5.1 Conditions and criteria for teaching in the LogicDrive RLD200
The following conditions and criteria apply to teaching in the LogicDrive RLD200:
Control signal
Always use the 0-10 V control signal of the climate
controller to teach in the RLD200.
The voltage difference of the control signal must be at
least 2 V to teach in the RLD200.
Teach-in sequence
You can teach in the RLD200 from end position A to
end position B and vice versa.
The 0-10 V control signal may increase from A to B or
from B to A.
Minimum
movement
The minimum movement between end positions A and
B is 90° (¼ revolution) of the drive shaft.
Emergency position
To use the emergency position C, the minimum control
voltage must be higher than 1 V.
The emergency position C must be programmed
between or to one of the end positions A or B.
5.2 Operating the LogicDrive RLD200
Chapter 6 describes how to teach in the LogicDrive RLD200. This section describes the control op-
tions for teaching in the RLD200.
Teach-in
mode
The DIP switch on the control board X1 allows
you to activate the teach-in mode of the RLD200.
To do so, adjust the DIP switch in the direction of
the control buttons.
Operating
mode
The DIP switch on the control board X1 allows
you to activate the operating mode of the
RLD200. To do so, adjust the DIP switch in the
direction of the terminal strip.