background image

Typical Installation

Recommended

heat trap 

6

minimum

Hot water outlet

to fixtures

6

air gap

Suitable open drain

6

Union

Temperature &

pressure relief

valve

Cold water supply

To cold water

supply

Shut-off valve

Relief 
valve
discharge
line to
suitable
open 
drain

Unions

*The drain valve is located below and to the right of jacket access panel and is

not visible in this view.

Anode

Jacket
access
panel

Power supply
cord 2

1

/

2

gal.

models only

Temperature &
pressure relief
valve

Opening
for 1/2

or 3/4

electrical
fitting 

(use only copper
conductors)

Auxiliary catch pan

Relief
valve
discharge
line 

Shut-off valve

Drain valve*

Jacket access
panel

Hot water
outlet 
(to fixtures)

Auxiliary
catch pan

Auxiliary catch
pan drain line

Auxiliary catch pan drain
line

Suitable open drain

7

WARNING: The pressure

rating of the relief valve must
not exceed 150 PSI, the
maximum working pressure of
the water heater as marked on 
the rating plate. 

Relief Valve

The Btuh rating of the relief valve must
not be less than the input rating of the
water heater as indicated on the rating
label located on the front of the heater 
(1 watt=3.412 Btuh).

Connect the outlet of the relief valve to a
suitable open drain so that the discharge
water cannot contact live electrical parts or
persons and to eliminate potential water
damage. 

Piping used should be of a type approved
for hot water distribution. The discharge
line must be no smaller than the outlet of
the valve and must pitch downward from
the valve to allow complete drainage (by
gravity) of the relief valve and discharge
line. The end of the discharge line should
not be threaded or concealed and should
be protected from freezing. No valve of
any type, restriction or reducer coupling
should be installed in the discharge line.

A new combination temperature and pressure relief valve, complying with the Standard for Relief
Valves and Automatic Gas Shut-Off Devices for Hot Water Supply Systems, ANSI Z21.22, is supplied
and must be installed in the opening provided and marked for the purpose on the water heater. No
valve of any type should be installed between the relief valve and the tank. Local codes shall govern the
installation of relief valves.

Drain valve

(not supplied)

To Fill the Water Heater

WARNING: The tank must be full of

water before heater is turned on. The water
heater warranty does not cover damage or
failure resulting from operation with an
empty or partially empty tank.

Make certain the drain valve is completely
closed. 

Open the shut-off valve in the cold water
supply line.

Open each hot water faucet slowly to
allow the air to vent from the water heater
and piping. 

A steady flow of water from the hot water
faucet(s) indicates a full water heater.

Summary of Contents for 120 Volt

Page 1: ...cancer birth defects or other reproductive harm 2 through 30 Gallon Capacity 120 and 240 Volt Models LISTED 786H AP10227 10 11 03 Printed in USA Use Care Manual With Installation Instructions for the...

Page 2: ...ou can find them on a label on the appliance Staple sales slip or cancelled check here Proof of the original purchase date is needed to obtain service under the warranty Your safety and the safety of...

Page 3: ...uctions in how to adjust the thermostat s DANGER Hotter water increases the potential for Hot Water SCALDS D A N G E R HOT Water temperature over 125 F can cause severe burns instantly or death from s...

Page 4: ...with generic earthquake bracing instructions can be obtained from Office of the State Architect 400 P Street Sacramento CA 95814 or you may call 916 324 5315 or ask a water heater dealer However appl...

Page 5: ...such a manner that the thermostat and element access panels can be removed to permit inspection and servicing such as removal of elements or checking controls The water heater and water lines should...

Page 6: ...he suggested method of controlling thermal expansion is to install an expansion tank in the cold water line between the water heater and the check valve The expansion tank is designed with an air cush...

Page 7: ...s or persons and to eliminate potential water damage Piping used should be of a type approved for hot water distribution The discharge line must be no smaller than the outlet of the valve and must pit...

Page 8: ...l for wiring connections The branch circuit wiring should include either Metallic conduit or metallic sheathed cable approved for use as a grounding conductor and installed with fittings approved for...

Page 9: ...vices other than those authorized by the manufacturer into onto or in conjunction with the water heater The use of unauthorized energy saving devices may shorten the life of the water heater and may e...

Page 10: ...ection arrangement Typical side connection arrangement Relief Valve Insulation Installation CAUTION Ensure the T P Valve opening is not obstructed by the insulation Heat Trap For increased energy effi...

Page 11: ...nt room to service heater Water heater completely filled with water Air purged from water heater and piping Water connections tight and free of leaks Temperature and Pressure Relief Valve properly ins...

Page 12: ...Do not smoke or use an open flame near the faucet at the time it is open CAUTION The cause of the high temperature condition must be investigated by qualified service technician and corrective action...

Page 13: ...ure Setting The temperature of the water in the water heater can be regulated by setting the temperature dial of the adjustable surface mounted thermostat s located behind the jacket access panel s Du...

Page 14: ...nd or replacement as operation with the anode rod removed will shorten the life of the glass lined tank and will exclude warranty coverage Care and cleaning of the water heater Draining the Water Heat...

Page 15: ...y may be off Make sure electric supply to water heater and disconnect switch if used are in the ON position The thermostat may See the Temperature regulation of the water heater be set set too low sec...

Page 16: ...below and number of parts desired CAUTION For your safety DO NOT attempt repair of electrical wiring thermostat s heating elements or other operating controls Refer repairs to qualified service person...

Page 17: ...ed below and number of parts desired CAUTION For your safety DO NOT attempt repair of electrical wiring thermostat s heating elements or other operating controls Refer repairs to qualified service per...

Page 18: ...ER BEFO RE SERV ICING R E SE T R E S E T 140 130 120 110 100 90 T H E R M O D I S C TURN OFF POW ER BEFO RE SERV ICING 140 130 120 110 100 90 T H E R M O D I S C R E SE T R E S E T 140 130 120 110 10...

Page 19: ...he Manufacturer s National Service Department at the following address 2600 Gunter Park Drive Montgomery Alabama 36109 1413 Phone 1 800 432 8373 When contacting the manufacturer the following informat...

Page 20: ...T TO ELECTRICAL DISTRIBUTION PANEL JUNCTION BOX N 120 V Plug Connected Cord Set ONLY SINGLE ELEMENT FIG B BRANCH CIRCUIT TO ELECTRICAL DISTRIBUTION PANEL UPPER THERMOSTAT HIGH TEMP LIMIT ECO 2 UPPER H...

Reviews: