RFD-2000X
Document No. Manual-2000X Rev.3
March 2013
- 24 -
3.3.4 Setting of Product
3.3.4.1 Sensitivity setting
Sensitivity setting can be adjusted by user according to the various environmental
conditions. Due to the difference in law or regulation from various countries, this function
may not be applicable to all. So we have no responsibility for the troubles related with
sensitivity setting over the approved range.
- Setting method of sensitivity
Do not set the switch, while power is applied. The switch adjustment with power
connection will not be recognized by the detector.
SW1
Switch setting
Sensitivity
Range of Sensitivity
ft(m)
No.3
No.1
No.2
0
0
0
-
99(30)
0
1
0
-
66(20)
0
0
1
-
33(10)
0
1
1
-
17(5)
- Reference Source of fire standard is 1ft
2
of N-Heptane
[Table 17] Sensitivity range of N-Heptane
3.3.4.2 Setting of Delay Time
The flame detectors are equipped with Alarm delay option, which provides programmable
time delays by settings. The Alarm signal will be activated if the fire still exists after
programmed delay time. But the fire disappears within programmed delay time, the
detector will return to its standby state again.
The Alarm delay option affects the output relays and the 0-20mA. The LEDs and outputs
indicate warning levels during the delay time only if the fire condition exists.