AIR FLOW PERFORMANCE - (-)801T SERIES (Downflow) MODELS
MODEL
MOTOR H.P. [W]
BLOWER SIZE
IN [mm]
SPEED
TAP
CFM [L/s] AIR DELIVERY
EXTERNAL STATIC PRESSURE INCHES WATER COLUMN [kPa]
0.1 [.02]
0.2 [.05]
0.3 [.07]
0.5 [.12]
0.6 [.15]
0.8 [.19]
(-)801TA075317ZSA
1/2 [373]
11 x 7
[279 x 178]
Low
Med. Lo
Med
Med. Hi
High
916
993
1205
1367
1475
803
952
1158
1333
1444
669
910
1124
1300
1416
561
827
1056
1236
1354
504
793
1024
1203
1329
421
706
950
1140
1264
(-)801TA075521ZSA
1 [748]
11 x 10
[279 x 254]
Low
Med. Lo
Med
Med. Hi
High
1198
1411
1608
1918
2122
1105
1358
1564
1877
2083
1093
1317
1529
1840
2054
931
1227
1451
1767
1977
901
1196
1416
1706
1945
791
1093
1340
1636
1874
(-)801TA100521ZSA
1 [748]
11 x 10
[279 x 254]
Low
Med. Lo
Med
Med. Hi
High
1240
1405
1600
1903
2072
1120
1364
1561
1877
2028
1073
1317
1526
1833
2006
974
1232
1445
1766
1940
917
1181
1403
1711
1908
799
1083
1325
1631
1840
(-)801TA125524ZSA
1 [748]
11 x 10
[279 x 254]
Low
Med. Lo
Med
Med. Hi
High
1225
1302
1553
1902
2403
1073
1240
1503
1859
2369
988
1191
1455
1822
2332
864
1074
1370
1722
2246
795
1027
1313
1686
2190
697
932
1237
1602
2059
NOTE: Bold data is factory heating tap