left side of unit. (See Figure 12.) If no economizer is required, then a 12” clearance
is required on left side of unit.
2. Provide 60” minimum clearance between top of unit and maximum 3 foot overhang.
3. Unit is design certified for 2” minimum clearance between supply duct and a com-
bustible structure for the first 3 feet of duct. 0” clearance is allowed after 3 feet.
F. ROOFTOP INSTALLATION
1. Before locating the unit on the roof, make sure that the roof structure is adequate to
support the weight involved. (See electrical & physical tables in this book for weight
of unit.)
THIS IS VERY IMPORTANT AND THE INSTALLER’S RESPONSIBILITY.
2. For rigging and roofcurb details, see Figures 17, 18, and 19.
3. The location of the unit on the roof should be such as to provide proper access for
inspection and servicing.
IMPORTANT:
If unit will not be put into service immediately, block off supply and return
air openings to prevent excessive condensation.
G. DUCTWORK
The installing contractor should fabricate ductwork in accordance with local codes. Use
industry manuals as a guide when sizing and designing the duct system. Contact Air
Conditioning Contractors of America, 1513 16th St. N.W., Washington, D.C. 20036.
17
!
WARNING
DO NOT, UNDER ANY CIRCUMSTANCES, CONNECT RETURN DUCTWORK TO
ANY OTHER HEAT PRODUCING DEVICE SUCH AS FIREPLACE INSERT,
STOVE, ETC. UNAUTHORIZED USE OF SUCH DEVICES MAY RESULT IN FIRE,
CARBON MONOXIDE POISONING, EXPLOSION, PERSONAL INJURY, OR
PROPERTY DAMAGE.
FIGURE 12
CLEARANCES
Summary of Contents for RRNL-B
Page 39: ...39 FIGURE 31 COOLING ON DELAY PROFILES INTERFACE BOARD SWITCH 7 8 7 8 7 8 7 8...
Page 40: ...FIGURE 32 BLOWER OFF DELAY PROFILES INTERFACE BOARD SWITCH 7 8 7 8 7 8 7 8 40...
Page 77: ...FIGURE 35 WIRING DIAGRAM XV WIRING DIAGRAMS 77...
Page 78: ...FIGURE 36 WIRING DIAGRAM 78...
Page 79: ...FIGURE 37 WIRING DIAGRAM 5 TON 4 TON LOW HEAT HIGH COOL 3 TON LOW HEAT MED COOL 79...
Page 80: ...FIGURE 38 WIRING DIAGRAM 80...
Page 81: ...FIGURE 39 WIRING DIAGRAM 81...
Page 82: ...FIGURE 40 WIRING DIAGRAM 82...
Page 83: ...FIGURE 41 WIRING DIAGRAM 83...
Page 84: ...FIGURE 42 WIRING DIAGRAM 84...
Page 85: ...FIGURE 43 WIRING DIAGRAM 85...
Page 86: ...86 FIGURE 44 WIRING DIAGRAM...
Page 87: ...87 FIGURE 45 WIRING DIAGRAM...
Page 90: ...FIGURE 48 SYSTEM CHARGE CHARTS RNL RPL 3 TON COOLING SYSTEM CHARGE CHART REFRIGERANT 410A 90...
Page 92: ...FIGURE 50 SYSTEM CHARGE CHARTS RNL RPL 4 TON COOLING SYSTEM CHARGE CHART REFRIGERANT 410A 92...
Page 108: ...108 CM 0314...