UV/IR Type Flame Detector
RFD-2000X
Document No. Manual-2000X Rev.3
March 2013
- 26 -
- Setting of Self Checking Function
After the appropriate installation, the detector performs self diagnostic test by itself from
the internal sensor to circuit repeatedly.
SW1
Switch Setting
Function
No.8
0
Self testing function "OFF"
1
Self testing function "ON"
- Period of self testing : Every 12 hours
[Table 20] Switch setting for self-diagnosis test
3.3.5 Ground Connection
For proper operation of the detector, the RFD-2000X must be grounded through a wire to
the chassis.
Failure to establish a ground connection can lead to greater susceptibility of the
detector to electric surges, electromagnetic interference, and ultimately, damage to the
instrument.
3.3.5.1 Grounding Method
Grounding can be connected to case outside or inside.