35
Section I :: User
EN
Open the probe cover (attached to the sequencer panel) and set it for
the signal 4÷20mA
(*)
only for EXP units
Active sensors for distances up to 200 meters
RMST temperature probes
Rhoss RMST sequencer input/output definition
Probe configuration
(G) + out T
M
T
T
J8
J6
J5
J4
Digital inputs Function
ID1
Centralised remote On/Off
ID2
Centralised Summer/Winter
ID3
Requested recovery*
ID4
Double Set-point (primary)
ID5
Double Set-point (recovery) *
ID6
System general alarm
ID7
Primary flow switch
ID8
Rejection device flow switch (water/water vers.)
ID9
Primary pump alarm 1
ID10
Primary pump alarm 2
ID11
Rejection device pump alarm 1 (water/water vers.)
ID12
Rejection device pump alarm 2 (water/water vers.)
ID13
Recovery pump alarm 1 *
ID14
Recovery pump alarm 2 *
Analog inputs Function
B1
Primary shifting Set-point (signal 4-20mA)
B2
System return water temperature probe
B3
System flow water temperature probe
B4
Outdoor air temperature probe
B5
Recovery flow switch *
B6
Recovery shifting Set-point (signal 4-20mA) *
B7
Recovery return water temperature probe *
B8
Recovery flow water temperature probe *
Digital outputs Function
NO1
Primary pump 1
NO2
NO3
NO4
Primary pump 2
NO5
NO6
NO7
Rejection device pump 1 (water/water vers.)
NO8
Rejection device pump 2 (water/water vers.)
NO9
System general alarm (from sequencer digital inputs)
NO10
Chiller general alarm + serial network alarm
NO11
Integrative/replacement boiler request
NO12
Recovery pump 1 *
NO13
Recovery pump 2 *