Air
Gross Systems Performance Data
RKNL-B Series
27
GROSS SYSTEMS PERFORMANCE DATA—B151
ENTERING INDOOR AIR @ 80°F [26.7°C] dbE
➀
wbE
71°F [21.7°C]
67°F [19.4°C]
63°F [17.2°C]
CFM [L/s]
5070 [2393]
4225 [1994]
3380 [1595]
5070 [2393]
4225 [1994]
3380 [1595]
5070 [2393]
4225 [1994]
3380 [1595]
DR
➀
0.11
0.08
0.05
0.11
0.08
0.05
0.11
0.08
0.05
O
U
T
D
O
O
R
D
R
Y
B
U
L
B
T
E
M
P
E
R
A
T
U
R
E
°F
[°C]
75
[23.9]
Total BTUH [kW]
Sens BTUH [kW]
Power
180.7 [52.9]
98.6 [28.9]
9.2
174.3 [51.1]
90.2 [26.4]
9.1
168 [49.2]
81.8 [24.0]
8.9
171.0 [50.1]
119.8 [35.1]
9
165 [48.3]
109.6 [32.1]
8.8
159 [46.6]
99.4 [29.1]
8.7
163 [47.8]
137.4 [40.3]
8.8
157.3 [46.1]
125.7 [36.8]
8.6
151.6 [44.4]
114 [33.4]
8.5
80
[26.7]
Total BTUH [kW]
Sens BTUH [kW]
Power
176.1 [51.6]
98.5 [28.9]
9.7
169.9 [49.8]
90.1 [26.4]
9.5
163.7 [48.0]
81.7 [23.9]
9.4
166.4 [48.8]
119.7 [35.1]
9.5
160.6 [47.1]
109.5 [32.1]
9.3
154.7 [45.3]
99.3 [29.1]
9.2
158.4 [46.4]
137.3 [40.2]
9.3
152.9 [44.8]
125.6 [36.8]
9.1
147.3 [43.2]
113.9 [33.4]
8.9
85
[29.4]
Total BTUH [kW]
Sens BTUH [kW]
Power
171.3 [50.2]
97.8 [28.7]
10.2
165.3 [48.4]
89.4 [26.2]
10
159.3 [46.7]
81.1 [23.8]
9.9
161.6 [47.4]
119 [34.9]
10
156 [45.7]
108.8 [31.9]
9.8
150.3 [44.0]
98.7 [28.9]
9.6
153.6 [45.0]
136.6 [40.0]
9.8
148.3 [43.4]
124.9 [36.6]
9.6
142.9 [41.9]
113.3 [33.2]
9.4
90
[32.2]
Total BTUH [kW]
Sens BTUH [kW]
Power
166.4 [48.8]
96.4 [28.2]
10.8
160.5 [47.0]
88.2 [25.8]
10.6
154.7 [45.3]
79.9 [23.4]
10.4
156.7 [45.9]
117.6 [34.5]
10.5
151.2 [44.3]
107.6 [31.5]
10.4
145.7 [42.7]
97.5 [28.6]
10.2
148.7 [43.6]
135.2 [39.6]
10.3
143.5 [42.0]
123.7 [36.2]
10.1
138.2 [40.5]
112.1 [32.9]
9.9
95
[35]
Total BTUH [kW]
Sens BTUH [kW]
Power
161.2 [47.2]
94.4 [27.7]
11.3
155.6 [45.6]
86.3 [25.3]
11.1
149.9 [43.9]
78.3 [22.9]
10.9
151.5 [44.4]
115.6 [33.9]
11.1
146.2 [42.8]
105.7 [31.0]
10.9
140.9 [41.3]
95.8 [28.1]
10.7
143.5 [42.1]
133.2 [39.0]
10.9
138.5 [40.6]
121.8 [35.7]
10.7
133.5 [39.1]
110.4 [32.4]
10.5
100
[37.8]
Total BTUH [kW]
Sens BTUH [kW]
Power
155.9 [45.7]
91.7 [26.9]
11.9
150.4 [44.1]
83.9 [24.6]
11.7
144.9 [42.5]
76 [22.3]
11.5
146.2 [42.8]
112.9 [33.1]
11.7
141 [41.3]
103.3 [30.3]
11.5
135.9 [39.8]
93.6 [27.4]
11.3
138.2 [40.5]
130.5 [38.2]
11.5
133.3 [39.1]
119.4 [35]
11.3
128.5 [37.7]
108.2 [31.7]
11.1
105
[40.6]
Total BTUH [kW]
Sens BTUH [kW]
Power
150.3 [44.1]
88.4 [25.9]
12.6
145.1 [42.5]
80.8 [23.7]
12.4
139.8 [41.0]
73.3 [21.5]
12.1
140.6 [41.2]
109.6 [32.1]
12.3
135.7 [39.8]
100.2 [29.4]
12.1
130.8 [38.3]
90.9 [26.6]
11.9
132.7 [38.9]
127.2 [37.3]
12.1
128 [37.5]
116.3 [34.1]
11.9
123.4 [36.1]
105.5 [30.9]
11.7
110
[43.3]
Total BTUH [kW]
Sens BTUH [kW]
Power
144.6 [42.4]
84.4 [24.7]
13.2
139.6 [40.9]
77.2 [22.6]
13
134.5 [39.4]
70 [20.5]
12.8
134.9 [39.5]
105.6 [30.9]
13
130.2 [38.2]
96.6 [28.3]
12.8
125.5 [36.8]
87.6 [25.7]
12.6
126.9 [37.2]
123.2 [36.1]
12.8
122.5 [35.9]
112.7 [33]
12.6
118 [34.6]
102.2 [29.9]
12.3
115
[46.1]
Total BTUH [kW]
Sens BTUH [kW]
Power
138.7 [40.7]
79.8 [23.4]
13.9
133.9 [39.2]
73 [21.4]
13.7
129 [37.8]
66.2 [19.4]
13.4
129 [37.8]
101 [29.6]
13.7
124.5 [36.5]
92.4 [27.1]
13.5
120 [35.2]
83.8 [24.5]
13.2
121 [35.5]
118.6 [34.8]
13.5
116.8 [34.2]
108.5 [31.8]
13.2
112.6 [33]
98.4 [28.8]
13
120
[48.9]
Total BTUH [kW]
Sens BTUH [kW]
Power
132.6 [38.9]
74.6 [21.8]
14.7
128 [37.5]
68.2 [20.0]
14.4
123.3 [36.1]
61.8 [18.1]
14.1
122.9 [36.0]
95.8 [28.1]
14.4
118.6 [34.8]
87.6 [25.7]
14.2
114.3 [33.5]
79.4 [23.3]
13.9
115 [33.7]
113.4 [33.2]
14.2
110.9 [32.5]
103.7 [30.4]
14
106.9 [31.3]
94 [27.6]
13.7
125
[51.7]
Total BTUH [kW]
Sens BTUH [kW]
Power
126.4 [37.0]
68.7 [20.1]
15.4
121.9 [35.7]
62.8 [18.4]
15.1
117.5 [34.4]
56.9 [16.7]
14.9
116.7 [34.2]
89.9 [26.3]
15.2
112.6 [33.0]
82.2 [24.1]
14.9
108.5 [31.8]
74.5 [21.8]
14.7
108.7 [31.8]
107.5 [31.5]
15
104.9 [30.7]
98.3 [28.8]
14.7
101 [29.6]
89.1 [26.1]
14.4
DR —Depression ratio
dbE —Entering air dry bulb
wbE —Entering air wet bulb
Total —Total capacity x 1000 BTUH
Sens —Sensible capacity x 1000 BTUH
Power —KW input
NOTES:
➀
When the entering air dry bulb is other than 80°F [27°C], adjust the sensible
capacity from the table by adding [1.10 x CFM x (1 – DR) x (dbE – 80)].
[ ] Designates Metric Conversions
Summary of Contents for RKNL-B073CL15E
Page 39: ...Air Dimensional Data RKNL B Series 39 Designates Metric Conversions...
Page 70: ...Air Wiring Diagrams RKNL B Series 70...
Page 71: ...Air Wiring Diagrams RKNL B Series 71...
Page 72: ...Air Wiring Diagrams RKNL B Series 72...
Page 73: ...Air Wiring Diagrams RKNL B Series 73...
Page 74: ...Air Wiring Diagrams RKNL B Series 74...
Page 75: ...Air Wiring Diagrams RKNL B Series 75...
Page 76: ...Air Wiring Diagrams RKNL B Series 76...
Page 77: ...Air Wiring Diagrams RKNL B Series 77...
Page 79: ...Air Notes RKNL B Series 79...