MAINTENANCE

The burner requires periodic maintenance carried out by a qualified and authorised technician 

in conformity

with legislation and local standards.

Maintenance is essential for the reliability of the burner, avoiding the excessive consumption of fuel and
consequent pollution.

Before  carrying  out  any  cleaning  or control always first switch off the electrical supply to the
burner acting on the main switch of the system.

THE BASIC CHECK ARE:

y

Check that there are not obstructions or dents in the supply or return oil pipes.

y

Clean the filter in the oil suction line and in the pump.

y

Clean the photoresistance, (5, fig. 1, page 1).

y

Check for correct fuel consumption.

y

Replace the nozzle and check the correct position of electrodes (fig. 9, page 7). 

y

Clean the combustion head in the fuel exit area, on the diffuser disc.

y

Leave the burner working without interruptions for 10 min. and set rightly all the components stated in
this manual.  

Then carry out a combustion check verifying:

Smoke temperature at the chimney;

 

Content of  CO

2

  ( % );

Content of CO (ppm);     

Smoke value according to opacity smokes index according to Bacharach scale.

Summary of Contents for RDB1 CF 38

Page 1: ...ntenance instructions Light oil burners One stage operation CODE MODEL TYPE 3510225 RDB1 CF 38 501 T3 3510050 RDB1R CF 26 501 T1R 3510150 RDB1R CF 33 501 T2R 3510250 RDB1R CF 38 501 T3R 3510650 RDB2R...

Page 2: ......

Page 3: ...justment 6 4 2 Nozzles recommended 6 4 3 Electrodes setting 7 4 4 Pump pressure 7 4 5 Air damper adjustment 7 4 6 Fuel heating 7 4 7 Burner start up cycle 7 5 MAINTENANCE 8 6 FAULTS SOLUTIONS 9 O The...

Page 4: ...ent 0 7A 2850 rpm 298 rad s Capacitor 4 5 F Ignition transformer Secondary 8 kV 16 mA Pump Pressure 8 15 bar Absorbed electrical power 0 115 kW 0 170 kW 0 180 kW 0 0 4 Pressure in the combustion chamb...

Page 5: ...3 1 BOILER FIXING y Put on the flange 1 the screw and two nuts see fig 2 y Fix the flange 1 to the boiler door 4 using screws 2 and if necessary the nuts 3 interposing the insulating gasket 5 see fig...

Page 6: ...m 0 5 1 1 5 2 10 20 40 60 20 40 80 100 On the systems in fig 6 and 7 start the burner and wait for the priming Should lock out occur prior to the arrival of the fuel await at least 20 seconds before r...

Page 7: ...O NOT EXCHANGE NEUTRAL WITH PHASE WARNING Resistance PE M thermostat Ignition electrodes Neutral Capacitor L N M 50Hz 230V Oil valve D6041 CONTROL BOX Photoresistance 535SE LD Limit thermostat Motor R...

Page 8: ...d with gas oil and room temperature of 20 C 4 2 NOZZLES RECOMMENDED Delavan type W E Monarch type R NS Steinen type Q H Danfoss type S H TYPE Nozzle Pump pressure Burner output Air damper adjustment G...

Page 9: ...ermostats close and it is indicated by the ignition of an orange led placed on the control box When the required temperature for ignition is reached the thermostat fitted on the nozzle holder starts t...

Page 10: ...that there are not obstructions or dents in the supply or return oil pipes y Clean the filter in the oil suction line and in the pump y Clean the photoresistance 5 fig 1 page 1 y Check for correct fue...

Page 11: ...urner or due to the intervention of unqualified personnel FAULTS POSSIBLE CAUSES SOLUTION The burner will not start when the ad justment thermostat closes Lack of electrical supply Check presence of v...

Page 12: ...Subject to modifications RIELLO S p A I 37045 Legnago VR Tel 39 0442 630111 http www rielloburners com...

Reviews: