Rheem RKNL-B073CL15E Manual Download Page 37

Air

Dimensional Data

RKNL-B Series

37

[    ] Designates Metric Conversions

BOTTOM VIEW

Illustration

ST-A0715-03-X1

Summary of Contents for RKNL-B073CL15E

Page 1: ...M NO R11 855 REV 1 Air Package Gas Electric RKNL B Series RKNL B Series Rheem Commercial Classic Series Package Gas Electric Unit Nominal Sizes 6 12 5 Tons 21 1 44 0 kW ASHRAE 90 1 2010 Compliant Mode...

Page 2: ...9 Selection Procedure 10 General Data RKNL Series 11 23 General Data Notes 24 Gross Systems Performance Data RKNL Series 25 27 Indoor Airflow Performance RKNL Series 28 32 Electrical Data RKNL Series...

Page 3: ...ce Powder Paint Finish meets ASTMB117 steel coated on each side for maximum protection G90 galvanized One piece top cover and one piece base pan with drawn supply and return opening for superior water...

Page 4: ...d on the underside of the basepan removing areas that would allow for potential moisture accumula tion which can facilitate growth of harmful bacteria All insulation is secured with both adhesive and...

Page 5: ...dentifies the com pressor circuit high pressure connec tion and low pressure connection With the gauge ports mounted exter nally an accurate diagnostic of system operation can be performed quickly and...

Page 6: ...t seal and provides strain relief Care is also taken to tuck raw edges of insulation behind sheet metal to improve indoor air quality The furnace compartment contains the latest furnace technology on...

Page 7: ...it is designed for both downflow or horizontal applications for job configura tion flexibility The return air compartment can also contain an economizer Two models exits one for downflow applications...

Page 8: ...e M Belt Drive High Static N Belt Drive High Static B090 Only Electrical Designation C 208 230 V 3 PH 60 Hz D 460 V 3 PH 60 Hz Y 575 V 3 PH 60 Hz Cooling Capacity BTUH kW 073 72 000 21 10 090 90 000 2...

Page 9: ...ion of options If no factory option s is required nothing follows the model number Step 1 After a basic rooftop model is selected choose a two character option code from the FACTORY INSTALLED OPTION S...

Page 10: ...apply to data obtained in step 2 to obtain gross capacity Total Capacity 118 900 x 0 98 116 522 BTUH 34 12 kW Sensible Capacity 92 268 x 0 95 87 655 BTUH 25 67 kW Power Input 8 950 x 0 99 8 861 Watts...

Page 11: ...d Louvered Louvered Tube Type Rifled Rifled Rifled Rifled Tube Size in mm OD 0 375 9 5 0 375 9 5 0 375 9 5 0 375 9 5 Face Area sq ft sq m 13 5 1 25 13 5 1 25 13 5 1 25 13 5 1 25 Rows FPI FPcm 1 22 9 1...

Page 12: ...0 375 9 5 0 375 9 5 0 375 9 5 Face Area sq ft sq m 13 5 1 25 13 5 1 25 27 2 51 27 2 51 Rows FPI FPcm 1 22 9 1 22 9 1 22 9 1 22 9 Indoor Coil Fin Type Louvered Louvered Louvered Louvered Tube Type Rifl...

Page 13: ...27 2 51 27 2 51 Rows FPI FPcm 1 22 9 1 22 9 1 22 9 1 22 9 Net Latent Capacity Btu kW 26 900 7 88 26 900 7 88 26 900 7 88 26 900 7 88 Indoor Coil Fin Type Louvered Louvered Louvered Louvered Tube Type...

Page 14: ...5 9 5 0 375 9 5 Face Area sq ft sq m 27 2 51 27 2 51 27 2 51 27 2 51 Rows FPI FPcm 1 22 9 1 22 9 1 22 9 1 22 9 Net Latent Capacity Btu kW 26 900 7 88 26 900 7 88 26 900 7 88 26 900 7 88 Indoor Coil Fi...

Page 15: ...5 9 5 0 375 9 5 Face Area sq ft sq m 27 2 51 27 2 51 27 2 51 27 2 51 Rows FPI FPcm 1 22 9 1 22 9 1 22 9 1 22 9 Net Latent Capacity Btu kW 26 900 7 88 26 900 7 88 26 900 7 88 26 900 7 88 Indoor Coil Fi...

Page 16: ...375 9 5 Face Area sq ft sq m 27 2 51 27 2 51 27 2 51 27 2 51 Rows FPI FPcm 1 22 9 2 18 7 2 18 7 2 18 7 Net Latent Capacity Btu kW 26 900 7 88 23 000 6 74 23 000 6 74 23 000 6 74 Indoor Coil Fin Type L...

Page 17: ...375 9 5 Face Area sq ft sq m 27 2 51 27 2 51 27 2 51 27 2 51 Rows FPI FPcm 2 18 7 2 18 7 2 18 7 2 18 7 Net Latent Capacity Btu kW 23 000 6 74 23 000 6 74 23 000 6 74 23 000 6 74 Indoor Coil Fin Type L...

Page 18: ...375 9 5 Face Area sq ft sq m 27 2 51 27 2 51 27 2 51 27 2 51 Rows FPI FPcm 2 18 7 2 18 7 2 18 7 2 22 9 Net Latent Capacity Btu kW 23 000 6 74 23 000 6 74 23 000 6 74 29 200 8 56 Indoor Coil Fin Type L...

Page 19: ...5 0 375 9 5 Face Area sq ft sq m 27 2 51 27 2 51 27 2 51 27 2 51 Rows FPI FPcm 2 22 9 2 22 9 2 22 9 2 22 9 Net Latent Capacity Btu kW 29 200 8 56 29 200 8 56 29 200 8 56 29 200 8 56 Indoor Coil Fin Ty...

Page 20: ...9 5 0 375 9 5 Face Area sq ft sq m 27 2 51 27 2 51 27 2 51 27 2 51 Rows FPI FPcm 2 22 9 2 22 9 2 22 9 2 22 9 Net Latent Capacity Btu kW 29 200 8 56 29 200 8 56 29 200 8 56 29 200 8 56 Indoor Coil Fin...

Page 21: ...oChannel MicroChannel Tube Size in mm OD 0 375 9 5 1 25 4 1 25 4 1 25 4 Face Area sq ft sq m 27 2 51 27 2 51 27 2 51 27 2 51 Rows FPI FPcm 2 22 9 2 23 9 2 23 9 2 23 9 Indoor Coil Fin Type Louvered Lou...

Page 22: ...1 25 4 1 25 4 1 25 4 1 25 4 Face Area sq ft sq m 27 2 51 27 2 51 27 2 51 27 2 51 Rows FPI FPcm 2 23 9 2 23 9 2 23 9 2 23 9 Indoor Coil Fin Type Louvered Louvered Louvered Louvered Tube Type Rifled Rif...

Page 23: ...nnel Tube Size in mm OD 1 25 4 1 25 4 1 25 4 Face Area sq ft sq m 27 2 51 27 2 51 27 2 51 Rows FPI FPcm 2 23 9 2 23 9 2 23 9 Indoor Coil Fin Type Louvered Louvered Louvered Tube Type Rifled Rifled Rif...

Page 24: ...tion program which is based on AHRI Standard 340 360 2 EER and or SEER are rated at AHRI conditions and in accordance with DOE test procedures 3 IEER is rated in accordance with AHRI Standard 340 360...

Page 25: ...capacity x 1000 BTUH Sens Sensible capacity x 1000 BTUH Power KW input NOTES When the entering air dry bulb is other than 80 F 27 C adjust the sensible capacity from the table by adding 1 10 x CFM x...

Page 26: ...l capacity x 1000 BTUH Sens Sensible capacity x 1000 BTUH Power KW input NOTES When the entering air dry bulb is other than 80 F 27 C adjust the sensible capacity from the table by adding 1 10 x CFM x...

Page 27: ...kW Sens BTUH kW Power 155 9 45 7 91 7 26 9 11 9 150 4 44 1 83 9 24 6 11 7 144 9 42 5 76 22 3 11 5 146 2 42 8 112 9 33 1 11 7 141 41 3 103 3 30 3 11 5 135 9 39 8 93 6 27 4 11 3 138 2 40 5 130 5 38 2 11...

Page 28: ...1 4 35 1 5 37 External Static Pressure Inches of Water kPa Voltage 208 230 460 575 3 phase Drive Package L M Motor H P W 1 5 1118 6 1 5 1118 6 Blower Sheave AK66 AK66 Motor Sheave 1VP 44 1VP 50 Turns...

Page 29: ...928 1880 957 1965 987 2051 1016 2136 1045 2222 2414 1075 2307 3300 1557 592 954 628 1096 660 1168 692 731 789 1431 818 1493 848 1555 877 1617 906 1859 935 1944 965 2029 994 2115 1023 2200 1053 Capacit...

Page 30: ...100 1935 726 1692 754 1766 781 1841 809 1915 836 1990 864 2064 922 2091 942 2204 963 2318 983 2431 1003 2545 1024 2658 1056 2772 1084 2885 1084 2999 1105 3112 1144 3226 Air Flow CFM L s 1148 2606 RPM...

Page 31: ...1 1021 3025 1041 3138 1061 3252 1124 3365 1151 3479 1122 3592 952 2585 973 2679 993 2793 1013 2906 1033 3020 1054 3133 1110 3247 1138 3360 1115 3474 1127 3468 1135 3587 4800 2265 821 2271 848 2345 876...

Page 32: ...3 0 1 02 0 2 05 0 3 07 0 4 10 0 5 12 0 6 15 0 7 17 0 8 20 0 9 22 1 0 25 1 1 27 1 2 30 1 3 32 1 4 35 1 5 37 1 6 40 1 7 42 1 8 45 1 9 47 2 0 50 External Static Pressure Inches of Water kPa Voltage 208 2...

Page 33: ...450 3450 3450 3450 3450 3450 3450 3450 3450 3450 HP Compressor 1 6 6 5 6 5 6 3 1 4 3 1 4 3 1 4 3 1 4 3 1 4 Amps RLA Comp 1 19 6 19 6 19 6 19 6 8 2 8 2 6 6 6 6 13 1 13 1 13 1 13 1 13 1 13 1 6 1 6 1 Amp...

Page 34: ...1 4 3450 3 600 2 20 20 575 518 632 38 1 7 3 8 8 2 3 208 230 1 4 7 4 7 1 2 1 2 1 3 1 208 230 2 16 16 91 91 3 3 4 3450 3 200 230 2 60 60 50 50 208 230 187 253 3 460 1 4 2 3 460 1 2 4 0 7 1 3 1 460 2 7 1...

Page 35: ...1 3 1 460 2 9 8 52 4 1 4 3450 3 480 2 30 25 460 414 506 82 6 82 6 18 8 18 8 5 4 2 3 575 1 1 5 0 5 1 3 1 575 2 5 7 38 9 4 1 4 3450 3 575 2 20 20 575 518 632 3 208 230 1 15 15 3 3 208 230 1 5 6 5 6 1 15...

Page 36: ...5 3 4 Amps LRA Comp 1 54 Amps RLA Comp 2 Unit Information Unit Operating Voltage Range 7 4 518 632 Condenser Motor No 2 Volts 575 Phase 1 HP 1 2 Amps FLA each 0 5 Amps LRA each 2 2 Evaporator Fan No...

Page 37: ...Air Dimensional Data RKNL B Series 37 Designates Metric Conversions BOTTOM VIEW Illustration ST A0715 03 X1...

Page 38: ...38 SUPPLY AND RETURN DIMENSIONS FOR DOWNFLOW APPLICATIONS SUPPLY AND RETURN DIMENSIONS FOR HORIZONTAL APPLICATIONS RECOMMENDED DUCT DIMENSIONS ARE 26 Designates Metric Conversions Illustration ST A07...

Page 39: ...Air Dimensional Data RKNL B Series 39 Designates Metric Conversions...

Page 40: ...5 38 60 38 17 24 Roof Curb 24 140 63 50 135 61 23 A B C D 33 27 17 23 Capacity Tons kW 6 12 5 21 1 44 0 Corner Weights by Percentage CLEARANCES The following minimum clearances must be observed for pr...

Page 41: ...low Transition Rect to Rect 18 x 28 RXMC CE05 18 8 2 16 7 3 No Compressor Time Delay Relay Kit RXMD A04 2 1 0 1 5 No Low Ambient Control Kit 1 Per Compressor RXRZ C02 3 1 4 2 1 0 Yes Freeze Stat Kit R...

Page 42: ...esentative Actual models may vary For detailed thermostat match up information see specification sheet form number T11 001 300 Series Deluxe Programmable 400 Series Special Applications Programmable 5...

Page 43: ...lable CO2 Input Sensor Available Field Assembled Hood Ships with Economizer Economizer Ships Complete for Downflow Duct Application Optional Remote Minimum Position Potentiometer Honeywell S963B1128 i...

Page 44: ...Low Leakage Dampers Slip In Design for Easy Installation Plug In Polarized 12 pin Electrical Connections Pre Configured No Field Adjustments Necessary Standard Barometric Relief Damper Single Enthalpy...

Page 45: ...of Fans Volts Phase HP ea Low Speed RXRX BFF02C 2 208 230 1 0 33 2200 1038 1518 2500 1179 High Speed 1670 1 48 FLA ea 3 6 LRA ea RXRX BFF02D 2 460 1 0 33 2200 1038 1518 2500 1179 1670 0 75 1 8 RXRX BF...

Page 46: ...Series 46 FRESH AIR DAMPER MOTORIZED DAMPER KIT RXRX AW02 Motor Kit for AXRF KDA1 Illustration ST A0886 38 7951 17a AXRF KDA1 Manual DOWNFLOW OR HORIZONTAL APPLICATION Illustration ST 7951 17 Designa...

Page 47: ...ssories RKNL B Series 47 FRESH AIR DAMPER Cont AXRF JDA1 Manual AXRF JDB1 Motorized Illustration ADS 7937 58 Illustration ST A0901 01 HORIZONTAL APPLICATION DOWNFLOW APPLICATION Designates Metric Conv...

Page 48: ...ttom pan to match the Thru the Curb electrical connection opening provided on the unit base pan 1 25 mm x 4 102 mm Nailer provided Insulating panels not required because of insulated outdoor base pan...

Page 49: ...RXRK E50 RXRX CDCE50 RGF 200075 RGG REG RCG 075 RGF REF RCF 085 RGF REF RCF 100 RGG REG RCG 100 RXRK E54 RXRX CFCE54 RGF REF RCF 125 RXRK E56 RXRX CFCE56 NOTE Ductwork modifications may be necessary i...

Page 50: ...Air Accessories RKNL B Series 50 ROOFCURB ADAPTERS Cont RXRX CDCE50 Illustration ADS 7952 02 Sheet 2 Illustration ADS 7952 02 Sheet 1 Designates Metric Conversions TOP VIEW...

Page 51: ...Air Accessories RKNL B Series 51 ROOFCURB ADAPTERS Cont RXRX CFCE54 Illustration ADS 7952 01 Sheet 1 Illustration ADS 7952 01 Sheet 2 Designates Metric Conversions TOP VIEW...

Page 52: ...Air Accessories RKNL B Series 52 ROOFCURB ADAPTERS Cont RXRX CFCE56 Illustration ADS 7952 03 Sheet 2 Illustration ADS 7952 03 Sheet 1 Designates Metric Conversions TOP VIEW...

Page 53: ...Air Accessories RKNL B Series 53 ROOFCURB ADAPTERS Cont RXRX CGCC12 Illustration ADS 7952 04 Sheet 1 Illustration ADS 7952 04 Sheet 2 Designates Metric Conversions TOP VIEW...

Page 54: ...L B Series 54 Illustration ST A0881 02 Designates Metric Conversions CONCENTRIC DIFFUSER APPLICATION Illustration ST A0840 02 DOWNFLOW TRANSITION DRAWINGS RXMC CE05 Used with RXRN AA61 or RXRN AA71 Co...

Page 55: ...Air Accessories RKNL B Series 55 Designates Metric Conversions Illustration ST A0881 03 DOWNFLOW TRANSITION DRAWINGS RXMC CF06 Used with RXRN AA66 or RXRN AA76 Concentric Diffusers...

Page 56: ...Air Accessories RKNL B Series 56 DOWNFLOW TRANSITION DRAWINGS RXMC CD04 Used with RXRN FA65 or RXRN FA75 Concentric Diffusers 795103 Illustration ADS 7951 03 Designates Metric Conversions...

Page 57: ...Terminal Velocities using isothermal air Throw is based on diffuser blades being directed in a straight pattern Actual noise levels may vary due to duct design and do not include transmitted unit noi...

Page 58: ...Pa Throw Feet m Neck Velocity fpm m s Noise Level dbA RXRN AA61 3600 1699 0 17 0 042 25 33 7 6 10 1 851 4 3 30 3800 1793 0 18 0 045 27 35 8 2 10 7 898 4 6 30 4000 1888 0 21 0 052 29 37 8 8 11 3 946 4...

Page 59: ...Pa Throw Feet m Neck Velocity fpm m s Noise Level dbA RXRN AA66 4600 2171 0 31 0 077 26 31 7 9 9 4 841 4 3 30 4800 2265 0 32 0 080 27 32 8 2 9 8 878 4 5 30 5000 2359 0 34 0 085 28 33 8 5 10 1 915 4 6...

Page 60: ...fusion council guidelines Throw data is based on 75 FPM Terminal Velocities using isothermal air Throw is based on diffuser blades being directed in a straight pattern Actual noise levels may vary due...

Page 61: ...bA RXRN AA71 3600 1699 0 17 0 042 22 29 6 7 8 8 844 4 3 35 3800 1793 0 18 0 045 22 30 6 7 9 1 891 4 5 40 4000 1888 0 21 0 052 24 33 7 3 10 1 938 4 8 40 4200 1982 0 24 0 060 26 35 7 9 10 7 985 5 0 40 4...

Page 62: ...ased on diffuser blades being directed in a straight pattern Actual noise levels may vary due to duct design and do not include transmitted unit noise Adequate duct attenuation must be provided to red...

Page 63: ...13 23 A Thermostats 1 Thermostat must a energize both W and G when calling for heat b have capability to energize 2 different stages of cooling and 2 different stages of heating c must include capabi...

Page 64: ...adhesive shall meet NFPA 90A requirements for flame spread and smoke generation 7 Unit casing shall be capable of withstanding 1000 hour salt spray exposure per ASTM B117 scribed specimen 8 Unit casin...

Page 65: ...ing to unit gas valve shall enter the unit cabinet at a single location on side of unit horizontal plane b Thru the base capability i Standard unit shall have a thru the base gas line location using a...

Page 66: ...l be aluminum lanced plate fins mechanically bonded to seamless internally grooved copper tubes with all joints brazed Note 12 1 2 ton utilizes MicroChannel condensing coil b Evaporator and condenser...

Page 67: ...ls to provide free cooling with outdoor air when temperature and or humidity are below setpoints e Shall be equipped with gear driven dampers for both the outdoor ventilation air and the return air fo...

Page 68: ...ed k Outlet shall be field installed and internally mounted with easily accessible 115 v female receptacle l Outlet shall include 15 amp GFI receptacle with independent fuse protection m Outlet shall...

Page 69: ...fire alarm control panel ii Two Form C auxiliary alarm relays for interface with rooftop unit or other equipment iii One Form C supervision trouble relay to control the operation of the Trouble LED o...

Page 70: ...Air Wiring Diagrams RKNL B Series 70...

Page 71: ...Air Wiring Diagrams RKNL B Series 71...

Page 72: ...Air Wiring Diagrams RKNL B Series 72...

Page 73: ...Air Wiring Diagrams RKNL B Series 73...

Page 74: ...Air Wiring Diagrams RKNL B Series 74...

Page 75: ...Air Wiring Diagrams RKNL B Series 75...

Page 76: ...Air Wiring Diagrams RKNL B Series 76...

Page 77: ...Air Wiring Diagrams RKNL B Series 77...

Page 78: ...rranties including applicable terms and conditions contact your local contractor or the Manufacturer for a copy of the product warranty certificate Compressor 3 Phase Commercial Applications Five 5 Ye...

Page 79: ...Air Notes RKNL B Series 79...

Page 80: ...em com In keeping with its policy of continuous progress and product improvement Rheem reserves the right to make changes without notice PRINTED IN U S A 10 12 QG FORM NO R11 855 REV 1 Rheem Canada Lt...

Reviews: