If held when the gate is fully open (or partially when using the pedestrian control) automatic 
closing is temporarily deactivated (if activated by the TCA trimmer and LED DL11 on). It is 
therefore necessary to use a new command to make it close.
The automatic closing function is reactivated on the next cycle (if activated by the TCA 
trimmer and LED DL11 ON).

FUNCTIONING IN HOLD-TO-RUN MODE WHEN THE SAFETY DEVICES ARE FAILING

If one of the safety edges fails or remains engaged for more than 5 s, or if one of the  photocells 
fails or remain engaded for more than 60 s, the OPEN, CLOSE, START and PED. commands will 
work only in hold-to-run mode.
The signal that this mode has been activated is given by the blinking of the programming led 
DL1.
The radio commands and the automatic closing will be excluded, since their use in this mode 
is not allowed by the norms.
Once the failing safety device is repaired, in automatic after 1 second, all standard commands 
functioning again so radio commands and the automatic closing will be enabled again.

Note 1:  during this functioning in hold-to-run mode, in case of damage to the safety strips (or 

photocells) the photocells (or safety strips) still work by interrupting the operation 
in progress.

Note 2:  the stop command is not to be considered a safety command that can be bypassed 

in this mode. Therefore, when pressed or damaged, it will not allow any movement 
of the gate.

The hold-to-run mode is only an emergency operation which must be activated for a very 
short period and with the complete installation at sight so to have a secure and safe control 
of the system. As soon as possible however, the failing safety devices must be repaired and 
activated.

VISUAL AND SOUND ALARMS

BLINKER

Connect the flashing light to the blinker output, use flashing lights ACG7072 and bulbs of 40 
W maximum.

PRE-BLINKING
DIP 5 OFF =>

 motor and blinker start simultaneously.

DIP 5 ON =>

 blinker starts 3 s before the motor.

BUZZER 

It has the task to signal the intervention of the security, the anomalies and the memorization 
and cancellation of the radio codes.

SIGNAL - 24 Vdc GATE OPEN WARNING LIGHT (COM A+/SIGNAL-)

Signals when the gate is open, partially open or not closed completely. It turns OFF only when 
the gate is completely closed.
During opening, it flashes slowly.
When the gate is stationary or opened, it is permanently on.
During closing, it flashes quickly

N.B.:  Max 3 W. If warning lights are in excess, the control panel processes will be endangered 

with possible stop of all operations.

OPERATION AFTER BLACK-OUT

At the time of the blackout, gate status is saved in the memory.
When mains voltage is restored:

If the gate is located on the

 opening or closing limit switch, operating the control will close or 

open the gate with the saved data.

If the gate is in intermediate position

, operating the control will open the gate slowly until 

it reaches the opening limit switch. After completing this first movement, the operator will 
resume work at the set speed.

TECHNICAL SPECIFICATIONS

- Humidity 

 < 95% without condensation

- Power voltage 

 230V~ ±10% (120 V/60Hz upon request)  

- Frequency 

50/60Hz

- Maximum board absorption 

30 mA

- Interruptions in electricity supply 

100 ms

- Maximum load of open gate output 

 3 W (equal to 1 3 W bulb or to 5 LEDs 
connected in series through a resistor 
of from 2.2 KΩ)

- Blinking unit maximum output load 

 40 W with resistive load

- Current available for photocells and accessories 

400 mA 24 Vdc

- Current available on radio connector 

200 mA 24 Vdc

-  ALL THE PUSH BUTTONS, INPUTS AND COMMANDS CONNECTED TO THE CONTROL BOARD MUST BE 

CLEAN CONTACT.

TECHNICAL RADIO SPECIFICATIONS (Only L1-CRX)

- Reception frequency  

433,92MHz

- Impedance  

52 Ω

- Sensitivity  

>2.24µV

- Excitation time  

300 ms

- De-excitation time  

300 ms

- Codes in store  

N° 1000 total

-  All the inputs must be used as clean contacts because the power supply is generated 

internally (safe voltage) in the card and it is set in a way to guarantee the use of the double 
insulation and reinforced in relation to parts with hazardous voltage.    

-  Any external circuits connected to the outputs of the control board, must be carried out to 

make sure the double or reinforced insulation is used in relation to parts with hazardous 
voltage.

-  All the inputs are run by a programmed integrated circuit  which carries out a self-check at 

the beginning of each operation. 

MAINTENANCE CHECK

N.B.:  During this check the safety functions Edges, Photocells and Stop button are NOT active.

1 - Set 

DIP 1 to ON

 => LED DL1 starts to flash.

2 -  Press and hold the PROG button (the command is hold-to-run, open-stop-close-stop-open-

etc ...) => The gate starts at high speed and then slow down until the limit switch is reached.

3 -  At the end, put 

DIP 1 back to OFF

. The DL1 LED turn OFF signaling the exit from the check.

If the motor does not work during this check, check the connections and its capacitor.
If the motor is working properly, check the safety devices.

TROUBLE SHOOTING

After having carried out all connections, by carefully following the layout and having positioned 
the gate in intermediate position, check the correct ignition of red LEDS DL6, DL7, DL8, DL9 
and DL10.
In case of no ignition of the LEDS, always with gate in intermediate position, check the following 
and replace any faulty components.
DL6 

OFF   Stop button malfunction (if Stop is not connected, perform the jump 

between COM A+ and STOP).

DL7 or DL8 

OFF   Faulty photocells (In case the edge is not connected, carry out jumper 

between COM A+ and PHOTO 1/PHOTO 2)

DL9 or DL10  OFF   Faulty safety edge (In case the edge is not connected, carry out jumper 

between COM A+ and EDGE 1/EDGE 2)

DL13 blue 

ON 

 Some functions are enabled via smartphone, so via smartphone check 
the card functions as the dips/trimmers status may not be true.

On the board there are resettable fuses which intervene in the event of a short circuit, 
interrupting the output assigned to them.
In the event of troubleshooting, it is advisable to disconnect all the removable connectors and 
insert them one at a time in order to more easily identify the cause of the fault.

G

B

Summary of Contents for AA31020

Page 1: ...24 Il corretto funzionamento dell operatore garantito solo se viene gestito da un quadro di comando RIB Le bon fonctionnement de l op rateur n est garanti que s il est g r par un panneau de contr le R...

Page 2: ...ovocati dalla mancata osservanza nell installazione delle norme di sicurezza e delle leggi attualmente in vigore ATTENTION POUR LA SECURITE DES PERSONNES IL EST IMPORTANT DE SUIVRE TOUTES LES INSTRUCT...

Page 3: ...s caused by the non observance during the installation of the safety standards and of the laws in force at present ACHTUNG F R DIE SICHERHEIT DER PERSONEN IST ES WICHTIG DASS ALLE ANWEISUNGEN GENAU AU...

Page 4: ...dell acquisto di una nuova apparecchiatura di tipo equivalente Presso i distributori di prodotti elettronici con superficie di vendita di almeno 400 m2 inoltre possibile consegnare gratuitamente senz...

Page 5: ...icace chiusura Il motore protetto da una sonda termica che in caso di utilizzo prolungato interrompe momentaneamente il movimento Misure in mm 1 CARATTERISTICHE TECNICHE SUPER 3600 Peso max cancello k...

Page 6: ...ersone esperte fuori da area pubblica Persone esperte area pubblica Persone non esperte mantenuto A B non possibile impulsivo in vista es pulsante C o E C o E C e D o E impulsivo non in vista es telec...

Page 7: ...a posizionare a vista i due finecorsa F agendo sui pomoli P Dopo aver verificato il corretto funzionamento elettrico dei due microswitches si perfeziona la loro posizione fino ad ottenere l arresto in...

Page 8: ...2 FOTOCELLULA 2 COSTA 1 24Vdc 0 4A 15 24Vdc 0 4A 15 A TEST A AUTOTEST FOTOCELLULE ANTENNA 433 MHz SCHERMATURA CAVO D ANTENNA 700 W MAX CHIUDE APRE COMUNE ALIMENTAZIONE 230Vac 50 Hz CONDENSATORE COLLE...

Page 9: ...J7 COM A Comune dei contatti Positivo 24 Vdc LIMIT SWITCH Contatti finecorsa che fermano il motore J8 PROBE NON DISPONIBILE J9 ENCODER NON DISPONIBILE J10 Terminazione RS485 di J11 J11 APP Connettore...

Page 10: ...PHOT1 PHOT2 EDGE1eEDGE2nonsonocollegati eseguiredeiponticellitra COMA STOP PHOT1 PHOT2 EDGE1 EDGE2primadiprocedereconlaprogrammazione N B In questo caso le sicurezza Costa Fotocellule e Pulsante di st...

Page 11: ...su ON e poi il DIP 3 su ON Il led DL12 lampeggia arancio per 10 s 2 Entro questi 10 s premere e mantenere premuto il pulsante PROG per 5 s La conferma della cancellazione della memoria viene segnalat...

Page 12: ...ore ed il lampeggiatore partono contemporaneamente DIP 5 ON Il lampeggiatore parte 3 secondi prima del motore BUZZER Ha il compito di segnalare l intervento delle sicurezze lo stato degli allarmi e lo...

Page 13: ...rogrammazione codici radio per rel R AUX spento Spento Lampeggia arancio per 10 s Programmazione corretta dei codici radio per apertura totale e R AUX 1 Tono Spento Si accende verde una volta Programm...

Page 14: ...tocellule fallito verificare i collegamenti tra quadro elettronico e fotocellule Il cancello non apre e non chiude azionando i vari pulsanti START RADIO OPEN e CLOSE Contatto costa guasto Contatto fot...

Page 15: ...e la centrale tramite rete Wi Fi locale WLAN APP8066 Modulo RJ45 per Scheda APP per gestire la centrale tramite rete dati locale LAN NOVA NOVA WIRELESS EN12978 EN13849 2 FOTOCELLULE NOVA portata 25 m...

Page 16: ...RE RADIO RED per costa meccanica o elettrica da alimentare con 3 batterie stilo tipo AA da 1 5V non incluse RED permette la realizzazione di un impianto con coste fissate anche sull anta in movimento...

Page 17: ...serrure lectrique pour une fermeture efficace Le moteur est prot g par une sonde thermique qui interrompt momentan ment le mouvement en cas de non utilisation prolong e Mesures en mm 1 CARACTERISTIQU...

Page 18: ...EDECOMMANDE USAGE DE LA FERMETURE Personne expertes zone sans publique Personne expertes zone avec publique Personnes non expertes homme presente A B Pas possible impulsion en vue ex bouton C ou E C o...

Page 19: ...cameHenouvertureetenfermeture positionner vue les deux fins de course F en agissant sur les pommeaux P Apr s avoir contr l le fonctionnement lectrique correct des deux microinterrupteurs parfaire leur...

Page 20: ...R 2 2K 1 4W COMMUN COMMUN COMMUN COMMUN CORDON 2 PHOTOCELLULES 2 CORDON 1 A TEST A AUTOTEST PHOTOCELULES ANTENNE 433 MHz ENVELOPPE ANTENNE 24Vdc 0 4A 15 24Vdc 0 4A 15 700 W MAX FERMETURE OUVERTURE CO...

Page 21: ...llules 2 NF EDGE 1 Contact barres palpeuse 1 NF EDGE 2 Contact barres palpeuse 2 NF J7 COM A Commun des contacts Positif 24 Vdc LIMIT SWITCH Contact fin de course qui arr te la fermeture du moteur J8...

Page 22: ...nt actives et leur niveau de performance est PL c selon EN13849 1 leur intervention arr te la programmation le led DL1 reste allum N B Si les entr es STOP PHOT 1 PHOT 2 EDGE 1 et EDGE 2 ne sont pas co...

Page 23: ...ivante 3 Pour terminer la programmation laisser s couler 10 sec ou bien appuyer pendant un instant sur le bouton PROG La LED DL12 arr te de clignoter 4 Repositionner DIP 1 2 et 3 sur OFF PROCEDURE D E...

Page 24: ...commande maintenue est exclusivement une manoeuvre d urgence qui doit tre effectu e pour des temps brefs et avec la s curit de la vue quand l op rateur est en mouvement D s possible les protections e...

Page 25: ...totest de la photocellule est n gatif v rifier les connexions entre le tableau et la le photocellule s En actionnant le bouton START OPEN ou CLOSE le portail n effectue aucun mouvement Impulsion START...

Page 26: ...ssion codes ouverture totale pi ton et R AUX 2 Tonalit s teint Effectue 2 clignotements verts SIGNALISATIONS PENDANT LE FONCTIONNEMENT V NEMENT TAT BUZZER TAT CLIGNOTEUR TAT LED ET SORTIE SIGNAL Bouto...

Page 27: ...le tableau de contr le via Bluetooth 4 2 APP8064 Module Wi Fi pour Carte APP pour g rer le tableau de contr le via un r seau Wi Fi local WLAN APP8066 Module RJ45 pour Carte APP pour g rer le tableau...

Page 28: ...NSMETTEUR RADIO RED pour barre palpeuse m canique ou lectrique alimenter par 3 piles de type AA de 1 5V non comprise RED permet la r alisation d une installation avec barres palpeuses fix es galement...

Page 29: ...D Key selector E Tuned aerial F Flashing lamp H Galvanized column for P E cells I Photo electric cells internal L Safety strip fixed to column M Mecanichal or electrical safety strip with RED transmit...

Page 30: ...ing to EN 12453 standard COMMAND TYPE USE OF THE SHUTTER Skilled persons out of public area Skilled persons public area Notskilled persons Hold to run operation A B Not possible Impulsive in sight e g...

Page 31: ...he two limit switches F by turning knobs P and judging by sight After checking for correct operation of the two microswitches precisely adjust their positions so that the gate will stop in the desired...

Page 32: ...R 2 2K 1 4W COMMON COMMON COMMON COMMON EDGE 2 PHOTOCELL 2 EDGE 1 A TEST A PHOTOCELLS AUTO TEST ANTENNA 433 MHz ANTENNA BRAIDING 24Vdc 0 4A 15 24Vdc 0 4A 15 700 W MAX CLOSE OPEN COMMON POWER SUPPLY 2...

Page 33: ...ells contact 2 NC EDGE 1 Edge 1 contact NC EDGE 2 Edge 2 contact NC J7 COM A Common contacts Positive 24 Vdc LIMIT SWITCH Limit switches that cuts OFF the motor J8 PROBE IS NOT AVAILABLE J9 ENCODER IS...

Page 34: ...fety Edge Photocells and Stop button will be ignored N B The start slow down point is automatically determined in the time programming phase and 50 60 cm is activated before reaching the opening or cl...

Page 35: ...useful during peak hours when vehicle traffic is slow e g entry exit of workers emergencies in parking or residential areas and temporarily for moving operations By connecting a switch and or a daily...

Page 36: ...this first movement the operator will resume work at the set speed TECHNICAL SPECIFICATIONS Humidity 95 without condensation Power voltage 230V 10 120 V 60Hz upon request Frequency 50 60Hz Maximum bo...

Page 37: ...ne OFF Turns red once Remote control code not present in memory OFF OFF Turns red once Memory saturated by remote control codes 1000 codes saved OFF OFF Runs 6 green flashes Radio code deletion for fu...

Page 38: ...check the connections between the control panel and the photocells The gate does not open or close by activating the various START RADIO OPEN and CLOSE buttons Faulty safety edge contact Faulty photoc...

Page 39: ...panel APP8064 Wi Fi module for APP card to manage the control panel using the local Wi Fi network WLAN APP8066 RJ45 module for APP card to manage the control panel using the local network LAN NOVA NOV...

Page 40: ...OUT WIRES code ACG3016 RED RADIO TRANSMITTER for mechanical and electrical safety strip Batteries not included RED allows to make a system made with edges fixed to the moving shutter without having to...

Page 41: ...riegelung kein elektrisches Sicherheitsschloss Der Motor wird durch eine thermische Sonde gesch tzt die im Fall eines langen Einsatzes momentan die Bewegung unterbricht Abmessungen in mm 1 TECHNISCHE...

Page 42: ...ntlichen Bereichs Erfahrene Personen ffentlicher Bereich Nicht fachkundige Personen Gedr ckt halten A B nicht m glich Impulsiv in Sicht z B Wandtaster C oder E C oder E C und D oder E impulsiv au er S...

Page 43: ...schalter F durch Bet tigung der Kn pfe P auf Sicht zu positionieren Nach berpr fung der beiden Mikroschalter auf deren korrekte Funktionsweise Elektrik ist ihre Position genau einzustellen bis der Sto...

Page 44: ...NGSKONTAKT GEMEINSAMER ERDUNGSKONTAKT GEMEINSAMER GEMEINSAMER KONTAKTLEISTE 2 FOTOZELLE 2 KONTAKTLEISTE 1 A TEST A AUTOTEST FOTOZELLEN ANTENNE 433 MHz ANTENNE ZOPFFLECHTEN 24Vdc 0 4A 15 24Vdc 0 4A 15...

Page 45: ...en Kontakt 1 NS PHOT 2 Fotozellen Kontakt 2 NS EDGE 1 Ripppen Kontakt 1 NS EDGE 2 Ripppen Kontakt 2 NS J7 COM A Gemeinsame erdungskontakte Positive 24 Vdc LIMIT SWITCH Steckverbinder f r elektrische o...

Page 46: ...die Programmierung die LED DL1 blinkt nicht mehr N B Wenn die Eing nge STOP PHOT 1 PHOT 2 EDGE 1 und EDGE 2 nicht angeschlossen sind stellen Sie die Jumper zwischen COM A STOP PHOT 1 PHOT 2 EDGE 1 EDG...

Page 47: ...ieser 10 s dr cken und halten Sie die PROG Taste f r 5 s Die Speicherl schung wird durch zwei gr ne Blinksignale der LED DL12 und zwei Signalt ne des Summers angezeigt 3 Die LED DL12 blinkt erneut f r...

Page 48: ...ausgang Verwenden Sie Blinklichter ACG7072 von maximal 40 W FUNKTION VORBLINKEN DIP 5 OFF Motor und Blinker starten gleichzeitig DIP 5 ON Blinker startet 3 s vor dem Motor SUMMER EshatdieAufgabe dasEi...

Page 49: ...DIO OPEN und CLOSE Tasten nicht Kontakt dek Kontaktleiste Schaden Kontakt Fotozellen Schaden mit DIP 4 OFF Reparieren oder ersetzen Sie den fehlerhaften Kontakt Fotozellen Auto Test fehlgeschlagen ber...

Page 50: ...unkcodes f r voll ffnung fussg nger ffnung R AUX relais 2 T ne Abgeschaltet Blinkt 2 mal gr n SIGNALISIERUNGEN W HREND DES BETRIEBS EREIGNIS STATUS BUZZER STATUS BLINKLEUCHTE LEDZUSTAND UND AUSGANGSSI...

Page 51: ...rte um Zugriff auf das Steuerungen hinzuzuf gen APP8064 WLAN Modul f r APP Karte Verwalten des Steuerung ber das lokale Wi Fi Netzwerk WLAN APP8066 RJ45 Modul f r APP Karte Verwalten der Steuerung ber...

Page 52: ...der elektrische Kontaktleiste Versorgung mit Mignon Batterien vom Typ AA zu 1 5V nicht im Lieferumfang enthalten RED erlaubt die Realisierung einer Anlage mit Kontaktleisten die auch auf dem sich bewe...

Page 53: ...radura el ctrica para un cierre eficaz El motor est protegido por una sonda t rmica que en caso de uso prolongado interrumpe moment neamente el movimiento Medidas en mm 1 CARACTER STICAS T CNICAS SUPE...

Page 54: ...sonas expertas fuera de un rea p blica Personas expertas rea p blica Personas no expertas mantenido A B non posivel impulsivo a la vista por ejemplo bot n C o E C o E C e D o E impulsivo no a la vista...

Page 55: ...ovimiento de la camme H ya sea en abertura que en cierre posicionar en vista los dos finales de carrera F operando con los p mulos P Despu s de haber verificado el correcto funcionamiento el ctrico de...

Page 56: ...LED R 2 2K 1 4W COM N COM N COM N COM N BANDA 2 FOTOC LULA 2 BANDA 1 A TEST A AUTOPRUEBA DE FOTOC LULAS ANTENA 433 MHz ARMADURA ANTENA 24Vdc 0 4A 15 24Vdc 0 4A 15 700 W MAX CIERRE ABRE COM N ALIMENTAC...

Page 57: ...ulas 1 NC PHOT 2 Contacto de las fotoc lulas 2 NC EDGE 1 Contacto banda de seguridad 1 NC EDGE 2 Contacto banda de seguridad 2 NC J7 COM A Com n de los contactos Positivo 24 Vdc LIMIT SWITCH Contactos...

Page 58: ...nci n detiene la programaci n el led DL1 del destello permanece iluminado constantemente N B Si las entradas de parada PHOT 1 PHOT 2 EDGE 1 y EDGE 2 no est n conectados realice puente entre COM A STOP...

Page 59: ...para poder memorizar el mando a distancia sucesivo 3 Para terminar la programaci n deje transcurrir 10 s o presione por un instante el pulsador PROG El led DL12 deja de parpadear 4 Vuelva a colocar e...

Page 60: ...ridad que se puede bypasar en este funcionamiento y por lo tanto si viene apretrado o se rompe no permite alg n movimiento del port n La maniobra con mando mantenido presionado es exclusivamente una m...

Page 61: ...CI N Despu s de haber efectuado varias conexiones y haber dado tensi n todos los led est n apagados En el cuadro hay fusibles reajustables que intervienen en caso de cortocircuito que interrumpa la sa...

Page 62: ...r c digos de radio 1000 c digos memorizados Apagado Apagado Realiza 6 parpadeos verdes Anulaci n c digos radio de apertura total peatonal y R AUX 2 Tonos Apagado Realiza 2 parpadeos verdes SE ALIZACIO...

Page 63: ...de control a trav s de Bluetooth 4 2 APP8064 M dulo wi fi para Tarjeta APP para administrar el panel de control a trav s de una red Wi Fi local WLAN APP8066 M dulo RJ45 para Tarjeta APP para administr...

Page 64: ...ja en movimiento sin la adopci n de sistemas recoge cables Conforme a la norma EN13849 1 2007 Unido a un cuadro electr nico RIB es un dispositivo de protecci n de Clase 2 c d ACG6202 E S NOVA NOVA WIR...

Page 65: ...self test 2 Fotozellen FIT SLIM FIT SYNCRO mit Selbstkontrolle 2 fotoc lulas FIT SLIM FIT SYNCRO con autotest 2 fotocellule F97P F97I con autotest 2 photocellules F97P F97I avec autotest 2 photocells...

Page 66: ...UTOTEST est activ e et qu une seule photocellule est connect e un cavalier doit tre cr entre les bornes PHOT 1 et PHOT 2 Si le cavalier n est pas ex cut l autotest choue et le portail ne bouge pas WAR...

Page 67: ...forzo Super CCA1215 Protezione ingranaggio SUPER CCU6207 Cuscinetto 6207 35x72x17 CCU6307 Cuscinetto 6307 35x80x21 CEL1433 Pressacavo CAL1437 Condensatore 50 F 470V CME1034 Albero traino Super CME1063...

Page 68: ...t ndigen nationalen Beh rden Diese unvollst ndige Maschine in bereinstimmung mit den Bestimmungen der folgenden anderen CE Richtlinien Richtlinien 2014 30 UE 2014 35 UE und 2014 53 UE Alle grundlegend...

Reviews: