![Rheem Raypak Hi Delta 302C Installation And Operation Manual Download Page 21](http://html1.mh-extra.com/html/rheem/raypak-hi-delta-302c/raypak-hi-delta-302c_installation-and-operation-manual_4133547021.webp)
21
Injector & Heater Pump Comparison
Heater
Model
Heater Pump
Injector Pump
Flow
GPM (lpm)
Temp. Rise
º
F (
º
C)
Press. Drop
Ft. hd. (kPa)
Pump Model/
Imp.
Flow
GPM (lpm)
Temp. Rise
º
F (
º
C)
Pump
Model-HP
302C
32 (121.1)
16 (8.9)
2 (6.0)
112
13 (49.2)
40 (22.2)
1911-1⁄4
402C
34 (128.7)
20 (11.1)
2 (6.0)
112
17 (64.4)
40 (22.2)
1911-1⁄4
502C
42 (159.0)
20 (11.1)
2.3 (6.9)
1630/4.0
22 (83.3)
40 (22.2)
1911-1⁄4
652C
55 (208.2)
20 (11.1)
4.1 (12.3)
1630/4.0
28 (106.0)
40 (22.2)
1911-1⁄4
752C
63 (238.5)
20 (11.1)
5.7 (17.0)
1630/4.2
32 (121.1)
40 (22.2)
1911-1⁄4
902C
76 (287.7)
20 (11.1)
8.4 (25.1)
1630/4.2
38 (143.8)
40 (22.2)
1911-1⁄4
992C
83 (314.2)
20 (11.1)
5.2 (15.5)
1630/4.7
42 (159.0)
40 (22.2)
1911-1⁄4
1262C
107 (405.0)
20 (11.1)
9.6 (28.7)
1630/4.7
54 (204.4)
40 (22.2)
1911-1⁄3
1532C
120 (454.3)
22 (12.2)
12.4 (37.1)
1632/5.6
62 (234.7)
42 (23.3)
1911-1⁄3
1802C
120 (454.3)
25 (13.9)
13 (38.8)
1632/5.6
68 (257.4)
45 (25.0)
1911-1⁄3
2002C
132 (499.7)
26 (14.4)
19 (56.8)
1634/6.1
74 (280.1)
46 (25.6)
1935-3⁄4
2072C
132 (499.7)
27 (15.0)
19 (56.8)
1634/6.1
75 (283.9)
47 (26.1)
1935-3⁄4
2342C
132 (499.7)
30 (16.7)
21.4 (63.9)
1634/6.1
80 (302.8)
50 (27.8)
1935-3⁄4
Table C. Injector and Heater Pump Specifications—Hi Delta
Heater
Model
Heater Pump
Injector Pump
Flow
GPM (lpm)
Temp. Rise
º
F (
º
C)
Press. Drop
Ft. hd. (kPa)
Pump Model/
Imp.
Flow
GPM (lpm)
Temp. Rise
º
F (
º
C)
Pump
Model-HP
503A
58 (219.6)
15 (8.3)
2.4 (7.2)
1611
29 (109.8)
30 (16.7)
1911-1⁄4
753A
63 (238.5)
21 (11.7)
5.6 (16.7)
1611
44 (166.6)
30 (16.7)
1911-1⁄4
1003A
87 (329.3)
20 (11.1)
8.2 (24.5)
1630
58 (219.6)
30 (16.7)
1911-1⁄3
1253A
86 (325.5)
25 (13.9)
12.2 (36.5)
1630
73 (276.3)
30 (16.7)
1911-1⁄3
1503A
100 (378.5)
26 (14.4)
18.5 (55.3)
1632
87 (329.3)
30 (16.7)
1911-1⁄3
1753A
109 (412.6)
28 (15.6)
26 (77.7)
1634
102 (386.1)
30 (16.7)
1911-1⁄3
2003A
116 (439.1)
30 (16.7)
36.2 (108.2)
1636
116 (439.1)
30 (16.7)
1935-3⁄4
Table D. Injector and Heater Pump Specifications—MVB
Summary of Contents for Raypak Hi Delta 302C
Page 14: ...14 Wiring Diagrams Cold Water Start...
Page 29: ...29 Wiring Diagrams Cold Water Run SEE PAGE 17...
Page 31: ...31 7 ILLUSTRATED PARTS LISTS Cold Water Start Manufactured from 2006 through current...
Page 32: ...32 1 M 8 M Cold Water Start...
Page 33: ...33 Cold Water Start Multiple Boiler Interlock...
Page 34: ...34 NOTE Sizing is specific to the application...
Page 37: ...37 NOTE Sizing is specific to the application...
Page 38: ...38 NOTES...
Page 39: ...39 NOTES...