Combustion air must be free of acid
forming chemicals; such as sulphur,
fluorine and chlorine. These elements
are found in aerosol sprays,
detergents, bleaches, cleaning
solvents, air fresheners, paint and
varnish removers, refrigerants and
many other commercial and household
products. Vapors from these products
when burned in a gas flame form acid
compounds. The acid compounds
increase the dew point temperature of
the flue products and are highly
corrosive after they condense.
ALL FURNACE INSTALLATIONS
MUST COMPLY WITH THE
NATIONAL FUEL GAS CODE AND
LOCAL CODES TO PROVIDE
ADEQUATE COMBUSTION AND
VENTILATION AIR FOR THE
FURNACE. FAILURE TO DO SO CAN
CREATE HAZARDOUS CONDITIONS
RESULTING IN PROPERTY
DAMAGE, BODILY INJURY OR
DEATH FROM SMOKE, FIRE OR
CARBON MONOXIDE.
Combustion air requirements are
determined by whether the furnace is
in an open (unconfined) area or in a
confined space such as a closet or
small room.
EXAMPLE 1.
FURNACE LOCATED IN AN
UNCONFINED SPACE
Using indoor air for combustion.
An unconfined space must have at
least 50 cubic feet for each 1,000 Btuh
of the total input for all appliances in
the space. Here are a few examples of
the room sizes required for different
inputs. The sizes are based on 8 foot
ceilings.
Btuh
Minimum Sq. Feet
Typical Room Size
Input
With 8' Ceiling
With 8' Ceiling
50,000
312
14
*
x24
*
or 18
*
x18
*
75,000
469
15
*
x31
*
or 20
*
x24
*
100,000
625
20
*
x31
*
or 25
*
x25
*
125,000
833
23
*
x34
*
or 26
*
x30
*
150,000
938
25
*
x38
*
or 30
*
x31
*
If the open space containing the
furnace is in a building with tight
construction (contemporary
construction), outside air may still be
required for the furnace to operate and
vent properly. Outside air openings
should be sized the same as for a
confined space.
11
WARNING
!
FIGURE 7
AIR FROM ATTIC/CRAWL SPACE
FURNACE LOCATED IN A
CONFINED SPACE
A confined space is any space smaller
than shown above as unconfined.
A. USING INDOOR AIR FOR
COMBUSTION
When using indoor air for
combustion a confined space must
have
two openings into the space.
One opening must be within 12
inches of the ceiling and the other
must be within 12 inches of the
floor.
The openings must be sized
by how they are connected to the
heated area or to the outside, and
by the input of all appliances in the
space.
The openings must
each
have at
least 100 square inches of free area.
Each opening must have at least
one square inch of free area for
each 1,000 BTUH of total input in
the space. Here are some typical
openings required.
Btuh
Free Area
Input
Each Opening
50,000
100 Square Inches
100,000
100 Square Inches
150,000
150 Square Inches
IMPORTANT:
Do not take air from a
heated space with a fireplace, exhaust
fan or other device that may produce a
negative pressure.
B. USING OUTDOOR AIR FOR
COMBUSTION
The confined space must
communicate with the outdoors in
accordance with methods 1 or 2.
The minimum dimension of air
openings shall not be less than 3
inches. Where ducts are used, they
shall be of the same cross-sectional
area as the free area of the
openings to which they connect.
Method 1
Two permanent openings, one located
within 12 inches of the top and one
located within 12 inches of the bottom,
of the enclosure shall be provided. The
openings shall communicate directly,
or by ducts, with the outdoors or
spaces (crawl or attic) that freely
communicate with the outdoors.
a. Where directly communicating with
the outdoors or where
communicating to the outdoors
through vertical ducts, each opening
shall have a minimum free area of 1
square inch for each 4,000 BTUH of
total appliance input rating in the
enclosure. Here are some typical
sizes.
Btuh
Free Area
Round Pipe
Input
Each Opening
Size
50,000
12.5 Square Inches
4
(
75,000
18.75 Square Inches
5
(
100,000
25 Square Inches
6
(
125,000
31.25 Square Inches
7
(
150,000
37.5 Square Inches
7
(
b. Where communicating with outdoors
through horizontal ducts, each
opening shall have a minimum free
area of 1 square inch for each 2,000
BTUH of total input rating of all
equipment in the enclosure. Here
are some typical sizes.
Summary of Contents for RGLK
Page 21: ...21 FIGURE 16 UTEC NO 1095 100 CONTROL BOARD TWINNING CONNECTION SINGLE STAGE OPERATION I685 ...
Page 22: ...22 FIGURE 17 UTEC NO 1095 100 CONTROL BOARD TWINNING CONNECTION TWO STAGE OPERATION I684 ...
Page 30: ...30 FIGURE 25 FILTER RETAINING RODS SIDE RETURN FIGURE 26 DOWNFLOW FILTER INSTALLATION ...
Page 32: ...FIGURE 27 INTEGRATED FURNACE CONTROL IFC TROUBLESHOOTING GUIDE FOR UTEC 1095 100 32 ...
Page 33: ...33 ...
Page 34: ...FIGURE 28 UTEC 1095 100 INTEGRATED FURNACE CONTROL 34 ...
Page 35: ...35 ...
Page 36: ...36 CM 997 Rheem Manufacturing Company Air Conditioning Division Fort Smith Arkansas ...