30

G

B

INSTALLATION SUPER 3600

2

3

4

2”

2”

CHECKING BEFORE THE INSTALLATION

!! THE GATE SHALL MOVE FRICTIONLESS !!

N.B.:  

Gate features must be uniformed with the standards and laws in force. The door/gate 
can be automated only if it is in a good condition and its conditions comply with the 
BS EN 12604 norm.

-  The door/gate leaf does not have to have a pedestrian opening. In the opposite case it is 

necessary to take the appropriate steps, in accordance with BS EN 12453 point 6.5.1 (for 
instance; by preventing the operation of the motor when the pedestrian opening is opened, 
by installing a safety microswitch connected with the control panel).

-  Besides the electrical or mechanical limit switches available on the operators, there must 

be, on both ends of the installation, a fixed mechanical stopper which stop the gate in the 
unlikely event of ill functioning of limit swithces on the operators. For this reason the fixed 
mechanical stopper must be of an adeguate size to withstand the static and kinetic forces 
generated by the gate (12) (Fig.2).The guide must be provided with two mechanical stops 
at its ends (12) (Fig. 2). 

-  Gate columns shall have anti-derailment  guides on their top (Fig. 3), to avoid the 

unintentional gate release.  

N.B.:

  Eliminate those mechanical stops of the kind described by figure 3. 

No mechanical stop shall be on top of the gate, since mechanical stops are not safe enough.

Parts to install according to EN 12453 standard

COMMAND TYPE

USE OF THE SHUTTER

Skilled persons

(out of public area*)

Skilled persons

(public area)

Not skilled 

persons

Hold-to-run operation

A

B

Not possible

Impulsive - in sight 
(e.g. push-button)

C or E

C or E

C and D, or E

impulsive - out of sight 
(e.g. remote)

C or E

C and D, or E

C and D, or E

automatic

C and D, or E

C and D, or E

C and D, or E

* a typical example are those doors which do not have access to any public way
A:  Hold-to-run operation made by push-button ex: code ACG2013
B: Hold-to-run operation made by key selector ex: code ACG1010
C:  Adjustable power of the motor or photocells to respect impact forces as indicated in 

Annex A

D:  Safety strips and/or other additional devices to reduce the probability of contact with 

the door.

E:  Devices installed in such a way that a person can not be touched by the door.

EMERGENCY RELEASE

To be undertaken after disconnecting power supply.

The operator is irreversible and keeps the door closed even without a lockset. 
To open the gate manually, in open the motor cover and turn the knob «A» anti-clockwise. 
To restore electric working you have to turn the lever clockwise (Fig. 4).
In order to carry out the manual operation of the gate leaf the followings must be checked:
- That the gate is endowed with appropriate handles;
-  That these appropriate handles are placed so to avoid safety risks for the operator; 
-  That the physical effort necessary to move the gate leaf should not be higher than 225 

N, for doors/gates for private dwellings, and, 390 N for doors/gates for commercial and 
industrial sites ( values indicated in 5.4.5 of the EN 12453 norm).

Summary of Contents for AA31020

Page 1: ...24 Il corretto funzionamento dell operatore garantito solo se viene gestito da un quadro di comando RIB Le bon fonctionnement de l op rateur n est garanti que s il est g r par un panneau de contr le R...

Page 2: ...ovocati dalla mancata osservanza nell installazione delle norme di sicurezza e delle leggi attualmente in vigore ATTENTION POUR LA SECURITE DES PERSONNES IL EST IMPORTANT DE SUIVRE TOUTES LES INSTRUCT...

Page 3: ...s caused by the non observance during the installation of the safety standards and of the laws in force at present ACHTUNG F R DIE SICHERHEIT DER PERSONEN IST ES WICHTIG DASS ALLE ANWEISUNGEN GENAU AU...

Page 4: ...dell acquisto di una nuova apparecchiatura di tipo equivalente Presso i distributori di prodotti elettronici con superficie di vendita di almeno 400 m2 inoltre possibile consegnare gratuitamente senz...

Page 5: ...icace chiusura Il motore protetto da una sonda termica che in caso di utilizzo prolungato interrompe momentaneamente il movimento Misure in mm 1 CARATTERISTICHE TECNICHE SUPER 3600 Peso max cancello k...

Page 6: ...ersone esperte fuori da area pubblica Persone esperte area pubblica Persone non esperte mantenuto A B non possibile impulsivo in vista es pulsante C o E C o E C e D o E impulsivo non in vista es telec...

Page 7: ...a posizionare a vista i due finecorsa F agendo sui pomoli P Dopo aver verificato il corretto funzionamento elettrico dei due microswitches si perfeziona la loro posizione fino ad ottenere l arresto in...

Page 8: ...2 FOTOCELLULA 2 COSTA 1 24Vdc 0 4A 15 24Vdc 0 4A 15 A TEST A AUTOTEST FOTOCELLULE ANTENNA 433 MHz SCHERMATURA CAVO D ANTENNA 700 W MAX CHIUDE APRE COMUNE ALIMENTAZIONE 230Vac 50 Hz CONDENSATORE COLLE...

Page 9: ...J7 COM A Comune dei contatti Positivo 24 Vdc LIMIT SWITCH Contatti finecorsa che fermano il motore J8 PROBE NON DISPONIBILE J9 ENCODER NON DISPONIBILE J10 Terminazione RS485 di J11 J11 APP Connettore...

Page 10: ...PHOT1 PHOT2 EDGE1eEDGE2nonsonocollegati eseguiredeiponticellitra COMA STOP PHOT1 PHOT2 EDGE1 EDGE2primadiprocedereconlaprogrammazione N B In questo caso le sicurezza Costa Fotocellule e Pulsante di st...

Page 11: ...su ON e poi il DIP 3 su ON Il led DL12 lampeggia arancio per 10 s 2 Entro questi 10 s premere e mantenere premuto il pulsante PROG per 5 s La conferma della cancellazione della memoria viene segnalat...

Page 12: ...ore ed il lampeggiatore partono contemporaneamente DIP 5 ON Il lampeggiatore parte 3 secondi prima del motore BUZZER Ha il compito di segnalare l intervento delle sicurezze lo stato degli allarmi e lo...

Page 13: ...rogrammazione codici radio per rel R AUX spento Spento Lampeggia arancio per 10 s Programmazione corretta dei codici radio per apertura totale e R AUX 1 Tono Spento Si accende verde una volta Programm...

Page 14: ...tocellule fallito verificare i collegamenti tra quadro elettronico e fotocellule Il cancello non apre e non chiude azionando i vari pulsanti START RADIO OPEN e CLOSE Contatto costa guasto Contatto fot...

Page 15: ...e la centrale tramite rete Wi Fi locale WLAN APP8066 Modulo RJ45 per Scheda APP per gestire la centrale tramite rete dati locale LAN NOVA NOVA WIRELESS EN12978 EN13849 2 FOTOCELLULE NOVA portata 25 m...

Page 16: ...RE RADIO RED per costa meccanica o elettrica da alimentare con 3 batterie stilo tipo AA da 1 5V non incluse RED permette la realizzazione di un impianto con coste fissate anche sull anta in movimento...

Page 17: ...serrure lectrique pour une fermeture efficace Le moteur est prot g par une sonde thermique qui interrompt momentan ment le mouvement en cas de non utilisation prolong e Mesures en mm 1 CARACTERISTIQU...

Page 18: ...EDECOMMANDE USAGE DE LA FERMETURE Personne expertes zone sans publique Personne expertes zone avec publique Personnes non expertes homme presente A B Pas possible impulsion en vue ex bouton C ou E C o...

Page 19: ...cameHenouvertureetenfermeture positionner vue les deux fins de course F en agissant sur les pommeaux P Apr s avoir contr l le fonctionnement lectrique correct des deux microinterrupteurs parfaire leur...

Page 20: ...R 2 2K 1 4W COMMUN COMMUN COMMUN COMMUN CORDON 2 PHOTOCELLULES 2 CORDON 1 A TEST A AUTOTEST PHOTOCELULES ANTENNE 433 MHz ENVELOPPE ANTENNE 24Vdc 0 4A 15 24Vdc 0 4A 15 700 W MAX FERMETURE OUVERTURE CO...

Page 21: ...llules 2 NF EDGE 1 Contact barres palpeuse 1 NF EDGE 2 Contact barres palpeuse 2 NF J7 COM A Commun des contacts Positif 24 Vdc LIMIT SWITCH Contact fin de course qui arr te la fermeture du moteur J8...

Page 22: ...nt actives et leur niveau de performance est PL c selon EN13849 1 leur intervention arr te la programmation le led DL1 reste allum N B Si les entr es STOP PHOT 1 PHOT 2 EDGE 1 et EDGE 2 ne sont pas co...

Page 23: ...ivante 3 Pour terminer la programmation laisser s couler 10 sec ou bien appuyer pendant un instant sur le bouton PROG La LED DL12 arr te de clignoter 4 Repositionner DIP 1 2 et 3 sur OFF PROCEDURE D E...

Page 24: ...commande maintenue est exclusivement une manoeuvre d urgence qui doit tre effectu e pour des temps brefs et avec la s curit de la vue quand l op rateur est en mouvement D s possible les protections e...

Page 25: ...totest de la photocellule est n gatif v rifier les connexions entre le tableau et la le photocellule s En actionnant le bouton START OPEN ou CLOSE le portail n effectue aucun mouvement Impulsion START...

Page 26: ...ssion codes ouverture totale pi ton et R AUX 2 Tonalit s teint Effectue 2 clignotements verts SIGNALISATIONS PENDANT LE FONCTIONNEMENT V NEMENT TAT BUZZER TAT CLIGNOTEUR TAT LED ET SORTIE SIGNAL Bouto...

Page 27: ...le tableau de contr le via Bluetooth 4 2 APP8064 Module Wi Fi pour Carte APP pour g rer le tableau de contr le via un r seau Wi Fi local WLAN APP8066 Module RJ45 pour Carte APP pour g rer le tableau...

Page 28: ...NSMETTEUR RADIO RED pour barre palpeuse m canique ou lectrique alimenter par 3 piles de type AA de 1 5V non comprise RED permet la r alisation d une installation avec barres palpeuses fix es galement...

Page 29: ...D Key selector E Tuned aerial F Flashing lamp H Galvanized column for P E cells I Photo electric cells internal L Safety strip fixed to column M Mecanichal or electrical safety strip with RED transmit...

Page 30: ...ing to EN 12453 standard COMMAND TYPE USE OF THE SHUTTER Skilled persons out of public area Skilled persons public area Notskilled persons Hold to run operation A B Not possible Impulsive in sight e g...

Page 31: ...he two limit switches F by turning knobs P and judging by sight After checking for correct operation of the two microswitches precisely adjust their positions so that the gate will stop in the desired...

Page 32: ...R 2 2K 1 4W COMMON COMMON COMMON COMMON EDGE 2 PHOTOCELL 2 EDGE 1 A TEST A PHOTOCELLS AUTO TEST ANTENNA 433 MHz ANTENNA BRAIDING 24Vdc 0 4A 15 24Vdc 0 4A 15 700 W MAX CLOSE OPEN COMMON POWER SUPPLY 2...

Page 33: ...ells contact 2 NC EDGE 1 Edge 1 contact NC EDGE 2 Edge 2 contact NC J7 COM A Common contacts Positive 24 Vdc LIMIT SWITCH Limit switches that cuts OFF the motor J8 PROBE IS NOT AVAILABLE J9 ENCODER IS...

Page 34: ...fety Edge Photocells and Stop button will be ignored N B The start slow down point is automatically determined in the time programming phase and 50 60 cm is activated before reaching the opening or cl...

Page 35: ...useful during peak hours when vehicle traffic is slow e g entry exit of workers emergencies in parking or residential areas and temporarily for moving operations By connecting a switch and or a daily...

Page 36: ...this first movement the operator will resume work at the set speed TECHNICAL SPECIFICATIONS Humidity 95 without condensation Power voltage 230V 10 120 V 60Hz upon request Frequency 50 60Hz Maximum bo...

Page 37: ...ne OFF Turns red once Remote control code not present in memory OFF OFF Turns red once Memory saturated by remote control codes 1000 codes saved OFF OFF Runs 6 green flashes Radio code deletion for fu...

Page 38: ...check the connections between the control panel and the photocells The gate does not open or close by activating the various START RADIO OPEN and CLOSE buttons Faulty safety edge contact Faulty photoc...

Page 39: ...panel APP8064 Wi Fi module for APP card to manage the control panel using the local Wi Fi network WLAN APP8066 RJ45 module for APP card to manage the control panel using the local network LAN NOVA NOV...

Page 40: ...OUT WIRES code ACG3016 RED RADIO TRANSMITTER for mechanical and electrical safety strip Batteries not included RED allows to make a system made with edges fixed to the moving shutter without having to...

Page 41: ...riegelung kein elektrisches Sicherheitsschloss Der Motor wird durch eine thermische Sonde gesch tzt die im Fall eines langen Einsatzes momentan die Bewegung unterbricht Abmessungen in mm 1 TECHNISCHE...

Page 42: ...ntlichen Bereichs Erfahrene Personen ffentlicher Bereich Nicht fachkundige Personen Gedr ckt halten A B nicht m glich Impulsiv in Sicht z B Wandtaster C oder E C oder E C und D oder E impulsiv au er S...

Page 43: ...schalter F durch Bet tigung der Kn pfe P auf Sicht zu positionieren Nach berpr fung der beiden Mikroschalter auf deren korrekte Funktionsweise Elektrik ist ihre Position genau einzustellen bis der Sto...

Page 44: ...NGSKONTAKT GEMEINSAMER ERDUNGSKONTAKT GEMEINSAMER GEMEINSAMER KONTAKTLEISTE 2 FOTOZELLE 2 KONTAKTLEISTE 1 A TEST A AUTOTEST FOTOZELLEN ANTENNE 433 MHz ANTENNE ZOPFFLECHTEN 24Vdc 0 4A 15 24Vdc 0 4A 15...

Page 45: ...en Kontakt 1 NS PHOT 2 Fotozellen Kontakt 2 NS EDGE 1 Ripppen Kontakt 1 NS EDGE 2 Ripppen Kontakt 2 NS J7 COM A Gemeinsame erdungskontakte Positive 24 Vdc LIMIT SWITCH Steckverbinder f r elektrische o...

Page 46: ...die Programmierung die LED DL1 blinkt nicht mehr N B Wenn die Eing nge STOP PHOT 1 PHOT 2 EDGE 1 und EDGE 2 nicht angeschlossen sind stellen Sie die Jumper zwischen COM A STOP PHOT 1 PHOT 2 EDGE 1 EDG...

Page 47: ...ieser 10 s dr cken und halten Sie die PROG Taste f r 5 s Die Speicherl schung wird durch zwei gr ne Blinksignale der LED DL12 und zwei Signalt ne des Summers angezeigt 3 Die LED DL12 blinkt erneut f r...

Page 48: ...ausgang Verwenden Sie Blinklichter ACG7072 von maximal 40 W FUNKTION VORBLINKEN DIP 5 OFF Motor und Blinker starten gleichzeitig DIP 5 ON Blinker startet 3 s vor dem Motor SUMMER EshatdieAufgabe dasEi...

Page 49: ...DIO OPEN und CLOSE Tasten nicht Kontakt dek Kontaktleiste Schaden Kontakt Fotozellen Schaden mit DIP 4 OFF Reparieren oder ersetzen Sie den fehlerhaften Kontakt Fotozellen Auto Test fehlgeschlagen ber...

Page 50: ...unkcodes f r voll ffnung fussg nger ffnung R AUX relais 2 T ne Abgeschaltet Blinkt 2 mal gr n SIGNALISIERUNGEN W HREND DES BETRIEBS EREIGNIS STATUS BUZZER STATUS BLINKLEUCHTE LEDZUSTAND UND AUSGANGSSI...

Page 51: ...rte um Zugriff auf das Steuerungen hinzuzuf gen APP8064 WLAN Modul f r APP Karte Verwalten des Steuerung ber das lokale Wi Fi Netzwerk WLAN APP8066 RJ45 Modul f r APP Karte Verwalten der Steuerung ber...

Page 52: ...der elektrische Kontaktleiste Versorgung mit Mignon Batterien vom Typ AA zu 1 5V nicht im Lieferumfang enthalten RED erlaubt die Realisierung einer Anlage mit Kontaktleisten die auch auf dem sich bewe...

Page 53: ...radura el ctrica para un cierre eficaz El motor est protegido por una sonda t rmica que en caso de uso prolongado interrumpe moment neamente el movimiento Medidas en mm 1 CARACTER STICAS T CNICAS SUPE...

Page 54: ...sonas expertas fuera de un rea p blica Personas expertas rea p blica Personas no expertas mantenido A B non posivel impulsivo a la vista por ejemplo bot n C o E C o E C e D o E impulsivo no a la vista...

Page 55: ...ovimiento de la camme H ya sea en abertura que en cierre posicionar en vista los dos finales de carrera F operando con los p mulos P Despu s de haber verificado el correcto funcionamiento el ctrico de...

Page 56: ...LED R 2 2K 1 4W COM N COM N COM N COM N BANDA 2 FOTOC LULA 2 BANDA 1 A TEST A AUTOPRUEBA DE FOTOC LULAS ANTENA 433 MHz ARMADURA ANTENA 24Vdc 0 4A 15 24Vdc 0 4A 15 700 W MAX CIERRE ABRE COM N ALIMENTAC...

Page 57: ...ulas 1 NC PHOT 2 Contacto de las fotoc lulas 2 NC EDGE 1 Contacto banda de seguridad 1 NC EDGE 2 Contacto banda de seguridad 2 NC J7 COM A Com n de los contactos Positivo 24 Vdc LIMIT SWITCH Contactos...

Page 58: ...nci n detiene la programaci n el led DL1 del destello permanece iluminado constantemente N B Si las entradas de parada PHOT 1 PHOT 2 EDGE 1 y EDGE 2 no est n conectados realice puente entre COM A STOP...

Page 59: ...para poder memorizar el mando a distancia sucesivo 3 Para terminar la programaci n deje transcurrir 10 s o presione por un instante el pulsador PROG El led DL12 deja de parpadear 4 Vuelva a colocar e...

Page 60: ...ridad que se puede bypasar en este funcionamiento y por lo tanto si viene apretrado o se rompe no permite alg n movimiento del port n La maniobra con mando mantenido presionado es exclusivamente una m...

Page 61: ...CI N Despu s de haber efectuado varias conexiones y haber dado tensi n todos los led est n apagados En el cuadro hay fusibles reajustables que intervienen en caso de cortocircuito que interrumpa la sa...

Page 62: ...r c digos de radio 1000 c digos memorizados Apagado Apagado Realiza 6 parpadeos verdes Anulaci n c digos radio de apertura total peatonal y R AUX 2 Tonos Apagado Realiza 2 parpadeos verdes SE ALIZACIO...

Page 63: ...de control a trav s de Bluetooth 4 2 APP8064 M dulo wi fi para Tarjeta APP para administrar el panel de control a trav s de una red Wi Fi local WLAN APP8066 M dulo RJ45 para Tarjeta APP para administr...

Page 64: ...ja en movimiento sin la adopci n de sistemas recoge cables Conforme a la norma EN13849 1 2007 Unido a un cuadro electr nico RIB es un dispositivo de protecci n de Clase 2 c d ACG6202 E S NOVA NOVA WIR...

Page 65: ...self test 2 Fotozellen FIT SLIM FIT SYNCRO mit Selbstkontrolle 2 fotoc lulas FIT SLIM FIT SYNCRO con autotest 2 fotocellule F97P F97I con autotest 2 photocellules F97P F97I avec autotest 2 photocells...

Page 66: ...UTOTEST est activ e et qu une seule photocellule est connect e un cavalier doit tre cr entre les bornes PHOT 1 et PHOT 2 Si le cavalier n est pas ex cut l autotest choue et le portail ne bouge pas WAR...

Page 67: ...forzo Super CCA1215 Protezione ingranaggio SUPER CCU6207 Cuscinetto 6207 35x72x17 CCU6307 Cuscinetto 6307 35x80x21 CEL1433 Pressacavo CAL1437 Condensatore 50 F 470V CME1034 Albero traino Super CME1063...

Page 68: ...t ndigen nationalen Beh rden Diese unvollst ndige Maschine in bereinstimmung mit den Bestimmungen der folgenden anderen CE Richtlinien Richtlinien 2014 30 UE 2014 35 UE und 2014 53 UE Alle grundlegend...