22
AIR CONDITIONING SYSTEM TROUBLESHOOTING TIPS
AIR CONDITIONING SYSTEM
TROUBLESHOOTING TIPS
SUPERHEAT CALCULATION
1. Measure the suction pressure at the suction line service valve.
3. Measure the temperature of the suction line at the suction line service valve.
4. Compare the temperature of the suction line to the saturated temperature.
5. The difference between saturated temperature and suctin line temperature is the
superheat. Superheat normal range 12° to 15°.
SUBCOOLING CALCULATION
1. Measure the liquid pressure at the liquid line service valve.
3. Measure the liquid line temperature at the liquid line service valve.
4. Compare the liquid line temperature to the saturated temperature.
5. The difference between saturated temperature and liquid line temperature is the
subcooling. Subcooling normal range 9° to 12°.
TEMPERATURE PRESSURE CHART
TEMP
R-410A
(Deg. F)
PSIG
-150
—
-140
—
-130
—
-120
—
-110
—
-100
—
-90
—
-80
—
-70
—
-60
0.4
-50
5.1
-40
10.9
-35
14.2
-30
17.9
-25
22.0
-20
26.4
-15
31.3
-10
36.5
-5
42.2
0
48.4
5
55.1
10
62.4
15
70.2
20
78.5
25
87.5
30
97.2
35
107.5
40
118.5
45
130.2
50
142.7
55
156.0
60
170.1
65
185.1
70
201.0
75
217.8
80
235.6
85
254.5
90
274.3
95
295.3
100
317.4
105
340.6
110
365.1
115
390.9
120
418.0
125
446.5
130
476.5
135
508.0
140
541.2
145
576.0
150
612.8
DISCHARGE
SUCTION
SUPERHEAT SUBCOOLING
COMPRESSOR
PRESSURE
PRESSURE
AMPS
Overcharge
High
High
Low
High
High
Undercharge
Low
Low
High
Low
Low
Liquid Restriction (Drier)
Low
Low
High
High
Low
Low Evaporator Airflow
Low
Low
Low
Low
Low
Dirty Condenser
High
High
Low
Low
High
Low Outside Ambient Temperature
Low
Low
High
High
Low
Inefficient Compressor
Low
High
High
High
Low
Low
Low
High
High
Low
Poorly Insulated Sensing Bulb
High
High
Low
Low
High
SYSTEM PROBLEM
INDICATORS
TABLE 9
TABLE 10
2. Convert the suction pressure to saturated temperature. See Table 9.
2. Convert the liquid line pressure to saturated temperature. See Table 10.
TEV Feeler Bulb Charge Lost
Convert the suction pressure to saturated temperature. See Table 12.
Convert the liquid line pressure to saturated temperture. See Table 13.
TABLE 12
TEMPERATURE PRESSURE CHART
TABLE 13
AIR CONDITIONING SYSTEM TROUBLESHOOTING TIPS