Rheem RLKN-B073 Series Installation Instructions Manual Download Page 12

C.  CLEARANCES

The following minimum clearances must be observed for proper unit performance

and serviceability.

      1. Unit is design certified for application on combustible flooring with 0" minimum

clearance.

      2. See Figure 6 for illustration of minimum installation-service clearances.

D.  ROOFTOP INSTALLATION

      1. Before locating the unit on the roof, make sure that the strength of the roof and

beams is adequate at that point to support the weight involved. (See specifica-

tion sheet for weight of unit.) This is very important and user’s responsibility.

      2. For  rigging  and  roofcurb  details,  see  Figures  8  and  9.  Use  field-furnished

spreaders.

      3. For roofcurb assembly, see Roofcurb Installation Instructions.

      4. If the roofcurb is not used, provisions for disposing of condensate water runoff

must be provided.

      5. The unit should be placed on a solid and level roofcurb or platform of adequate

strength. See Figure 10.

      6. The location of the unit on the roof should be such as to provide proper access

for inspection and servicing.

IMpORTANT:

If unit will not be put into service immediately, cover supply and return

openings to prevent excessive condensation.

IX. DUCTWORK

Ductwork  should  be  fabricated  by  the  installing  contractor  in  accordance  with  local

codes  and  NFPA90A.  Industry  manuals  may  be  used  as  a  guide  when  sizing  and

designing the duct system – contact Air Conditioning Contractors of America, 1513 16th

St. N.W., Washington, D.C. 20036.
The unit should be placed as close to the space to be air conditioned as possible allow-

ing clearance dimensions as indicated. Ducts should be run as directly as possible to

supply  and  return  outlets.  Use  of  non-flammable  waterproof  flexible  connectors  on

both supply and return connections at the unit to reduce noise transmission is recom-

mended.
It is preferable to install the unit on the roof of the structure if the registers or diffusers

are located on the wall or in the ceiling. A slab installation could be considered when

the registers are low on a wall or in the floor.
On ductwork exposed to outside air conditions of temperature and humidity, use a min-

imum of 2" of insulation and a vapor barrier. Distribution system in attic, furred space

or crawl space should be insulated with at least 2" of insulation with vapor barrier. One-

DO  NOT,  uNDER  ANy  CIRCuM-

STANCES, CONNECT RETuRN DuCT-

wORK  TO  ANy  OThER  hEAT  pRO-

DuCINg  DEVICE  SuCh  AS  A  fIRE-

pLACE  INSERT,  STOVE,  ETC.

uNAuThORIzED  uSE  Of  SuCh

DEVICES MAy RESuLT IN fIRE, CAR-

BON MONOxIDE pOISONINg, ExpLO-

SION, pROpERTy DAMAgE, SEVERE

pERSONAL INjuRy OR DEATh.

s

WARNING

!

fIguRE 10

pACKAgED AIR CONDITIONER

FLAT ROOFTOP INSTALLATION, ATTIC OR DROP CEILING DISTRIBUTION

SYSTEM. MOUNTED ON ROOFCURB. CURB MUST BE LEVEL

ST-A1142-10

12

Summary of Contents for RLKN-B073 Series

Page 1: ...TALLATION OR OPERATION FAILURE TO FOLLOW THESE INSTRUCTIONS MAY RESULT IN IMPROPER INSTALLATION ADJUSTMENT SERVICE OR MAINTENANCE POSSIBLY RESULTING IN FIRE ELECTRICAL SHOCK PROPERTY DAMAGE PERSONAL I...

Page 2: ...cation 10 B Outside Slab Installation 10 C Clearances 12 D Rooftop Installation 12 IX Ductwork 12 X Filters 13 XI Conversion Procedure 13 XII Condensate Drain 13 XIII Electrical Wiring 14 A Power Wiri...

Page 3: ...inish 1 Frequent washing of the cabinet fan blade and coil with fresh water will remove most of the salt or other contaminants that build up on the unit 2 Regular cleaning and waxing of the cabinet wi...

Page 4: ...cumulate in storage tanks Leak checking should never be done with a mixture of R 410A and air Leak checking can be performed safely with nitrogen or a mixture of R 410A and nitrogen 2 Quick Reference...

Page 5: ...5 fIguRE 1 6 TON MODEL fIguRE 2 BACK VIEw OUTDOOR COIL OUTDOOR FAN ST A1143 Designates Metric Conversion...

Page 6: ...fIguRE 3 SIDE VIEw fIguRE 4 fRONT VIEw ST A1143 Designates Metric Conversion ST A1143 Designates Metric Conversion 6...

Page 7: ...Op VIEw 7 2 5 32 55 4 5 8 118 26 660 4 502 114 13 1 8 333 4 1 2 114 13 1 8 333 77 15 32 1968 20 508 2 3 8 60 43 7 32 1098 2 3 8 60 2 3 8 60 RETURN AIR SUPPLY AIR DESIGNATES METRIC CONVERSIONS TOP VIEW...

Page 8: ...C t n a r e Drain Connection No Size in mm 1 1 25 4 1 1 25 4 1 1 25 4 1 1 25 4 Outdoor Fan Type Propeller Propeller Propeller Propeller No Used Diameter in mm 1 24 609 6 1 24 609 6 1 24 609 6 1 24 60...

Page 9: ...city Btu kW 46 000 13 48 46 000 13 48 Net Latent Capacity Btu kW 22 000 6 45 22 000 6 45 IEER 12 9 12 9 Net System Power kW 6 07 6 07 Compressor No Ty l 2 Stage l o r c S 1 l 2 Stage l o r c S 1 e p O...

Page 10: ...outdoor slab installations are shown in Figures 6 and 7 1 Select a location where external water drainage cannot collect around the unit 2 Provide a level concrete slab extending 3 beyond all four si...

Page 11: ...D C 39 CENTER OF GRAVITY 26 1 8 fIguRE 8 pACKAgED AIR CONDITIONER RIGGING FOR LIFTING CORNER wEIghTS By pERCENTAgE A B C D 23 29 21 27 ILL I300 ILL I301 fIguRE 9 pACKAgED AIR CONDITIONER ROOFCURB INS...

Page 12: ...A Industry manuals may be used as a guide when sizing and designing the duct system contact Air Conditioning Contractors of America 1513 16th St N W Washington D C 20036 The unit should be placed as c...

Page 13: ...sket to seal the covers 3 Secure the supply cover to the base of the unit with 1 screw engaging prepunched tab in unit base 4 Secure the return cover to the base of the unit with screws engaging prepu...

Page 14: ...s to the terminal block on the electric heater kit in the electric heat access area Connect the unit contactor pigtails to the appropriate fuse block on the heater kit Connect the ground wire to the g...

Page 15: ...he unit in the low voltage connection box located below the unit control box 3 Figure 13 shows representative low voltage connection diagrams Read your thermostat installation instructions for any spe...

Page 16: ...ll not be affected by unconditioned air sun or drafts from open doors or other sources READ installation instructions in thermostat package CAREFULLY because each has some different wiring requirement...

Page 17: ...3 3 3 3 3 3 RPM 3450 3450 3450 3450 3450 3450 HP Compressor 1 5 5 5 5 5 5 Amps RLA Comp 1 17 6 17 6 8 5 8 5 6 3 6 3 Amps LRA Comp 1 136 136 66 1 66 1 55 3 55 3 HP Compressor 2 Amps RLA Comp 2 Amps LRA...

Page 18: ...ter KBTU Hr 480 V Heater Amp 480 V Unit Min Ckt Ampacity 480 V Max Fuse Size 480V Min Circuit Ampacity 480V 480 V 480 V Min Ckt Ampacity 480V 480 VOLT THREE PHASE 60 HZ AUXILIARY ELECTRIC HEATER KITS...

Page 19: ...l p p u S r e w o P e l g n i S RHEEM Model Number r e n o i t i d n o C r i A t i K r e t a e H r e n o i t i d n o C r i A t i K r e t a e H No of Sequence Steps Rated Heater kW 600 V Heater KBTU H...

Page 20: ...0 980 1005 1030 wATTS 560 675 740 810 870 945 1020 1105 1200 RpM 850 895 920 945 960 990 1020 1040 1060 wATTS 605 720 780 850 910 990 1085 1175 1260 RpM 895 930 955 980 1000 1025 1045 1065 1090 wATTS...

Page 21: ...ressor running correctly 8 Check the refrigerant charge using the instructions located on compressor access panel Replace service port caps Service port cores are for system access only and will leak...

Page 22: ...one or more supplementary resist ance heaters XXIII REPLACEMENT PARTS Contact your local distributor for a complete parts list XXIV CHARGE INFORMATION Refer to the appropriate charge chart included in...

Page 23: ...temperatures and pressures to stabilize Sheets It is required to fine tune unit charge Indoor ambient temperature must be between 72 F and 82 F dry bulb at the indoor coil Measure liquid line tempera...

Page 24: ...unit is operating Defective overload protector Replace check for correct voltage Refrigerant undercharge Add refrigerant Registers sweat Low evaporator airflow Increase speed of blower or reduce rest...

Page 25: ...LOW PRESSURE CONTROL OUTDOOR FAN MOTOR PLUG RUN CAPACITOR TERMINAL BLOCK LOW VOLTAGE TIME DELAY CONTROL WIRE NUT TCJW 1 CONNECTORS SUITABLE FOR USE WITH COPPER CONDUCTORS ONLY 2 COMPRESSOR MOTOR THER...

Page 26: ...SURE CONTROL INDOOR BLOWER MOTOR BELT DRIVE LOW AMBIENT COOLING CONTROL LOW PRESSURE CONTROL OUTDOOR FAN MOTOR PLUG RUN CAPACITOR TERMINAL BLOCK LOW VOLTAGE TIME DELAY CONTROL WIRE NUT TCJW 1 CONNECTO...

Page 27: ...27...

Page 28: ...28 CM 0218...

Reviews: