VII. GAS SUPPLY, CONDENSATE DRAIN AND
VII.
PIPING
A. GAS CONNECTION
IMPORTANT:
Connect this unit only to gas supplied by a commercial utility.
1. Install gas piping in accordance with local codes and regulations of the local utility
company. In the absence of local codes, the installation must conform to the specifi-
cations of the National Fuel Gas Code, ANSI Z223.1 - latest edition.
NOTE: The use of flexible gas connectors is not permitted.
NOTE: The Commonwealth of Massachusetts requires the gas shut-off valve to be
a T-handle gas cock.
2. Connect the gas line to the gas pipe inlet opening provided into the 1/2” inlet valve.
See Figure 5 for typical piping.
3. Size the gas line to the furnace adequate enough to prevent undue pressure drop
and never less than 1/2”.
4. Install a drip leg or sediment trap in the gas supply line as close to the unit as possi-
ble.
5. Install an outside ground joint union to connect the gas supply to the control assem-
bly at the burner tray.
6. Gas valves have been factory installed. Install a manual gas valve where local codes
specify a shut-off valve outside the unit casing. (See Figure 22.)
7. Make sure piping is tight.
A pipe compound resistant to the action of liquefied
petroleum gases must be used at all threaded pipe connections.
8. IMPORTANT: Any additions, changes or conversions required for the furnace to sat-
isfactorily meet the application should be made by a qualified installer, service
agency or the gas supplier, using factory-specified or approved parts. In the com-
monwealth of Massachusetts, installation must be performed by a licensed plumber
or gas fitter for appropriate fuel.
IMPORTANT:
Disconnect the furnace and its individual shutoff valve from the gas sup-
ply piping during any pressure testing of that system at test pressures in excess of 1/2
psig or isolate the system from the gas supply piping system by closing its individual
manual shutoff valve during any pressure testing of this gas supply system at pressures
equal to or less than 1/2 PSIG.
FIGURE
19
SUGGESTED GAS PIPING
FROM GAS
METER
*
Factory supplied grommet must be utilized.
MANUAL GAS
SHUT-OFF
VALVE
UNIT GAS SUPPLY
CONNECTION
*
ROOF OR GROUND LEVEL INSTALLATION
Nominal
Iron Pipe
Size,
Inches
Equivalent Length of Pipe, Feet
10
20
30
40
50
60
70
80
1
/
2
132
92
73
63
56
50
46
43
3
/
4
278
190
152
130
115
105
96
90
1
520
350
285
245
215
195
180
170
1
1
/
4
1,050
730
590
500
440
400
370
350
1
1
/
2
1,600 1,100
890
760
670
610
560
530
TABLE
1
GAS PIPE CAPACITY TABLE (CU. FT./HR.)
FIGURE 22
SUGGESTED GAS PIPING
22
Summary of Contents for RRNL-B
Page 39: ...39 FIGURE 31 COOLING ON DELAY PROFILES INTERFACE BOARD SWITCH 7 8 7 8 7 8 7 8...
Page 40: ...FIGURE 32 BLOWER OFF DELAY PROFILES INTERFACE BOARD SWITCH 7 8 7 8 7 8 7 8 40...
Page 77: ...FIGURE 35 WIRING DIAGRAM XV WIRING DIAGRAMS 77...
Page 78: ...FIGURE 36 WIRING DIAGRAM 78...
Page 79: ...FIGURE 37 WIRING DIAGRAM 5 TON 4 TON LOW HEAT HIGH COOL 3 TON LOW HEAT MED COOL 79...
Page 80: ...FIGURE 38 WIRING DIAGRAM 80...
Page 81: ...FIGURE 39 WIRING DIAGRAM 81...
Page 82: ...FIGURE 40 WIRING DIAGRAM 82...
Page 83: ...FIGURE 41 WIRING DIAGRAM 83...
Page 84: ...FIGURE 42 WIRING DIAGRAM 84...
Page 85: ...FIGURE 43 WIRING DIAGRAM 85...
Page 86: ...86 FIGURE 44 WIRING DIAGRAM...
Page 87: ...87 FIGURE 45 WIRING DIAGRAM...
Page 90: ...FIGURE 48 SYSTEM CHARGE CHARTS RNL RPL 3 TON COOLING SYSTEM CHARGE CHART REFRIGERANT 410A 90...
Page 92: ...FIGURE 50 SYSTEM CHARGE CHARTS RNL RPL 4 TON COOLING SYSTEM CHARGE CHART REFRIGERANT 410A 92...
Page 108: ...108 CM 0314...