RIB K500 Manual Download Page 21

21

21

G

B

4 -  The  code  programming  time  resets  automatically  so  that  you  can  programme  the  next 

remote control. 

5 -  To finish programming, let 10 seconds pass and then press the PROG. button briefly. The 

red DL1 LED will stop flashing. 

6 -  Reposition DIP 1 to OFF and DIP 2 to OFF.
7 -  You have completed the procedure

PROCEDURE  FOR  DELETING  ALL  RADIO  CODES  USED  ONLY  FOR  COMPLETE 
OPENING 

You can only delete the codes if the gate is closed. 
1 - Position DIP 1 to ON and then DIP 2 to ON.
2 -  The red programming DL1 LED will flash ON and OFF, one second on each, for 10 seconds. 
3 -  Press and hold the PROG button for 5 seconds. The green DL2 LED will flash twice to 

confirm that the stored codes have been deleted. 

4 -  The  red  programming  DL1  LED  remains  active  and  you  can  programme  new  codes  as 

shown above if required. 

5 -  Reposition DIP 1 to OFF and DIP 2 to OFF.
6 -  You have completed the procedure.

HOW  TO  CHECK  IF  THE  MEMORY  IS  FULL  FOR  RADIO  CODES  USED  ONLY  FOR 
COMPLETE OPENING 

You can only check the memory if the gate is closed. 
1 -  Position DIP 1 to ON and then DIP 2 to ON.
2 -  The green DL2 LED will flash 6 times if the memory is full (30 codes have been stored). 
3 -  After this, the DL1 programming LED will remain active for 10 seconds, so that you can 

delete all codes if required. 

4 -  Reposition DIP 1 to OFF and DIP 2 to OFF.
5 -  You have completed the procedure

POINT G

 - 

 

PROGRAMMING RADIO CODES FOR PEDESTRIAN OPENING

(UP TO 30 CODES - ONLY FOR CRX MODELS)

You can only programme the codes if the gate is closed. 
1 -  Position DIP 1 to ON and then DIP 3 to ON.
2 -  The red programming DL1 LED will flash ON and OFF, one second on each, for 10 seconds. 
3 -  Press the remote control button (normally channel B) within the 10 seconds proscribed. If 

the remote control has been correctly programmed, the DL2 LED (green) will flash once.

4 -  The  code  programming  time  resets  automatically  so  that  you  can  programme  the  next 

remote control. 

5 -  To finish programming, let 10 seconds pass and then press the PROG. button briefly. The 

red DL1 LED will stop flashing. 

6 -  Reposition DIP 1 to OFF and DIP 3 to OFF.

 

 N.B: IF THE DL1 LED CONTINUES TO FLASH RAPIDLY, THIS MEANS THAT DIP 1 IS 
STILL POSITIONED TO ON AND ANY MANOEUVRE HAS BEEN DELETED. 

7 - You have completed the procedure.

PROCEDURE  FOR  DELETING  ALL  RADIO  CODES  USED  ONLY  FOR  COMPLETE 
OPENING 

You can only delete the codes if the gate is closed. 
1 -  Position DIP 1 to ON and then DIP 3 to ON.
2 -  The red programming DL1 LED will flash ON and OFF, one second on each, for 10 seconds. 
3 -  Press and hold the PROG button for 5 seconds. The green DL2 LED will flash twice to 

confirm that the stored codes have been deleted. 

4 -  The  red  programming  DL1  LED  remains  active  and  you  can  programme  new  codes  as 

shown above if required. 

5 - Reposition DIP 1 to OFF and DIP 3 to OFF.
6 -  You have completed the procedure.

HOW  TO  CHECK  IF  THE  MEMORY  IS  FULL  FOR  RADIO  CODES  USED  ONLY  FOR 
COMPLETE OPENING 

You can only check the memory if the gate is closed. 
1 - Position DIP 1 to ON and then DIP 3 to ON.
2 -  The green DL2 LED will flash 6 times if the memory is full (30 codes have been stored). 
3 -  After this, the DL1 programming LED will remain active for 10 seconds, so that you can 

delete all codes if required. 

4 - Reposition DIP 1 to OFF and DIP 3 to OFF.
5 - You have completed the procedure.

F

UNCTIONING OF CONTROL ACCESSORIES

STEP BY STEP or AUTOMATIC commands  
(K BUTT button,  PED BUTT button, RADIO REMOTE button)
DIP 6 - ON

 

 The K BUTT,  the PED BUTT button, the RADIO REMOTE buttons perform the 
cyclic command open-stop-close-open-stop-etc.

DIP 6 - OFF

   The K BUTT,  the PED BUTT button, the RADIO REMOTE buttons perform:

 

 -  the open command, if pressed with the gate completely closed

 

 -  the close command, if pressed with the gate completely opened

 

- no effect, if pressed during the gate opening  

 

- the gate re-open, if pressed while the gate is closing

The K BUTT opens the gate completely, whereas the PED BUTT opens the gate partially as 

described in Point D.

CLOCK FUNCTION
If you want the Clock Function must request K2007 with firmware 04.
ATTENTION: A CLOCK CONNECTED TO K2007 with fw 05 or more ACTIVATES THE 
AUTOMATIC  MOVEMENT  OF  THE  GATE  WITHOUT  HAVING  THE  PROTECTION  OF 
THE SAFETY DEVICES!

The  Clock  Function  is  useful  during  rush  hours,  when  traffic  is  heavy  and  the  flow  is 
slow (e.g. entrance/exit of employees, emergencies in residential areas or car parks and, 
temporarily, for removal vans) and it’s necessary to keep the gate opened.

CLOCK FUNCTION APPLICATION
It is necessary to request a K2007 control panel with firmware 04.

Select the automatic functioning 

DIP 6 OFF

.

It can be done by connecting a switch and/or a daily/weekly clock either in parallel to the 
K  BUTT  button  or  instead  of  the  K  BUTT  button.  When  the  control  board  receives  this 
command, the gate will open and by keeping this contact closed for all the time of the gate 
opening,  the  Clock  Function  is  automatically  activated.  In  fact,  once  reached  the  open 
position, the gate will remain opened and all of the control board functions are blocked. 
Only when K BUTT contact is released, the control board functions are re-activated and 
the Automatic Closing restarts (if enabled) doing the countdown to the gate closing.

PEDESTRIAN command (PED BUTT - COM)

This  command  is  useful  to  open  the  gate  partially,  just  enough,  for  example,  to  permit  a 
pedestrian  crossing.  In  fact,  the  Pedestrian  command  (see  Point  E)  is  carried  out  only  by 
opening the gate just enough for a pedestrian to pass, as described into the Point E procedure.
From the Pedestrian opening position the Automatic Closing can be enabled or disabled with 
DIP3. 
From the Pedestrian opening position, the gate can be completely opened by the OPEN or by 
the K BUTT button or by the RADIO button.

AUTOMATIC CLOSING (from the COMPLETE open position)

The Automatic Closing from the complete open position can be enabled turning ON the DIP3.
The maximum gap of time that can be programmed is 5 minutes (see Point D).

AUTOMATIC CLOSING (from the PEDESTRIAN open position)

The Automatic Closing from the pedestrian open position can be enabled turning ON the DIP3. 
The maximum gap of time that can be programmed is 5 minutes (see Point E).

F

UNCTIONING OF SAFETY ACCESSORIES

PHOTOCELL (PHOT - COM)

In case the switch DIP4 is in the OFF position, the photocells are active both in gate opening 
and in gate closing. In this configuration, if an obstacle cuts the photocell beam:
- while the gate is closing, the gate will open
-  while the gate is opening, the gate will stop and will restart opening when the obstacle is 

removed

-  while the gate is still, it will not move neither in opening nor in closing.
In case of the switch DIP4 is in the ON position, the photocells are active only in gate closing. 
In this configuration, if an obstacle cuts the photocell beam:
- while the gate is closing, the gate will open
- while the gate is opening, the gate will continue open
-  while the gate is still, it will open if a open command is request, it will remain still if a close 

command is request.

The photocell input (PHOT - COM) is a NORMALLY CLOSED contact. 
In case there are more couple of photocells, the contacts from all the photocell receivers must 
be connected in series.
In case the photocells are not installed, this contact must be short circuited with a wire jump 
(from PHOT to COM) to permit the gate to operate.

SAFETY STRIP (EDGE - COM)

If an obstacle presses the safety strip:
- while the gate is still, it will not move neither in opening nor in closing
- while the gate is closing, the gate will open
- while the gate is opening, the gate will close.
In case the safety strip is held pressed a further quick reversion, after 2 seconds, is performed. 
The gate interrupts any movement and this 

alarm state

 will be signalled by both the Blinker 

and the Buzzer, if installed, which will remain on for 1 minute. The normal gate operations can 
be restored by pressing any push button or radio commands. 
The safety strip input (EDGE - COM) is a NORMALLY CLOSED contact. In case there are more 
than one safety strip, all their contacts must be connected in series.

In case the safety strip is not installed, this contact must be short circuited with a wire 
jump (from EDGE to COM) to permit the gate to operate.

TESTING THE SAFETY STRIP equipment 

The DIP10 ON enables to test the safety strip equipment. The test is performed every time the 

Summary of Contents for K500

Page 1: ...kg 1103 lbs ITALIANO pag 05 ENGLISH pag 15 OPERATORE IRREVERSIBILE PER CANCELLI SCORREVOLI OPERATEUR IRREVERSIBLE POUR PORTAILS COULISSANTES IRREVERSIBLE OPERATOR FOR SLIDING GATES SELBSTHEMMENDER TORANTRIEB FÜR SCHIEBETOREN OPERADOR IRREVERSIBLE PARA VERJAS CORREDERAS con avec with mit K2007 NUOVA VERSIONE con funzionamento a uomo presente se le fotocellule o le coste sono guaste Conforme alle no...

Page 2: ...INSTRUCTIONS 1 Si la centrale électrique ne dispose d aucun interrupteur il faut en installer un de type magnétothermique en amont de cette dernière omnipolaire avec ouverture minimale des contacts correspondant à 3mm la marque de cet interrupteur devra être en conformité avec les normes internationales Ce dispositif doit être protégé contre toute remise en fonction accidentelle ex en l installant...

Page 3: ...HE SAFETY OF THE PEOPLE IT IS IMPORTANT TO FOLLOW ALL THE INSTRUCTIONS INSTALLATIONSVORSCHRIFTEN BEACHTET WERDEN 1 Wenn nicht bereits an der elektrischen Schaltzentrale vorgesehen muss vor der Schaltzentrale ein thermomagnetischer Schalter installiert werden omnipolar mit einer minimalen Kontaktöffnung von 3 mm der ein von den internationalen Normen anerkanntes Konformitätszeichen besitzt Solch ei...

Page 4: ... sistema respetando las normas y las leyes vigentes SEGUIR TODAS LAS INSTRUCCIONES DE INSTALACIÓN 1 Este manual de instrucciones está exclusivamente dirigido a personal especializado que conozca los criterios de construcción y de los dispositivos de protección contra accidentes con cancelas puertas y portales motorizados atenerse a las normas y a las leyes vigentes 2 El instalador tendrá que dar a...

Page 5: ...di serratura elettrica per un efficace chiusura Il motore è protetto da una sonda termica che in caso di utilizzo prolungato interrompe momentaneamente il movimento I Misure in mm inch 1 500 400 9 5 4 230V 50Hz 60Hz 229 228 1 21 1 05 10 12 30s 2s 10 30s 2s 300 60 25 5m COMLUBE LHITGREASE EP GR 2 8 70 10 55 54 K500 CARATTERISTICHE TECNICHE Peso max cancello Forza max di spinta Coppia max Cremaglier...

Page 6: ...ettuare dopo aver tolto l alimentazione elettrica al motore Per poter agire manualmente sul cancello è sufficiente inserire l apposita chiave e ruotarla 3 volte in senso antiorario Fig 4 Per poter eseguire in modo sicuro la movimentazione manuale dell anta occorre verificare che sull anta siano presenti maniglie idonee tali maniglie siano posizionate in modo da non creare punti di pericolo durante...

Page 7: ...altezza viene fatta affinché il cancello durante il movimento non si appoggi sull ingranaggio di trazione del K500 Fig 5 e 6 Per fissare la cremagliera sul cancello eseguire dei fori di Ø 5 mm e filettarli utilizzando un maschio del tipo M6 L ingranaggio di traino deve avere circa 1 mm di agio rispetto alla cremagliera FISSAGGIO FINECORSA Per determinare la corsa della parte mobile si devono posiz...

Page 8: ...230Vac 50 Hz PASSO PASSO PEDONALE SELETTORI A CHIAVE BLOCK E PULSANTIERA FLAT FOTOCELLULE FIT SLIM COSTA MECCANICA SPARK 230Vac 40W APRE ANTENNA COMUNE COMUNE PEDONALE PASSO PASSO BUZZER 24Vdc 0 4A 15 24Vdc 0 4A 15 LED R 2K2 COSTA MECCANICA FOTOCELLULE CHIUDE AUTOTEST PER COSTA ACCESSORI ...

Page 9: ...i a 24Vdc Negativo per alimentazione accessori a 24Vdc Comune dei contatti POSITIVO Contatto impulso singolo NA Contatto fotocellule NC Contatto coste in apertura e chiusura NC Buzzer Collegamento segnalatore sonoro 24Vdc max 200 mA NEGATIVO Lampeggiatore max 40W Collegamento comune motore Collegamento invertitori e condensatore motore Connettore per collegamento sonda riscaldatore Cod ACG4665 opz...

Page 10: ...ettrico se questo non succede rilasciare il pulsante PROG ed invertire i due fili del finecorsa LSO e LSC 4 Premere il pulsante PROG e mantenerlo premuto il LED ROSSO DL5 CLOSE si accende e il cancello deve chiudere e in seguito fermarsi al contatto con il finecorsa elettrico 5 Dopo 2 sec e fino a 10 sec di lavoro consecutivi in apertura o chiusura si innesca automaticamente la frizione elettronic...

Page 11: ...gio di tipo giornaliero settimanale al posto o in parallelo al pulsante di comando n a COM K BUTTON è possibile aprire e mantenere aperta l automazione finché l interruttore viene premuto o l orologio rimane attivo Ad automazione aperta vengono inibite tutte le funzioni di comando Al rilascio dell interruttore o allo scadere dell ora impostata si avrà la chiusura immediata dell automazione PULSANT...

Page 12: ...RATTERISTICHE TECNICHE Umidità 95 senza condensazione Tensione di alimentazione 230V 10 120V 10 a richiesta Frequenza 50 60Hz Microinterruzioni di rete 20ms Potenza massima gestibile all uscita del motore 1CV Carico massimo all uscita del lampeggiatore 40W con carico resistivo Assorbimento massimo scheda esclusi accessori 33mA Corrente disponibile per le fotocellule 0 4A 15 24Vdc Grado di protezio...

Page 13: ...cod ACS9000 10 m 1 m x 10 cod ACS9001 PROBE Sonda di rilevamento temperatura ambiente motore per riscaldamento dello stesso in climi particolarmente freddi fino a 30 C collegare a connettore J8 cod ACG4665 TOUCH COSTA MECCANICA L 2 m CERTIFICATA EN 13849 2 2008 CATEGORIA 3 cod ACG3015 SUN 2CH cod ACG6052 SUN 4CH cod ACG6054 SUN CLONE 2CH cod ACG6056 SUN CLONE 4CH cod ACG6058 TELECOMANDO SUN TRASME...

Page 14: ...SENZA FILI cod ACG7064 SUPPORTO LATERALE cod ACG7042 BLOCK Wi Fi SELETTORE A CHIAVE SENZA FILI cod ACG6098 MASTER Wi Fi SCHEDA DI GESTIONE SISTEMA SENZA FILI con innesto 12 30V ac dc cod ACG6094 con morsettiera 12 30V ac dc cod ACG6099 TOUCH Wi Fi COSTA SENZA FILI cod ACG3016 Scopri gli unici automatismi senza fili su www ribind it ...

Page 15: ...temporary interrupts the operating cycle in case of prolonged use 1 500 4 230V 50Hz 60Hz 400 9 5 229 228 1 21 1 05 10 120V 60Hz 500 12 259 3 5 35 12 30s 2s 10 30s 2s 9 30s 2s 300 60 25 5m COMLUBE LHITGREASE EP GR 2 8 70 10 55 54 K500 TECHNICAL DATA Max leaf weight Rack EEC Power supply 230V Thrust force to constant turns Max torque Motor capacity Power absorbed Capacitor EEC Power supply 120V Thru...

Page 16: ...upted In order to work manually on the gate you just need to insert the fitting key and rotate it 3 times counterclockwise fig 4 In order to carry out the manual operation of the gate leaf the followings must be checked That the gate is endowed with appropriate handles That these appropriate handles are placed so to avoid safety risks for the operator That the physical effort necessary to move the...

Page 17: ...be adjusted thanks to the holes In the rack The height is adjusted to prevent the gate from resting on the driving gear of the K as it moves Fig 5 6 To fix the rack on the gate drill some Ø 5 mm holes and thread them using an M6 screw tap The driving gear needs some 1 mm clearance from the rack LIMIT SWITCH FITTING In order to determine the travel of the moving part place two cams at the ends of t...

Page 18: ... 2K2 POWER SUPPLY 230Vac 50 Hz K PEDESTRIAN KEY SELECTORS BLOCK AND PUSH BOTTON FLAT PHOTOCELLS FIT SLIM MECHANICAL SAFETY STRIP SPARK 230Vac 40W OPEN AERIAL COMMON COMMON PEDESTRIAN K BUZZER STRIP PHOTOCELLS CLOSE FOR AUTOTEST STRIP FOR ACCESSORIES SUPPLY 24Vdc 0 4A 15 24Vdc 0 4A 15 ...

Page 19: ...self test power supply Accessories power supply 24Vdc Accessories power supply 24Vdc Common contact common line for all the command and safety inputs Single pulse contact NO Photocells contact NC Safety strip contact NC Buzzer contact 24Vdc max 200 mA Flashing light max 40W Motor common connection Motor phase and capacitor connections Temperature sensor cable connection PROBE Code ACG4665 optional...

Page 20: ...NING DL5 the RED led for CLOSING When you press and hold the PROG button if the gate opens with the green led on then you may proceed to step 4 If the gate moves in the wrong direction compared with the movement leds turn OFF the main AC power reverse the V and W motor cables position the blue motor cable must be always in the U position reverse the limit switch wires marked LSO and LSC turn ON th...

Page 21: ...K2007 with fw 05 or more ACTIVATES THE AUTOMATIC MOVEMENT OF THE GATE WITHOUT HAVING THE PROTECTION OF THE SAFETY DEVICES The Clock Function is useful during rush hours when traffic is heavy and the flow is slow e g entrance exit of employees emergencies in residential areas or car parks and temporarily for removal vans and it s necessary to keep the gate opened CLOCK FUNCTION APPLICATION It is ne...

Page 22: ... LSC It is turned ON when the gate is open or partially open it is turned OFF only when the gate is completely closed N B connect in series to the indicator a resistance of 2K2 WE RECOMMEND NOT TO OVERLOAD THE INDICATORS OUTPUT OTHERWISE THE GATE FUNCTIONING COULD BE COMPROMISED OR THE CONTROL BOARD COULD BE DAMAGED TECHNICAL SPECIFICATIONS Humidity 95 without condensation Power supply voltage 230...

Page 23: ... to 1 000 kg 2 200 lbs weight 1 m 3 28 code ACS9000 10 m 32 8 1 m 3 28 x 10 code ACS9001 PROBE The probe detects the motor temperature to operate the heating system under low temperature conditions up to 30 C connect to connector J8 code ACG4665 TOUCH MECHANICAL STRIP L 2 m CERTIFIED EN 13849 2 2008 CATEGORY 3 code ACG3015 SUN 2CH code ACG6052 SUN 4CH code ACG6054 SUN CLONE 2CH code ACG6056 SUN CL...

Page 24: ... 30V ac dc code ACG6099 NOVA Wi Fi PHOTOCELLS WITHOUT WIRES code ACG8037 PAIR OF COLUMS NOVA code ACG8039 TOUCH Wi Fi STRIP WITHOUT WIRES code ACG3016 SPARK Wi Fi BLINKER WITHOUT WIRES code ACG7064 LATERAL SUPPORT code ACG7042 BLOCK Wi Fi KEY SELECTOR WITHOUT WIRES code ACG6098 Discover the only wireless automation devices at www ribind it ...

Page 25: ...25 25 NOTES ...

Page 26: ...26 26 NOTES ...

Page 27: ...Aussi rentre t il dans le champ d application de l art 6 paragraphe 2 de la Directive machines 2006 42 CEE et de ses modifications successives Sa mise en service est interdite avant que l installation ait été déclarée conforme aux dispositions prévues par la Directive This product can not work alone and was designed to be fitted into a system made up of various other elements Hence it falls within...

Page 28: ...ox Molla per sblocco Spina CIL 8x32 non temprata Spina CIL10x55 Anello di tenuta OR_158 Anello di tenuta OR2037 Paraolio 25x40x7 Guarnizione K Codice Denominazione Particolare DAC29x95 DAC39x95 DAC35x95 DAC4X10 DAC42x16 DAC5x10 DAE55x16 DDD6MA DDMM8 DDMM3Z DRD4 DRL8x26 DSB6x25 DSC3x20Z DST8x45 DTB63x25 DTE8x40 Vite aut TC CR 2 9x9 5 ZINCAT Vite aut TC CR 3 9x9 5 DIN798 Vite aut TC CR 3 5x9 5 Vite ...

Reviews: