background image

3

The location chosen for the water heater must take into consideration the 

following:
LOCAL INSTALLATION REGULATIONS
This water must be installed in accordance with these instructions, local 
codes, utility company requirements or, in the absence of local codes, the 
latest edition of the National Electrical Code. It is available from some local 
libraries or can be purchased from the National Fire Prevention Association, 1 
Batterymarch Park, Quincy, MA 02269 as booklet ANSI/NFPA 70.

LOCATION
Locate the water heater in a clean dry area as near as practical to the area of 
greatest heated water demand. Long uninsulated hot water lines can waste 
energy and water. Place the water heater in such a manner that the front 
panel can be easily removed to permit inspection and servicing such as 
removal of elements or checking controls. The water heater and water lines 
should be protected from freezing temperatures. Do not install the water 
heater in outdoor, unprotected areas.

The water heater should not be located in an area where 

leakage of the tank or connections will result in damage to 

the area adjacent to it or to lower floors of the structure. 

This water heater SHOULD NOT be installed in a space where 

liquids which give off flammable vapors are to be used or 

stored.  Such liquids include gasoline, LP gas (butane and 

propane), paint or adhesives and their thinners, solvents or 

removers.  Because of natural air movement in a room or 

other enclosed space, flammable vapors can be carried from 

where their liquids are being used or stored.  The arc drawn 

within the water heater's control can ignite these vapors 

causing an explosion or fire which may result in severe burns 

or death to those in range, as well as property damage.

Introduction 

CAUTION

!

Installation

1.  INSPECT SHIPMENT — Inspect water heater for possible damage. 

Check the markings on the rating plate of the water heater to be 

certain the power supply corresponds to that for which the water 

heater is equipped.

2.  THERMAL EXPANSION — Determine if a check valve exists in the 

inlet water line. It may have been installed in the cold water line as 

a separate back flow preventer, or it may be part of a pressure reduc-

ing valve, water meter or water softener. A check valve located in the 

cold water inlet line can cause what is referred to as a 

”closed water 

system”. A cold water inlet line with no check valve or back flow 

prevention device is referred to as an ”open” water system.

  As water is heated, it expands in volume and creates an increase in 

the pressure within the water system. This action is referred to as 

”thermal expansion”. In an ”open” water system, expanding water 

which exceeds the capacity of the water heater flows back into the 

city main where the pressure is easily dissipated.

  A 

”closed water system”, however,  prevents the expanding water 

from flowing back into the main supply line, and the result of 

”thermal 

expansion” can create a rapid, and dangerous pressure increase in 

the  water heater and system piping. This rapid pressure increase 

can quickly reach the safety setting of the relief valve, causing it to 

operate during each heating cycle. Thermal expansion, and the result-

ing rapid, and repeated expansion and contraction of components in 

the water heater and piping system can cause premature failure of 

the relief valve, and possibly the heater itself.Replacing the relief 

valve 

will not correct the problem! 

  The suggested method of controlling thermal expansion is to install an 

expansion tank in the cold water line between the water heater and the 

check valve. The expansion tank is designed with an air cushion built 

in that compresses as the system pressure increases, thereby relieving 

the over pressure condition and eliminating the repeated operation of 

the relief vale. Other methods of controlling thermal expansion are also 

available. Contact your installing contractor, water supplier, or plumbing 

inspector for additional information regarding this subject.

 3.  WATER SUPPLY CONNECTIONS — Refer to Fig. 2 for suggested 

typical installation. The installation of unions or flexible copper con-

nectors is recommended on the hot and cold water connections so 

that the water heater may be easily disconnected for servicing if 

necessary. The HOT and COLD water connections are clearly marked 

and are 3/4” NPT on all models. Install a shut-off valve in the cold 

water line near the water heater.

IMPORTANT!! Do not apply heat to the hot or cold water connections. If 

sweat connections are used, sweat tubing to adapter before fitting adapt-

er to hot or cold water connections on heater. Any heat applied to the hot 

or cold water supply fittings will permanently damage them.

4.  RELIEF VALVE — A new combination temperature and pressure relief 

valve, complying with the Standard for Relief Valves and Automatic 

Gas Shutoff Devices for Hot Water Supply Systems, ANSI Z21.22, 

must be installed in the opening provided and marked for the purpose 

on the water heater. (Refer to Fig. 2.) No valve of any type should be 

installed between the relief valve and the tank. Local codes shall gov-

ern the installation of relief valves.

  The pressure rating of the relief valve must not exceed 150 PSI, the 

maximum working pressure of the water heater as marked on the 
rating plate. The BTUH Rating of the relief valve must not be less than 
the input rating of the water heater as indicated on the rating label 
located on front of the heater (1 watt = 3.412 BTUH).

  Connect the outlet of the relief valve to a suitable open drain so that 

the discharge water cannot contact live electrical parts and to elimi-

nate potential water damage. Piping used should be of a type ap-

proved for hot water distribution. The discharge line must be no 

smaller than the outlet of the valve and must pitch downward from 

the valve to allow complete drainage (by gravity) of the relief valve 

and discharge line. The end of the discharge line should not be 

threaded or concealed and should be protected from freezing. No 

valve of any type, restriction or reducer coupling should be installed 

in the discharge line.

5.  TO FILL WATER HEATER — Make certain drain valve is completely 

closed. Open shut-off valve in cold water supply line. Open each hot 

water faucet slowly to allow air to vent from the water heater and 

piping. A steady flow of water from the hot water faucet(s) indicates 

a full water heater.

WARNING

!

Summary of Contents for Single and Double Element Models

Page 1: ...e for Future Reference Recognize this symbol as an Indication of Important Safety Information The purpose of this manual is twofold one for the installing contrac tor to provide requirements and recommendations for the proper installation and adjustment of the water heater and two for the owner operator to explain the features operation safety precau tions maintenance and trouble shooting of the w...

Page 2: ...was shipped from the factory The illustration above shows the temperature adjustment dial used for setting the water temperature Refer to Operation section of this manual for detailed instructions in how to adjust the thermostat s There is a Hot Water SCALD Potential if the thermostat is set too high Mixing valves for reducing point of use water temperature by mixing hot and cold water in branch w...

Page 3: ...alve causing it to operate during each heating cycle Thermal expansion and the result ing rapid and repeated expansion and contraction of components in the water heater and piping system can cause premature failure of the relief valve and possibly the heater itself Replacing the relief valve will not correct the problem The suggested method of controlling thermal expansion is to install an expansi...

Page 4: ... approved for use as a grounding conductor and installed with fittings approved for the pur pose Installation Figure 2 Typical Installation Pictured from rear of heater with Top Panel and Insulation Pad removed Figure 3 Location of water connections on water heater tank Pictured with top insulation pad removed WARNING Hot Water Outlet to Fixtures To Electrical Distribution Panel Use only Copper Co...

Page 5: ...anufacturer s warranty does not cover any damage or defect caused by installation attachment or use of any type of energy saving or other unapproved devices other than those authorized by the manufacturer into onto or in conjunction with the water heater The use of unauthorized en ergy saving devices may shorten the life of the water heater and may en danger life and property The manufacturer disc...

Page 6: ...r is OFF before removing front center panel or top panel FOR ANY REASON If adjustment is necessary turn off power to water heater remove front center panel and insulation exposing thermostats The thermostat protective covers should not be removed Set thermostats dial pointers with a small screwdriver to desired temperature Refer to Fig 4 Replace insulation and front center panel Turn on power to w...

Page 7: ...e from your plumber or local plumbing supply store 2 ANODE ROD INSPECTION The anode rod should be removed from the water heater s tank annually for inspection and replaced when more than 6 of core wire is exposed at either end of the rod Refer to Fig 2 or 3 for anode rod location Make certain cold water supply is turned off before removing anode rod Operation Maintenance DANGER button Replace insu...

Page 8: ...allonTableTop Models Single and Double Element Instructions for placing a Parts Orders Address parts orders to the distributor or store from where the heater was purchased All parts orders should include 1 Model number and Serial number of heater from rating plate 2 Specify voltage and wattage as marked on rating plate 3 Part Description as noted at right and number of parts desired These parts ar...

Page 9: ...cription Req d 1 SplashTop 1 2 Front Center Panel 1 3 UpperThermostat on double element models only 1 4 UpperThermostat Protective Cover on double element models only 1 5 Thermostat Bracket As Req d 6 Heating Element Gasket As Req d 7 Heating Element As Req d 8 LowerThermostat Protective Cover 1 9 LowerThermostat 1 10 DrainValve 1 11 DipTube 1 12 DipTube Gasket 1 13 Anode 1 14 ReliefValve 1 Owners...

Page 10: ...ittings when in operation and does not indicate a need for service For your safety DO NOT attempt repair of Electrical Wiring Thermostat s Heating Elements or other Operating Controls Refer repairs to qualified service personnel CAUTION 1 Should you have any questions about your new water heater or if it requires adjustment repair or routine maintenance it is suggested that you first contact your ...

Page 11: ...heaters up to 52 gallon capacity a brochure with generic earthquake bracing instructions can be obtained from OFFICE OFTHE STATE ARCHITECT 1102 Q Street Suite 5100 Sacramento CA 95814 Telephone 916 445 8100 or ask a water heater dealer However applicable Local Codes shall govern installations For residential water heat ers of capacity greater than 52 gallons consult the local building jurisdiction...

Page 12: ...TRIBUTION PANEL G G G BRANCH CIRCUIT TO ELECTRICAL DISTRIBUTION PANEL UPPER THERMOSTAT HIGH TEMP LIMIT ECO 2 UPPER HEATING ELEMENT BLUE L1 JUNCTION BOX 4 L2 1 3 RED 10 GA BLACK LOWER HEATING ELEMENT LOWER THERMOSTAT HIGH TEMP LIMIT ECO 1 2 4 1 3 1 2 RED 2 BLACK 10 GA YELLOW BLACK 10 GA RED 10 GA G 2 UPPER THERMOSTAT HIGH TEMP LIMIT ECO UPPER HEATING ELEMENT BLUE L1 BRANCH CIRCUIT TO ELECTRICAL DIS...

Reviews: