background image

17

Operation and mechanisms

 BFN(T) Remotely controlled spring return actuator

The spring return actuator BFN(T) is specially designed to remotely control fire dampers. The BFN(T) model is intended for fire 
dampers with large dimensions (ø > 400 mm (CR2) or W+H > 1200 mm (CU2, CA2, CU2-15, CU4)) or for dampers CU-LT(-1s), CR60, 
CR120 with a production date before 1 July 2015.

1.  locking button
2.  plug (ST)
3.  access for manual resetting
4.  thermo-electric tripping device (T)

1

3

4

2

Options - at the time of order

SN2 BFL/BFN

Auxiliary limit switch ‘open/closed’

IXI-R1

Universal field module (Modbus, BACnet or analog connection), pre-mounted on the damper.

IXI-R2-24

Universal field controller (Modbus, BACnet), pre-mounted on the damper and with a connection for a second damper.

IXI-R2-230

Universal field controller (Modbus, BACnet), pre-mounted on the damper and with a connection for a second damper.

Unlocking

 

manual unlocking

: place the locking button on “unlock”. (In case of BFNT: the damper can alternatively be unlocked by pushing 

the “test” button on the thermo-electric fuse)

 

automatic unlocking

: the thermo-electric fuse reacts as soon as the temperature reaches 72°C (type BFNT).

 

remote unlocking

: by interrupting the power supply.

Caution: 

 

†

The thermo-electric fuse will not move the damper into its safety position (when the temperature reaches 72°C) if the motor 

is not powered.

Resetting

 

manual resetting

: turn the enclosed handle anti-clockwise. To block the motor, place the locking button on “lock”

 

motorised resetting

: switch off the power supply for at least 10 seconds. Supply the actuator (respect the prescribed voltage) for 

at least 75 seconds. The resetting stops automatically when the end of range is reached (damper open) - it takes about 60 seconds 
to reset the damper - or when the power supply is interrupted.

Caution: 

 

†

Do not use a drill or powered screwdriver.

 

†

Stop as soon as the motor is completely rearmed (end of range).

Caution: 

 

†

The mechanism may never be tested on its own, without being attached to the damper. Such a test might damage the 

mechanism or the operator might be injured.

 

prod. < 1/7/2015

 

prod. ≥ 1/7/2015 

 

CR60(1s) 

CR120 

CU-LT 

CU-LT-1s 

CR2≤400 

CU2≤1200 

CR2>400 

CU2>1200 

CR60(1s) 

CR120 (1s)

CU-LT 

CU-LT-1s 

CR2≤400 

CU2≤1200 

CR2>400 

CU2>1200 

Kit BFL 

 

 

 

 

 

 

 

 

Kit BFN 

 

 

 

 

 

 

 

 

Kit BF 

 

 

 

 

 

 

 

 

Summary of Contents for ONE-X CU2/B

Page 1: ...ww rft be en Rf Technologies nv Lange Ambachtstraat 40 9860 Oosterzele Belgium Tel 32 9 362 31 71 Fax 32 9 362 33 07 info rft be 0749 C31 EN H 03 2021 CU2 B Battery assembly of max 4 individual damper...

Page 2: ...i meets the criteria from the outside o to the inside i i o fire side not important V AC Volt alternating current V DC Volt direct current E TELE power supply magnet E ALIM power supply motor V volt W...

Page 3: ...ssification CU2 B 4 x CU2 200x200 mm CU2 1200x800 mm Rigid wall Reinforced concrete 110 mm Mortar 1 EI 120 v e i n o S 500 Pa CU2 B 4 x CU2 200x200 mm CU2 1500x800 mm Rigid wall Reinforced concrete 11...

Page 4: ...s linked to the project or to the local regulations 5 large dimensions 5 battery assembly tested in rigid wall tested according to EN 1366 2 up to 500 Pa suitable for installation in rigid wall mainte...

Page 5: ...ons are subject to extra cost heights between 275 and 299 mm are not possible Exceeding blade X on the mechanism side Y on the wall side Y X 45 240 500 Wn 6 x Hn 6 Wn 24 x Hn 24 Hn mm 500 550 600 650...

Page 6: ...n actuator ONE 230V with fusible link T unipolar beginning and end of range switch KITS ONE T 230 FDCB Spring return actuator ONE 230V with fusible link T bipolar beginning and end of range switch KIT...

Page 7: ...BFLT24 ST Spring return actuator BFL 24V with thermo electric fuse T and plug ST KITS BFN24 Spring return actuator BFN 24V KITS BFN24 Spring return actuator BFN 24V BFN kits must be used instead of B...

Page 8: ...ric fuse T KITS BFNT230 CRE Spring return actuator BFN 230V with thermo electric fuse T KITS BFNT24 ST CRE Spring return actuator BFN 24V with thermo electric fuse T and plug ST KITS BF24 Spring retur...

Page 9: ...r beginning and end of range switches KITS EQ Kit equipotential connection per set of 5 pieces Options at the time of order EQ Equipotential connection ONE X CN Connectors for the bus cables and the p...

Page 10: ...s The operating mechanism must also remain accessible allow for a clearance of 200 mm around the housing The air tightness class will be maintained if the damper is installed according to the installa...

Page 11: ...on the edges of the individual dampers flanges as illustrated i e the sides that connect with other individual dampers Bn 100 Hn 100 2 Provide in the wall an installation opening of minimum Xn 100 mm...

Page 12: ...Seal the openings with adhesive BCM Run a test on the mechanisms of the fire dampers TEST 8 Check the functioning of the damper blades Maintenance No specific maintenance required Schedule at least 2...

Page 13: ...s at the time of order FCU Limit switch closed FDCU Unipolar limit switch open closed FDCB Bipolar auxiliary limit switch open closed Unlocking manual unlocking use the unlocking button 1 automatic un...

Page 14: ...e battery the LED fades away Close the battery compartment motorised resetting switch off the power supply for at least 5 sec Power the actuator respect the prescribed voltage for at least 75 sec The...

Page 15: ...f the ONE X detects voltage on the power cable a brief contact of the battery is enough to start the resetting process provided the ZENiX controller has sent the damper to open position or the ONE X i...

Page 16: ...ively be unlocked by pushing the test button on the thermo electric fuse automatic unlocking the thermo electric fuse reacts as soon as the temperature reaches 72 C type BFLT remote unlocking by inter...

Page 17: ...n the thermo electric fuse automatic unlocking the thermo electric fuse reacts as soon as the temperature reaches 72 C type BFNT remote unlocking by interrupting the power supply Caution The thermo el...

Page 18: ...C 10 20 N A 0 28W 4 2W 1mA 1A 60V ONE T 230 FDCU 230 V AC 15 15 N A 0 57W 4 2W 1mA 1A 60V ONE T 24 FDCU ST 24 V AC DC 10 20 N A 0 28W 4 2W 1mA 1A 60V ONE T 24 FDCB 24 V AC DC 10 20 N A 0 28W 4 2W 1mA...

Page 19: ...cabled 85 s battery 30 s 64 dB A 67 dB A IP 54 ONE X 230 75 s cabled 85 s battery 30 s 64 dB A 67 dB A IP 54 BFL24 60 s 20 s 43 dB A 62 dB A 1 m 2 x 0 34 mm halogen free 1 m 6 x 0 75 mm halogen free I...

Page 20: ...3 33 5 34 6 35 7 36 8 37 9 39 1 40 2 300 kg 13 6 14 8 16 0 17 2 18 4 19 5 20 7 21 9 23 1 24 3 25 5 26 7 27 9 29 1 30 2 29 8 31 0 32 2 33 4 34 6 35 8 37 0 38 1 39 3 40 5 41 7 42 9 350 kg 14 6 15 9 17 1...

Page 21: ...9 51 4 52 9 54 4 55 9 600 kg 31 8 33 4 35 0 36 5 38 1 39 7 41 3 42 9 44 4 46 0 47 6 49 2 50 8 52 3 53 9 55 5 57 1 58 7 650 kg 31 8 33 4 35 0 36 7 38 3 40 0 41 6 43 3 44 9 46 6 48 2 49 8 51 5 53 1 54 8...

Page 22: ...36 3 37 5 38 8 40 0 41 2 42 4 43 7 300 kg 14 6 15 9 17 2 18 5 19 8 21 1 22 4 23 7 25 0 26 3 27 6 28 9 30 2 31 5 32 8 32 3 33 6 34 9 36 2 37 5 38 8 40 1 41 4 42 7 44 0 45 3 46 6 350 kg 15 7 17 1 18 5 1...

Page 23: ...56 0 57 6 59 3 60 9 600 kg 34 5 36 3 38 0 39 7 41 5 43 2 44 9 46 6 48 3 50 1 51 8 53 5 55 3 57 0 58 7 60 4 62 2 63 9 650 kg 34 5 36 3 38 1 39 9 41 7 43 5 45 3 47 1 48 9 50 7 52 5 54 3 56 0 57 9 59 6 6...

Page 24: ...e NF label guarantees conformity with the standard NF S 61 937 Parts 1 and 5 Syst mes de S curit Incendie Dispositifs Actionn s de S curit conformity with the national decree of March 22 2004 changed...

Reviews: