ENGINEERING DATA
➀
Model No.
Flow Rate
CFM [L/s]
Static Pressure
in w.c. [kPa]
Throw
➁ ➂
Feet [m]
Neck Velocity
fpm [m/s]
Noise Level
➃
(dbA)
RXRN-AA76
4600 [2171]
0.31 [0.077]
25-34 [7.6-10.4]
922 [4.7]
40
4800 [2265]
0.32 [0.080]
26-35 [7.9-10.7]
962 [4.9]
40
5000 [2359]
0.34 [0.085]
27-36 [8.2-11.0]
1002 [5.1]
40
5200 [2454]
0.36 [0.090]
30-39 [9.1-11.9]
1043 [5.3]
45
5400 [2548]
0.39 [0.097]
32-41 [9.8-12.5]
1083 [5.5]
45
NOTES:
➀
All data is based on the air diffusion council guidelines.
➁
Throw data is based on 75 FPM Terminal Velocities using isothermal air.
➂
Throw is based on diffuser blades being directed in a straight pattern.
➃
Actual noise levels may vary due to duct design and do not include transmitted unit noise.
Adequate duct attenuation must be provided to reduce sound output from the unit.
[ ] Designates Metric Conversions
Illustration
ADS-7951-07A
Illustration
ADS-7951-07B
Illustration
ADS-7951-07C
CONCENTRIC DIFFUSER—FLUSH
18" x 32" [457.2 x 813 mm]
RXRN-AA76 (12.5 & 15 Ton [44.0 & 52.8 kW] Models)
For Use With Downflow Transition (RXMC-CF06)
and 18" x 32" [457.2 x 813 mm]
Supply and Return Ducts
■
All aluminum diffuser with aluminum return
air eggcrate.
■
Built-in anti-sweat gasket.
■
Molded fiberglass supports.
■
Built-in hanging supports.
■
Diffuser box constructed of sheetmetal
insulated with 1" [25.4 mm] 1.5 lbs.
[.7 kg] duct liner.
Summary of Contents for RKNL-B073CL15E
Page 39: ...Air Dimensional Data RKNL B Series 39 Designates Metric Conversions...
Page 70: ...Air Wiring Diagrams RKNL B Series 70...
Page 71: ...Air Wiring Diagrams RKNL B Series 71...
Page 72: ...Air Wiring Diagrams RKNL B Series 72...
Page 73: ...Air Wiring Diagrams RKNL B Series 73...
Page 74: ...Air Wiring Diagrams RKNL B Series 74...
Page 75: ...Air Wiring Diagrams RKNL B Series 75...
Page 76: ...Air Wiring Diagrams RKNL B Series 76...
Page 77: ...Air Wiring Diagrams RKNL B Series 77...
Page 79: ...Air Notes RKNL B Series 79...