2661
5
3.3
ELECTRICAL WIRING
NOTES:
y
Wires of min. 1 mm
2
section.
(Unless requested otherwise by local standards and legislation).
y
The electrical wiring carried out by the installer must be in compliance with the rules in force in the Country.
TESTING:
Check the shut-down of the burner by opening the thermostats
and the lock-out by
darkening
the photoresistance.
Start
White
Black
N
eutral
Capacitor
L
N
M
~
50Hz - 230V
Oil valve
D6072
CONTROL BOX
Photoresistance
535RSE/LD
Motor
Main switch
T6A
Blue
White
Black
DO NOT EXCHANGE NEUTRAL WITH PHASE
WARNING
Resistance
PE
M
thermostat
Ignition
electrodes
Neu
tra
l
Capacitor
L
N
M
~
50Hz - 230V
Oil valve
D6041
CONTROL BOX
Photoresistance
535SE/LD
Limit thermostat
Motor
R
e
m
o
te
lo
ck
-o
ut sign
a
l
(2
30
V - 0
.5A
m
a
x.)
Main switch
T6A
Blue
White
Black
PE
Ignition
electrodes
M
CONTROL BOX (see fig. 8)
To remove the control box from the burner follow of the istruction:
y
Loosen the screw (1), open the protection (2) and remove all
components.
y
Remove the coil (3).
y
Loosen the two screws (4).
y
Move a little the control box and remove the high voltage leads.
E9150
4
4
3
1
2
Fig. 8
501T3
501T1R-2R-3R - 502T3R-5R
Safety thermostat
Safety thermostat
Limit thermostat
R
e
m
o
te
lo
ck
-o
ut sign
a
l
(2
30
V - 0
.5A
m
a
x.)
Summary of Contents for RDB1 CF 38
Page 2: ......