background image

6

Frequent washing of the cabinet, fan blade and coil with fresh water will remove
most of the salt or other contaminants that build up on the unit.

Regular cleaning and waxing of the cabinet with an automobile polish will pro-
vide some protection.

A liquid cleaner may be used several times a year to remove matter that will not
wash off with water.

Several different types of protective coatings are offered in some areas. These
coatings may provide some benefit, but the effectiveness of such coating materials
cannot be verified by the equipment manufacturer.

LOCATING UNIT

CONDENSER LOCATION

Consult local and national building codes and ordinances for special installation
requirements. Following location information will provide longer life and simplified
servicing of the outdoor condenser.

NOTE:

These units must be installed outdoors. No ductwork can be attached, or

other modifications made, to the discharge grille. Modifications will affect perform-
ance or operation.

OPERATIONAL ISSUES

IMPORTANT:

Locate the condenser in a manner that will not prevent, impair or

compromise the performance of other equipment horizontally installed in prox-
imity to the unit. Maintain all required minimum distances to gas and electric
meters, dryer vents, exhaust and inlet openings. In the absence of National
Codes, or manaufacturers’ recommendations, local code recommendations and
requirements will take presidence.

Refrigerant piping and wiring should be properly sized and kept as short as pos-
sible to avoid capacity losses and increased operating costs.

Locate the condenser where water run off will not create a problem with the
equipment. Position the unit away from the drip edge of the roof whenever pos-
sible. Units are weatherized, but can be affected by the following:

o Water pouring into the unit from the junction of rooflines, without protective

guttering. Large volumes of water entering the condenser while in operation
can impact fan blade or motor life, and coil damage may occur to a heat
pump if moisture cannot drain from the unit under freezing conditions.

Closely follow clearance recommendations on Page 3.

o 24” to the service panel access

o 60” above condenser fan discharge (unit top) to prevent recirculation

o 6” to condenser coil grille air inlets (per condenser).

FOR CONDENSERS WITH SPACE LIMITATIONS

In the event that a space limitation exists, we will permit the following clearances:

Single Unit Applications:

Clearances below 6 inches will reduce unit capacity and

efficiency. Do not reduce the 60-inch discharge, or the 24-inch service clearances.

Multiple Unit Applications:

When multiple condenser grille sides are aligned, a 6-

inch per unit clearance is recommended, for a total of 12" between two units. Two
combined clearances below 12 inches will reduce capacity and efficiency. Do not
reduce the 60-inch discharge, or 24-inch service, clearances.

Do not obstruct the bottom drain opening in the condenser base pan. It is
essential to provide defrost condensate drainage to prevent possible refreezing
of the condensation. Provide a base pad for mounting the unit, which is slightly
pitched away from the structure. Route condensate off the base pad to an area
which will not become slippery and result in personal injury.

!

WARNING

DISCONNECT

ALL

POWER

TO

UNIT

BEFORE

STARTING

MAINTENANCE. FAILURE TO DO SO CAN CAUSE ELECTRICAL SHOCK
RESULTING IN SEVERE PERSONAL INJURY OR DEATH.

Summary of Contents for 018J*Z

Page 1: ...T SAFETY INFORMA THESE INSTRUCTIONS ARE INTENDED AS AN AID TO QUALIFIED LICENSED SERVICE PERSONNEL FOR PROPER INSTALLATION ADJUSTMENT AND OPERATION OF THIS UNIT READ THESE INSTRUCTIONS THOROUGHLY BEFORE ATTEMPTING INSTALLATION OR OPERATION FAILURE TO FOLLOW THESE INSTRUCTIONS MAY RESULT IN IMPROPER INSTALLATION ADJUSTMENT SERVICE OR MAINTENANCE POSSIBLY RESULTING IN FIRE ELECTRICAL SHOCK PROPERTY ...

Page 2: ...ormance 14 Checking Airflow 14 Checking Refrigerant Charge 15 Electrical Wiring 16 High and Low Pressure Controls HPC or LPC 18 Field Installed Accessories 18 Service 19 Trouble Shooting 20 22 Trouble Shooting Chart 23 Wiring Diagrams 24 26 CHECKING PRODUCT RECEIVED Upon receiving unit inspect it for any shipping damage Claims for damage either apparent or concealed should be filed immediately wit...

Page 3: ... 043 42 000 BTU HR 048 049 48 000 BTU HR 060 60 000 BTU HR DESIGN SERIES L R 410A M R410 2ND DESIGN SERIES N STANDARD EFFICIENCY P HIGH EFFICIENCY REMOTE CONDENSING UNIT TRADE NAME DIMENSIONAL DATA CONDENSING UNIT MODEL ANL 018 19 19 19 25 29 23 33 351 2 401 2 443 8 443 8 443 8 443 8 443 8 243 4 275 8 311 2 311 2 311 2 311 2 311 2 LENGTH H INCHES LENGTH L INCHES WIDTH W INCHES 024 031 030 036 042 ...

Page 4: ...83 1 1 2 19 19 25 25 30 30 17 26 1 6 1 3200 1510 115 3260 205 93 215 97 043DAZ 3 60 460 6 0 44 0 6 9 15 15 17 26 1 6 1 3200 1510 115 3260 205 93 215 97 043JAZ 1 60 208 230 19 9 19 9 109 1 2 27 27 35 35 45 45 17 26 1 6 1 3200 1510 115 3260 205 93 215 97 048CAZ 3 60 208 230 13 7 13 7 83 1 1 2 19 19 25 25 30 30 23 01 2 14 1 3500 1652 145 4111 230 104 3 240 108 9 048DAZ 3 60 460 6 2 41 0 6 9 15 15 23 ...

Page 5: ... side of the building away from the water front Shielding provided by a fence or shrubs may give some protection but cannot violate minimum airflow and service access clearances Elevating the unit off its slab or base enough to allow air circulation will help avoid holding water against the basepan Regular maintenance will reduce the build up of contaminants and help to protect the unit s finish 5...

Page 6: ...l not create a problem with the equipment Position the unit away from the drip edge of the roof whenever pos sible Units are weatherized but can be affected by the following o Water pouring into the unit from the junction of rooflines without protective guttering Large volumes of water entering the condenser while in operation can impact fan blade or motor life and coil damage may occur to a heat ...

Page 7: ...he concrete fastener STEP 2 Center base pan on pad ensuring it is level STEP 3 Using basepad as a guide mark spots on concrete where 4 holes will be drilled see Figure 2 S TABLE 4 DIMENSIONS MODEL NUMBER L W A B C D ANL 018 024 030 APL 018 024 ANL 031 APM 018 375 8 2515 16 15 34 31 2 221 2 ANL 037 043 049 ANL 036 042 048 060 APL 030 036 042 048 060 APM 024 030 036 042 048 060 411 2 2913 16 15 38 3...

Page 8: ...ow Side 550 PSIG Low Side Retard Manifold Hoses Service Pressure Rating of 800 PSIG Recovery Cylinders 400 PSIG Pressure Rating Dept of Transportation 4BA400 or BW400 SPECIFICATION OF R 410A Application R 410A is not a drop in replacement for R 22 equipment designs must accommodate its higher pressures It cannot be retrofitted into R 22 condens ing units FIGURE 2 SCREW LOCATIONS CAUTION R 410A sys...

Page 9: ...9 R 410A refrigerant cylinders had a dip tube These cylinders should be kept upright for equipment charging Post March 1999 cylinders do not have a dip tube and should be inverted to ensure liquid charging of the equipment Do not install a suction line filter drier in the liquid line A liquid line filter drier is standard on every unit Only manufacturer approved liq uid line filter driers can be u...

Page 10: ...w check piston sizes if the vertical separation does not exceed the values in Table 4 3 Flow Check Piston Coil a The vertical separation can be greater than the value in Table 4 but no more than 120 feet b If the separation height exceeds the Table value reduce the indoor coil flow check piston by two sizes plus one size for additional 10 feet beyond the Table value 4 Expansion Valve Coil a The ve...

Page 11: ... with each other This causes an undesirable heat transfer resulting in capacity loss and increased power consumption The vapor line must be insulated If tubing has been cut make sure ends are deburred while holding in a position to prevent chips from falling into tubing Burrs such as those caused by tubing cutters can affect performance dramatically particularly on small liquid line sizes For best...

Page 12: ...itrogen into a service port and through the tubing while brazing After brazing use an appropriate heatsink material to cool the joint and remove any flux residue The service valves are not backseating valves To open the valves remove the valve cap with an adjustable wrench Insert a 3 16 or 5 16 hex wrench into the stem Back out counterclockwise Replace the valve cap finger tight then tighten an ad...

Page 13: ...ine Size Inch O D Total Minimum Vertical Separation Feet 25 50 75 100 125 150 1 4 25 40 25 9 N A N A 11 2 Ton 3 8ⴖ 5 16 25 50 62 58 53 49 3 8 25 50 75 72 70 68 1 4 23 N A N A N A N A N A 2 Ton 3 8ⴖ 5 16 25 36 29 23 16 9 3 8 25 50 72 70 68 65 1 4 25 N A N A N A N A N A 21 2 Ton 3 8ⴖ 5 16 25 49 38 27 17 6 3 8 25 50 68 65 62 58 5 16 25 50 37 22 7 N A 3 Ton 3 8ⴖ 3 8 25 50 68 63 58 53 5 16 25 23 4 N A ...

Page 14: ...ted if required Allow a minimum of 5 minutes running Before analyzing charge see the instruc tions on the unit service panel rating plate for marking the total charge CHECKING AIRFLOW The air distribution system has the greatest effect The duct system is totally con trolled by the contractor For this reason the contractor should use only industry recognized procedures The correct air quantity is c...

Page 15: ... systems in the cooling mode when an expansion valve is used on the evaporator The service port on the liquid service valve small valve is used for this purpose Read and record the outdoor ambient temperature entering the condensing unit and the liquid line pressure at the service valve the small valve Locate the charg ing chart attached to the unit The correct liquid line pressure will by found b...

Page 16: ...g within the condensing unit evaporator and interconnecting tubing should be checked for leaks If a leak is detected the refrigerant should be recovered before repairing the leak The Clean Air Act prohibits venting refrigerant into the atmosphere ELECTRICAL WIRING Field wiring must comply with the National Electric Code C E C in Canada and any applicable local code POWER WIRING It is important tha...

Page 17: ...inimum transformer are required for the control circuit of the condensing unit The furnace or the air handler transformer may be used if sufficient See the wiring diagram for reference Use Table 8 to size the 24 volt con trol wiring WARNING THE UNIT MUST BE PERMANENTLY GROUNDED FAILURE TO DO SO CAN CAUSE ELECTRICAL SHOCK RESULTING IN SEVERE PERSONAL INJURY OR DEATH SOLID COPPER WIRE AWG 3 0 16 14 ...

Page 18: ...m operation below 55 F All heaters are located on the lower half of the compressor shell Its purpose is to drive refrigerant from the compressor shell during long off cycles thus preventing damage to the compressor during start up At initial start up or after extended shutdown periods make sure the heater is ener gized for at least 12 hours before the compressor is started Disconnect switch on and...

Page 19: ...ops below designated levels This allows the unit to build a sufficient head pressure at lower ambient in order to maintain system balance and obtain improved capacity Low ambient control should be used on all equipment oper ated below 65 F ambient OUTDOOR UNIT COVERS Outdoor condensing unit covers are available if the homeowner requests a cover for their unit With the complete model number for the...

Page 20: ...eakers and Recheck Unit Wiring and Connections Condenser Fan Grounded Compressor Internal Overload Open TROUBLE SHOOTING In diagnosing common faults in the air conditioning system it is useful to present the logical pattern of thought that is used by experienced technicians The charts which follow are not intended to be an answer to all problems but only to guide your thinking as you attempt to de...

Page 21: ...problems Low on Charge Dirty Filters Dirty Condenser Coil Recirculation of Condenser Air Inoperative Compressor Valves Low on Charge Faulty Metering Device Restriction in System Restricted Filter drier Non condensibles Higher than Ambient Air Entering Condenser Go to Electrical Checks Flow Chart High Head Pressure Inoperative Outdoor Fan Broken Indoor Blower Belt Restriction in System Recirculatio...

Page 22: ... 2 0 48 4 5 55 1 10 62 4 15 70 2 20 78 5 25 87 5 30 97 2 35 107 5 40 118 5 45 130 2 50 142 7 55 156 0 60 170 1 65 185 1 70 201 0 75 217 8 80 235 6 85 254 5 90 274 3 95 295 3 100 317 4 105 340 6 110 365 1 115 390 9 120 418 0 125 446 5 130 476 5 135 508 0 140 541 2 145 576 0 150 612 8 DISCHARGE SUCTION SUPERHEAT SUBCOOLING COMPRESSOR PRESSURE PRESSURE AMPS Overcharge High High Low High High Undercha...

Page 23: ... Add refrigerant Registers sweat Low indoor airflow Increase speed of blower or reduce restriction replace air filter High head low vapor pressures Restriction in liquid line expansion device or filter drier Remove or replace defective component Flowcheck piston size too small Change to correct size piston Incorrect capillary tubes Change coil assembly High head high or normal vapor Dirty outdoor ...

Page 24: ...24 FIGURE 4 SINGLE PHASE WIRING DIAGRAM ...

Page 25: ...25 FIGURE 5 THREE PHASE WIRING DIAGRAM C D Y VOLTAGES ...

Page 26: ...26 FIGURE 6 ...

Page 27: ...27 ...

Page 28: ...28 CM 0908 ...

Reviews: