background image

The manufacturer’s warranty does not cover any damage or defect 

caused by installation, or attachment, or use of any special attach-

ment such as energy saving devices (other than those authorized 

by the manufacturer) into, onto, or in conjunction with the water 

heater. The use of such unauthorized devices may shorten the 

life of the water heater and may endanger life and property. The 

manufacturer disclaims any responsibility for such loss or injury 

resulting from the use of such unauthorized devices.

1.  INSPECT SHIPMENT — for possible damage. The manufacturer’s 

responsibility ceases upon delivery of goods to the carrier in good 

condition. Any claims for damage, shortage in shipments, or non de-

livery must be filed immediately against carrier by consignee.

2.   THERMAL EXPANSION — Determine if a check valve exists in the 

inlet water line. It may have been installed in the cold water line as a 

separate back flow preventer, or it may be part of a pressure reduc-

ing valve, water meter or water softener. A check valve located in 

the cold water inlet line can cause what is referred to as a ”closed 

water system”. A cold water inlet line with no check valve or back 

flow prevention device is referred to as an ”open” water system.

  As water is heated, it expands in volume and creates an increase 

in the pressure within the water system. This action is referred to as 

”thermal expansion”. In an ”open” water system, expanding water 

which exceeds the capacity of the water heater flows back into the 

city main where the pressure is easily dissipated.

  A ”closed water system”, however,  prevents the expanding water 

from flowing back into the main supply line, and the result of ”thermal 

expansion” can create a rapid, and dangerous pressure increase in 

the  water heater and system piping. This rapid pressure increase can 

quickly reach the safety setting of the relief valve, causing it to oper-

ate during each heating cycle. Thermal expansion, and the resulting 

rapid, and repeated expansion and contraction of components in the 

water heater and piping system can cause premature failure of the 

relief valve, and possibly the heater itself.  Replacing the relief valve 

will not correct the problem! 

  The suggested method of controlling thermal expansion is to install an 

expansion tank in the cold water line between the water heater and the 

check valve. The expansion tank is designed with an air cushion built in 

that compresses as the system pressure increases, thereby relieving 

the over pressure condition and eliminating the repeated operation of 

the relief valve. Other methods of controlling thermal expansion are also 

available. Contact your installing contractor, water supplier, or plumbing 

inspector for additional information regarding this subject.

  If a recirculation line is installed, the return connection should be made 

to a tee close to the inlet connection on the water heater. A check valve 

should always be installed in the recirculation line to prevent cold water 

from entering.

  WATER CONNECTIONS — This water heater may be connected indi-

vidually, in multiples with others, or with an external hot water storage 

tank.

  Inlet water connections are made to the lower coupling on the heater,  

and outlet water connections are made to the upper coupling.

  Each water heater is supplied with the necessary components (Diffuser 

tubes) to make the water connections that will ensure proper perfor-

mance. The components are supplied in a bag attached  to the water 

heater.  If special instructions are required for any specific water heater, 

they will be included in the bag.

  Cap or plug unused connections. Use only clean, new galvanized steel, 

copper or approved plastic  pipe for water connections. Local codes 

or regulations shall govern the exact type of material to be used. The 

installation of unions on the inlet and outlet water lines and a shut-off 

valve in at least the cold water inlet line is recommended, so the water 

heater may be easily disconnected for servicing. Dielectric unions are 

not required for protection of water heater.

  When this water heater is supplying general purpose hot water require-

ments for use by individuals, a thermostatically controlled mixing valve 

is recommended to reduce the risk of scald injury. Contact a licensed 

plumber or the local plumbing authority for further information.

  Thermometer(s) should be installed so that they indicate the tempera-

ture of the water at or near the outlet of the water heater and storage 

tank(s) if provided. See Fig. 4 on page 7.

3.  RELIEF VALVE — A new factory installed combination pressure and 

temperature relief valve, complying with the Standard for Relief Valves 

and Automatic Gas Shutoff Devices for Hot Water Supply Systems, 

ANSI Z21.22, or Standard CAN1-4.4, Temperature, Pressure, Tempera-

ture and Pressure Relief Valves and Vacuum Relief Valves is provided 

with the water heater. No valve is to be placed between the relief valve 

and the water heater. For a circulating tank installation, the separate 

storage tank(s) must have similar protection. The pressure rating of the 

relief valve must not exceed 150 psi (160 psi for ASME models), the 

maximum working pressure as marked on front of the water heater.

  The Btu/h rating of the relief valve must equal or exceed the Btu/h input 

of the water heater as marked on its rating plate.

  Connect the outlet of the relief valve to a suitable open drain. The 

discharge line must pitch downward from the valve to allow complete 

draining (by gravity) of the relief valve and discharge line, and be no 

smaller than the outlet of the valve. The end of the discharge line 

should not be threaded or concealed and should be protected from 

freezing. No valve of any type, restriction or reducer coupling should be 

installed in the discharge line. Local codes shall govern the installation 

of relief valves.

4.  GAS SUPPLY — The inlet gas pressure to the water heater must not 

exceed 10.5” w.c. (2.6 kPa) for Natural gas.  For purposes of input adjust-

ment, the minimum inlet gas pressure (with main burner on) is shown on 

the rating plate. Check to see if high or low gas pressure is present and 
then contact the gas company for correction.

  The gas line should be of adequate size to prevent undue pressure 

drop. Sizing based upon Table 1 (on pg. 13) is recommended. No ad-

ditional allowance is necessary for an ordinary number of fittings.

  A ground joint union and manual shutoff valve should be installed in 

the gas line near the water heater so that the burner assembly may 

be easily removed. The shut-off valve must be readily accessible for 

turning on or off. See Fig. 4 on page 7.

  A sediment trap must be installed at the bottom of the gas line. See 

Fig. 4 on page 7.

  LEAK TESTING — The water heater and its gas connections MUST 

be leak tested at normal operating pressure before it is placed in op-

eration. Turn ON the manual gas shut-off valve near the water heater. 

Use a soapy water solution to test for gas leaks at all connections and 

fittings. Bubbles indicate a gas leak that must be corrected. The water 

heater factory connections to the gas valve should also be leak tested 

after placing the water heater in operation.

6

installation

WARNING

!

Summary of Contents for VentMaster GP100-150

Page 1: ...er service agency or the gas supplier WARNING If the information in these instructions are not followed exactly a fire or explosion may result causing property damage personal injury or death NOTICE This water heater is designed for use in a commercial application and the installation and maintenance of it should be per formed by a qualified licensed service personnel If the foregoing assumption i...

Page 2: ...read and obey all safety messages This is the safety alert symbol Recognize this symbol as an indication of Important Safety Information This symbol alerts you to potential hazards that can kill or hurt you and others All safety messages will follow the safety alert sym bol and either the word DANGER WARNING CAUTION or NOTICE These words mean DANGER An imminently hazardous situation that will resu...

Page 3: ...w illustrates the thermostat and how to adjust the water tem perature Hotter water increases the Potential for HotWater SCALDS NOTICE Mixing valves are available for reducing point of use water temperature by mixing and cold water in branch water lines Contact a licensed plumber or the local plumbing authority for further information D A N G E R HOT Water temperature over 125 F can cause severe bu...

Page 4: ...ther flammable materials and liquids adhesives solvents etc and the vapors they produce are extremely dangerous DO NOT handle use or store gasoline or other flammable or combustible materials any where near or in the vicinity of a water heater Be sure to read and follow the warning label pictured below and other labels on the water heater as well as the warnings printed in this manual Failure to d...

Page 5: ...light ing the vapor of any flammable liquids which may be improperly stored or accidentally spilled C All models are certified for installation on combustible floors and in alcoves The minimum side and top clearance to walls and ceiling for providing protection of combustible materials are shown on the water heater s rating label A front clearance of 18 inches 46 cm should be provided for adequate...

Page 6: ...ecial instructions are required for any specific water heater they will be included in the bag Cap or plug unused connections Use only clean new galvanized steel copper or approved plastic pipe for water connections Local codes or regulations shall govern the exact type of material to be used The installation of unions on the inlet and outlet water lines and a shut off valve in at least the cold w...

Page 7: ... section on pages 8 11 in this manual NOTES 1 The gas supply piping must be adequately supported and aligned to minimize loads forces on the water heater s gas valve and burner system 2 R efer to local codes for installation guide lines for the Thermal Expansion Tank if required Thermal Expansion Tank if required Installation Figure 4 Typical Installation Drawing Vacuum Relief Valve Not Supplied I...

Page 8: ...erwise secure the vent ing system in a way that restricts the normal thermal expansion and contraction of the chosen venting material If the water heater is being installed as a replacement for an existing power vented water heater a thorough inspection of the existing venting system must be performed prior to any installation work Verify that the correct materials as detailed above have been used...

Page 9: ... location of the vent terminal depends on the minimum clearances and consider ations shown in the charts on pages 11 and 12 Number of 90º Elbows with Vent Terminal Number of 45º Elbows Minimum Pipe Length Required Ft Maximum Pipe Length Ft Inlet Vent Outlet Vent One 1 One 1 None 10 0 45 0 One 1 One 1 One 1 7 5 42 5 Two 2 Two 2 None 5 0 40 0 Two 2 Two 2 One 1 2 5 37 5 Three 3 Three 3 None 5 0 35 0 ...

Page 10: ...ix 6 feet of vent terminal 6 All painted surfaces should be primed to lessen the chance of physical damage Painted surfaces will require maintenance 7 Insulate vent pipe exposed to cold conditions attics crawl spaces etc to help prevent moisture from accu mulating in vent pipe Moisture in the flue gas will condense as it leaves the vent terminal In cold weather this condensate can freeze on the ex...

Page 11: ...ort piece of vent pipe VERTICAL VENT TERMINAL LOCATION The location of vertical vent terminal depends on the following considerations see Figure 8 1 Minimum twelve 12 inches above roof 2 Minimum twelve 12 inches above anticipated snow level D V V E FIXED CLOSED OPERABLE OPERABLE FIXED CLOSED v v B L F C B v v v X B B B A J C I H X v M K v G A The following information should be used for determinin...

Page 12: ...vent The drain hose should have two 2 loops formed to act as traps Before operation of the water heater both loops should have water placed in them Support the traps so that they remain horizontal Condensate is known to be acidic refer to local state or federal codes for proper handling methods JOINING PIPES AND FITTINGS All pipe fittings solvent cement primers and procedures must conform to Ameri...

Page 13: ... 195 180 170 160 150 130 120 110 100 1 1 4 1 380 1 050 730 590 500 440 400 370 350 320 305 275 250 225 210 1 1 2 1 610 1 600 1 100 890 760 670 610 560 530 490 460 410 380 350 320 2 2 067 3 050 2 100 1 650 1 450 1 270 1 150 1 050 990 930 870 780 710 650 610 2 1 2 2 469 4 800 3 300 2 700 2 300 2 000 1 850 1 700 1 600 1 500 1 400 1 250 1 130 1 050 980 3 3 068 8 500 5 900 4 700 4 100 3 600 3 250 3 000...

Page 14: ...ctions If you cannot reach your gas supplier call the fire department Use only your hand to turn the gas control knob Never use tools If the knob will not turn by hand don t try to repair it call a qualified service technician Force or attempt to repair may result in a fire or explosion C Do not use this appliance if any part has been under water Immediately call a qualified ser vice technician to...

Page 15: ...EQUIPPED WITH AN IGNITION DEVICE WHICH AUTOMA TICALLY LIGHTS THE PILOT DO NOT TRY TO LIGHT THE PILOT BY HAND TURN THE GAS CONTROL KNOB CLOCK WISE TO OFF 5 WAIT FIVE 5 MINUTES TO CLEAR OUT ANY GAS IF YOU THEN SMELL GAS STOP FOL LOW B IN THE SAFETY INFORMATION ABOVEON THIS LABEL IF YOU DON T SMEL L GAS 6 GO TO NEXT STEP TURN THE GAS CONTROL KNOB COUNTER CLOCKWISE TO ON 7 IF THE APPLIANCE WILL NOTOPE...

Page 16: ...f Use the following formula DO NOT exceed Input shown on the water heater s rating plate 16 Operation A Do turn off manual gas shut off valve if water heater has been sub jected to over heating fire flood physical damage or if gas supply fails to shut off B Do Not turn on water heater unless it is filled with water C Do Not turn on water heater if cold water supply shut off valve is closed D Do No...

Page 17: ... least yearly to make certain the passageways are free and unobstructed and that the vent connector from the water heater s blower assembly is properly posi tioned and securely attached Remove any obstructions in vent con nector or vent terminal C CONTROLS The manifold pressure and controls should be checked at least yearly by a qualified service technician To insure accuracy for rating clock enou...

Page 18: ...ter Any new installation should have a tank inspection program set up initially for frequent inspection The first inspection should be within a six month period Once the scaling tendencies have been established the inspection program can be modified to suit the water conditions Cleaning should be performed if the scale has accumulated above the drain valve opening A wet dry shop vac with a nozzle ...

Page 19: ...ther mostat is functioning calling for heat and 24VAC power is being supplied to the relay to turn on the blower and the N C terminal of the pressure switch with N C and N O terminals Refer to Section 2 of Troubleshooting Guide IGNITION When illuminated this red LED indicates that 24 VAC power is being supplied to the Ignition Control Module and the ignition sequence has begun The N O side of the ...

Page 20: ...er or fuse and field connec tion of branch circuit wiring to leads of switch Repair or replace as required Is POWER LED now illuminated Is 120 VAC power present between the Black and White wires to the transformer Is 24 VAC power present between the Yellow and Gray wires from the transformer The System Senti nel Panel is defective and must be replaced Replace Switch then verify that power is prese...

Page 21: ...rvicing controls Wiring errors can cause improper and dangerous operation VERIFY PROP ER OPERATION AFTER SERVICING Ensure that power is being supplied to the water heater Refer to Section 1 the POWER LED in thisTroubleshooting Guide and correct if necessary Is the THERMO STAT LED now illuminated Ensure that power is being supplied to the water heater Refer to Section 1 the POWER LED in thisTrouble...

Page 22: ...ure Switch Is continuity good The Thermostat has called for heat the Blower is running and 24VAC power is being supplied to the Ignition Control Module and the ignition sequence will begin YES YES YES YES NO NO NO NO NO Is the Ignition LED Illuminated Is there 120 VAC across Black wire and White wire of blower YES NO Is there 120 VAC between the black wire at the relay and the whitewireonthe trans...

Page 23: ... the ECO Energy Cut Off Device inside of theThermostat YES YES YES YES NO NO NO NO NO Refer to Section 5 the ECO LED in theTroubleshooting Guide NO NO Is the PILOTVALVE LED Illuminated 1 Remove Ignition Cable and check for good conti nuity replace if necessary 2 Check Ignitor Electrode gap for proper spacing 1 8 to 5 32 Correct if necessary 3 Examine Ceramic Insulator on Pilot Assembly for cracks ...

Page 24: ... Is the Spark Ignitor operating Can sparking be heard Ignition Control Module is inoperative and must be replaced Main GasValve is inoperative and must be replaced Is the inlet gas pressure at or below the maximum as specified on the rating plate Check Continuity of Blue and White wires between Ignition Control Module and Gas Control Valve Repair or replace as required to restore power to gas valv...

Page 25: ... of parts desired CAUTION For your safety DO NOT attempt repair of gas piping gas control thermostat burners vent con nectors or other safety devices Refer repairs to qualified service personnel Blower Assembly T P Valve Handhole Sealplate Gasket SP5886 Beneath Cover Drain Valve Thermostat Ignition Control Assembly w Relay Gas Valve Burner Assembly Pilot Ignitor Assembly Some assembly components a...

Page 26: ... MV THERM B L O W E R 2 1 4 6 5 5 1 2 0 V 2 4 V L 1 L 2 3 MGV AX4729 PGV HONEYWELL VR8304P OR VR8304M GAS VAL VE HONEYWELL S8600M IGNITION CONTROL IF ANY OF THE ORIGINAL WIRE AS SUPPLIED WITH THIS APPLIANCE MUST BE REPLACED IT MUST BE REPLACED WITH 18 GA 600V 105 C WIRE OR ITS EQUIVALENT N O R M A L O P E R A T I O N S E Q U E N C E I N D I C A T E D B Y B O X E D N U M E R A L S POWER LED IGNITIO...

Page 27: ...EPLACEMENT WIRE MUST BE RATED FOR 250 C NORMAL OPERATION SEQUENCE INDICATED BY BOXED NUMERALS ECO LED PILOT VALVE LED MAIN VALVE LED C NC NO W GR YL BK R 1 R8 G2 BK 2 W4 BK3 BL6 BLOWER GY 5 Y6 M R 3 BLOWER Y2 C NC PS2 PS1 Y 5 Y7 RELAY 3 4 6 5 2 R N C S W 4 2 Figure 14 Diagrams for units supplied with HoneywellVR8304P orVR8304M GasValve and Honeywell S8600M Ignition Control CAUTION Label all wires ...

Page 28: ...mercial listings or local utility for qualified service assistance 2 Should your problem not be solved to your complete satisfaction you should then contact the Manufacturer s National Service Department at one of the following address In The U S A Rheem Manufacturing Co Water Heater Division 2600 Gunter Park Drive Montgomery Alabama 36109 1413 Phone 1 800 432 8373 In CANADA Rheem Canada Ltd Ltée ...

Reviews: