0108RPVDGBEN
2
INDEX
Page
1. General.....................................................................................................................................................2
2. Technical data...........................................................................................................................................3
3. Installing...................................................................................................................................................6
4. Gas connection..........................................................................................................................................9
5. Electrical connection ................................................................................................................................10
6. Commissioning, lighting and operation........................................................................................................10
7. Maintenance ...........................................................................................................................................12
8. Fault finding............................................................................................................................................16
9. Spare parts list ........................................................................................................................................17
10. Gas conversion ......................................................................................................................................18
11. Health and Safety Statement...................................................................................................................19
12. User instructions....................................................................................................................................20
If optional equipment was ordered and supplied with this air heater, please refer to additional instructions for option(s).
SECTION 1. GENERAL
1.1
Before installation, check that the appliance as
described on the packaging label is in accordance
with the correct type and model as specified on
the data plate and complies with your customer
order.
1.2
Please read this document before commencing
installation.
1.3
These instructions are only valid for the country of
use indicated on the appliance i.e.: GB - IE. If these
symbols are not shown, it is necessary to obtain
appropriate technical instructions which will
provide information concerning the necessary
modification of the appliance for the conditions of
use in the country concerned. Such instructions
may be obtained upon request from your supplier.
1.4
Check that the local distribution conditions of
electricity supply, type of gas and pressure, and
adjustment of the appliance are compatible.
1.5
When installed in Great Britain the total installation
must comply with the requirements and
recommendations of British Standard BS 6230
1991. "Installation of Gas Fired Forced Convection
Air Heaters for Commercial and Industrial Space
Heating".
The Installation must also be in accordance with
the relevant requirements of "The Gas Safety
(Installation and Use regulations) and (Amendment
Regulations 1990)" and The "Building" and
"Electrical Regulations" (in GB the IEE Regulations).
The requirements of the "Local Building Standards
Office", the premises "Insurance" undertaking and
the"Fire Office" must also be observed.
1.6
Unauthorized modification of this appliance or
departure from use in the manner for which it was
intended by the manufacturer or installation in a
manner contrary to these instructions, may
constitute a hazard and jeopardize all warranties.
Deviations should only be carried out after formal
consent has been obtained from the manufacturer.
1.7
Ensure the environment in which the air heater will
be installed will not create a hazard i.e. where
excessive (volatile) dust, flammable or corrosive
substances and/or vapours and combustible
materials may be present.
1.8
This appliance has been tested, and set according
to the data plate before leaving the factory.
1.9
These air heaters may be used as a gas fired
heating module in an air handling appliance or in
conjunction with a cooling packaged appliance.
When applied in such manner the installation
instructions contained in this document must be
complied with as appropriate. The fitting within
another housing must take into account the gas
fired appliance requirements of the appropriate CE
standard, EN 1020 " Non-domestic gas-fired forced
convection air heaters for space heating
incorporating a fan to assist transportation of
combustion air and/or flue gases "PrEN 1020 is in
course of preparation and may be applied until the
final document is published, (anticipated 1996). It
is the responsibility of the installer to ensure that
the total installation complies with the
requirements of the following EC directives:
Dir CE 89/336/EEC Electro-magnetic compatibility;
Dir CE 73/23/EEC Low voltage directive;
Dir CE 89/392/EEC Machinery
1.10 The criteria recommended in this document
regarding air flow pressures, temperature rise,
firing rates and fitting methods must be strictly
complied with, wether or not the appliance is used
as a duct heater or as part of a multi-functional
appliance. This is to ensure satisfactory operation
of the gas heater.