DIAGNOSTICS
Service Analyzer Charts
COMPRESSOR OVERHEATING (cont.)
SYMPTOM
POSSIBLE CAUSE
CHECK OR REMEDIES
Short cycling of
compressor (cont�)
Low charge
Check system charge�
Low evaporator airflow
Dirty coil
Dirty filter
Duct too small or restricted
Faulty run capacitor
Replace�
Faulty internal overload
Replace compressor�
Faulty Compressor
Valves
Fast equalization/Low pressure difference
Replace compressor and examine system to
locate reason�
ELECTRICAL
SYMPTOM
POSSIBLE CAUSE
CHECK OR REMEDIES
Voltage present on
load side of com-
pressor contactor
and compressor
won't run
Compressor start components
Check start capacitor�
Check potential relay�
Run capacitor
Check with ohmmeter
Internal overload
Allow time to reset�
Compressor windings
Check for correct ohms�
Voltage present on
line side of com-
pressor contactor
only
Thermostat
Check for control voltage to contactor coil�
Compressor control circuit
High-pressure switch
Low-pressure switch
Ambient thermostat
Solid-state protection control or internal thermal sensors
Compressor timed off/on control or interlock
No voltage on line
side of compressor
contactor
Blown fuses or tripped circuit breaker
Check for short in wiring or unit�
Improper wiring
Recheck wiring diagram�
Improper voltage
High voltage
Wrong unit
Power supply problem
Low voltage
Wrong unit
Power supply problem
Wiring undersized
Loose connections
Single Phasing (3 phase)
Check incoming power and fusing�
FLOODED STARTS
SYMPTOM
POSSIBLE CAUSE
CHECK OR REMEDIES
Liquid in the com-
pressor shell
Faulty or missing crankcase heater
Replace crankcase heater�
Too much liquid in
system
Incorrect piping
Check piping guidelines�
Overcharge
Check and adjust charge�