6.0 GAS
CONNECTION
Rc ¾
or
Rc 1 ¼
for
M units
6.1.1
National requirements and regulations for the
installation of gas must be respected for all
countries into which the appliance is delivered.
Gas connections may only be carried out by
appropriately qualified persons.
6.1.2 Clearances around connections shall be
adequate so as to afford access to allow the use
of tools to connect and disconnect the gas service
connections.
6.1.3
Threads used for gas pipes and fittings shall
comply with ISO 7.1.
6.1.4
Copper pipes and fittings may not be used. Solder
which has a melting point of less than 450
o
C
neither solder or alloys containing cadmium shall
not be used.
6.1.5
All gas services to the heating module shall be
equipped with an isolation tap which shall be of
the 90
o
turn type and shall be provided with a
positive stop and it should be fitted adjacent to the
heating module. Such taps when installed in a
vertical position shall be such that in the event of
a falling handle the valve will be in the closed
condition, the open and closed positing shall be
readily distinguishable. The valve shall be easy to
operate when required.
Attention :
All passages for gas pipes, etc … to the control
department must be completely sealed !
7.0 ELECTRICAL
EQUIPMENT
WARNING
:
Ensure that when installing electrical
wiring or cables no contact is made with the burner,
heat exchanger or flue arrangement.
Cables or wires must be securely fixed so that they
cannot move. To protect supply cables as good as
possible we recommend to install them at the left
side of the control compartment.
7.1.1
The RHC 4000(M) heating module has been fully
tested prior to leaving the manufacturer. The
constructor shall not make changes to the wiring
supplied with the module. Electrical connections
may only be made using the terminals provided
and strictly in accordance with wiring diagram
provided with the module.
7.1.2 RHC 4000(M) electrical controls
are
phase
sensitive 230V 1N 50 Hz. The appliance must be
earthed
after the installation has been completed
and earth continuity test must be carried out.
7.1.3 The
electrical
equipment of the module complies
with the requirements of: EN 60335-1, EN60730-1
and EN61058-1 or to relevant amendments. The
constructor must also comply with these
requirements when fitting the module.
7.1.4 The protection of jacketless appliances
conforms to protection code IP 20. The
constructor must ensure that protection
accordingly to at least IP 45 is fulfilled and mark
his data/rating plate accordingly.
Note:
IP 45 provides:
a) Personal protection against contact with
electrical components within the
construction;
b)
Degree of protection within the
construction against ingress of water.
7.1.5
The constructor shall test and inspect fully the
total appliance prior to supply including the
following:
a) Earth continuity (re: CENELEC 289)
b) Di-electric strain (re: CENELEC 289)
c) Function of all electrical components and
securities and operational inspection
d) Heat input and test for good and clean
combustion
e) Auxiliary equipment to be supplied as part
of the appliance
f)
Soundness of the total gas circuit
Attention :
All passages for gas pipes, etc to the
control compartment must be completely
sealed !
8.0 COMBUSTION
CIRCUIT
RHC 4000(M)
RJL ‘OUTDOOR’
8.1.1
Inlets for combustion air and flue outlets shall
be so designed so that when an appliance is
finally installed their termination shall be at least
500mm above deck/ground level.
8.1.2
The heating modules are delivered with all
parts necessary for the construction of the
jacket so that combustion can take place safely
and in line with the Gas Appliance Directive.
Included with the heating module RHC 4000 :
-
Dia 100 terminal outlet (length 300mm)
(PN°60 50712 300)
-
90° elbow with sealing ring (dia 100)
(PN 60 50733 100)
-
Flue outlet combustion sealing ring (dia 100)
(PN 06 22786 104)
-
Combustion air inlet protection grill (PN 90
79050)
- Gas tube sealing ring (PN 06 22783 125)
Included with the heating module RHC 4000M:
-
Dia 130 terminal outlet (length 282mm)
(PN°60 50712 130282)
-
90° elbow with sealing ring (dia 130)
(PN 60 50786 134)
-
Flue outlet combustion sealing ring (dia 130)
(PN 06 22786 104)
-
Combustion air inlet protection grill (PN 90
79050)
-
Gas tube sealing ring (PN 06 22783 054).