3) Installation information
- The installation room must be well ventilated.
- For usage in ambient temperatures of under 10°C, we recommend a winter controller
(optional equipment). For usage in ambient temperatures higher than 35°C, select the "High
Temperature Model" (Unit GEK….1). The permissible ambient temperature for this model is
45°C.
- Adequate free space must be available (see dimensions sheets) for the intake and exhaust
vents openings of the refrigeration unit.
- Before the unit is mounted, the carrying capacity of the cold room needs to be checked. The
net weight of the integrated refrigeration unit is listed in the technical information.
- Installation, repairs or alterations may only be performed by a specialized company.
- Standard units are drip-proof (protection class IP 23) and therefore suitable for interior
installation. Outdoor installation requires the use of accessory components.
- Refrigeration units in storage must be protected from moisture.
- For ambient conditions that vary, we ask you to consult us.
-
The units are maintenance free.
The ventilation slits and heat exchanger fins should be
examined regularly. Any visible dirt must be removed by cleaning, either by using a vacuum
cleaner or compressed air.
If frost formation occurs, the manual de-frost process must
be performed.
Saddle Installation
- Create the recesses with the help of the enclosed template or according to the dimension
diagram pg. 27 in the instruction manual.
- Lower the refrigeration unit.
- Attach the bracket to the inner wall of the cell according to the wall thickness.
- Open the front cover of the outer unit and attach it to the cell wall with screws.
- Close
cover
- The lamp can be mounted either on the right or the left.
- Mount condensation water drainage tubes according to the dimensions sheet pg. 27
(avoid creating a siphon)
- Seal the connecting rod at the wall openings in the cold storage cell with silicon from both
the inside and the outside. Also seal the condensation tube where it penetrates the wall.
- For wall installation W, see separate installation instructions for the wall element.
Installation of split units
Installation of outdoor unit
- Screw the cropped strip (included in delivery) to the wall. Insert the outdoor unit and
secure with bracket (included in delivery).
- Standard units are not suitable for outdoor installation (IP23). By using the "remote control"
alternative and the usage of a winter controller (see accessory components), it can be
made suitable for outdoor installation (IP44). We recommend a weather canopy provided
by the client.
- The maximum distance from the indoor unit is 10m, the maximum height difference 3m. If
these values are exceeded, the installation should be performed by a refrigeration
specialist. Minimum distances (see dimensions sheet) must be observed.