0108RPVDGBEN
3
SECTION 2. TECHNICAL DATA
Table 1. Appliance Data Standard Efficiency Models
RPV 2000 Standard Model #
2025
2030
2035
2045
2055
2075
2095
RPV 2000 Low NO
x
#
2525
2530
2535
2545
2555
2575
2595
Gas category 'Cat.'
II
2H3
Air supply and flue type
FLUELESS OUTDOOR AIR HEATER
Heat input (Hs) 'Qn'
kW
28,8
35,2
42,7
49,9
63,2
86,5
115,4
Heat input (Hi) 'Qn'
kW
26,0
31,7
38,5
45,0
57,0
78,0
104,0
High heat output
kW
22,8
27,8
33,7
39,4
49,9
68,3
91,0
Number of jets
4
5
7
9
12
16
natural gas
∅
mm
2.4
2.2
2.4
Jet size
propane/butane
∅
mm
1.35
1.25
1.35
natural gas
mbar
(GB) =
17.5
(IE) =
20.0
propane
mbar
37.0
Gas supply
pressure 'P'
1
butane
mbar
28.0
Burner pressure
2
natural gas
mbar
8.50
natural gas
3
m
3
/h
2.74
3.36
4.04
4.76
6.02
8.30
11.00
propane
kg/h
2.06
2.52
3.05
3.56
4.51
6.18
8.25
Gas consumption
butane
kg/h
2.10
2.60
3.12
3.64
4.61
6.31
8.42
Gas service connection (not supply line size)
Rc ¾
Electrical supply
230/240V 1 N ~ 50Hz
Electrical rating
4
180 W
Protection grade
IP20
Appliance weight net
kg
80
85
99
115
139
171
Appliance weight gross (shipping)
± kg
88
96
109
126
152
187
1
Maximum gas pressure at inlet to appliance = 50,0 mbar
2
All casing panels fitted, service door open
3
Natural gas G20, calorific heating value 10,48 kWh/m
3
on Hs @ 15
°
C & 1013 mbar
Propane G31, calorific heating value 14,00 kWh/kg
Butane G30, calorific heating value 13,70 kWh/kg
4
Total electrical rating during the start-up period ± 30 seconds is increased by 130 W and is not included on the
appliance data plate or in the above table
Table 2
Appliance Data
Higher Efficiency Models
RPV 2000 Standard Model #
2026
2031
2036
2046
2056
2076
2096
RPV 2000Low NO
x
Model #
2526
2531
2536
2546
2556
2576
2596
High fire heat output
kW
23.7
28.8
35.0
41.0
51.9
71.0
94.6
Note: All other data as standard model