the table at page 6. 
Anyway, it is advised to adjust the content of CO

2

 at values not lower than 12%.

    

MEASURES MUST  BE RESPECTED.

WARNING:

Lean the diffuser disc-holder assembly (1)
on the nozzle-holder (2) and lock it by
screw (3). For prospective adjustments
loosen screw (4) and move the electrodes
assembly (5).

To have access to the electrodes carry
out operation as described in chapter “4.2
RECOMMENDED NOZZLES” 
(page 6).

D4019

4.5

 

– 0.5 mm

0

 7

 mm

Fig. 13

1

3

2

5

4

S7161

Fig. 14

Summary of Contents for RG3 393T1

Page 1: ...e gebruiks en onderhoudsvoorschriften Montage und Bedienungsanleitung O l Gebl sebrenner Br leur fioul Light oil burner Stookoliebrander CODE MODELL MODELE MODEL TYP TYPE 3739950 RG5S 399 T1 D F GB NL...

Page 2: ...ng 5 4 WORKING 6 4 1 Combustion adjustment 6 4 2 Recommended nozzles 6 4 3 Combustion head setting 7 4 4 Electrodes adjustment 7 4 5 Pump pressure and air output 7 4 6 Burner start up cycle 8 5 MAINTE...

Page 3: ...cal supply Single phase 50Hz 230V 10 Motor Run current 2 1A 2730 rpm 286 rad s Capacitor 8 F Ignition transformer Secondary 8 kV 16 mA Pump Pressure 8 15 bar Absorbed electrical power 0 47 kW 247 155...

Page 4: ...sing screws 5 and if necessary the nuts 2 interposing the insulating gasket 4 see fig 2 After installation ensure that burner is lightly inclined as in fig 5 3 2 FUEL SUPPLY The burner is designed to...

Page 5: ...8 it is sufficient to loosen the suction gauge connection 6 fig 7 and wait until oil flows out On the systems in fig 9 and 10 start the burner and wait for the priming Should lock out occur prior to...

Page 6: ...UTRAL WITH PHASE 7 pin plug 7 pole socket Black White Capacitor Main switch T6A Motor Blue Oil valve Hour counter 230V 0 1A max Limit thermostat Remote lock out signal 230V 0 5A max Ignition electrode...

Page 7: ...inen type S Danfoss type S TO FIT NOZZLE CARRY OUT THE FOLLOW ING ACTIONS see fig 12 Remove nozzle holder assembly 1 after loosing screws 2 and nut 3 remove the small cables 4 from the control box and...

Page 8: ...ure automatically brought to the air flow required for the big flame SETTING FOR THE LOW IGNITION FLAME See fig 14 ADJUSTMENT OF AIR SHUTTER Unloosen the screw 8 by approximately one full turn in this...

Page 9: ...ve consumption of fuel and consequent pollution Before carrying out any cleaning or control always first switch off the electrical supply to the burner acting on the main switch of the system THE BASI...

Page 10: ...the intervention of unqualified personnel FAULTS POSSIBLE CAUSES SOLUTION The burner doesn t start when the limit thermostat closes Lack of electrical supply Check presence of voltage in the L1 N clam...

Reviews: