Table 17. Required Manifold (Outlet) Gas Pressure
Elevation
Single-Stage and Two-Stage High-Fire
Two-Stage Low-Fire
Feet
Meters
Natural Gas
Propane
Natural Gas
Propane
Manifold Pressure (IN WC)
US
0–2000
0–610
3 .5
10 .0
1 .8
5 .6
2001–3000
611–915
3 .1
8 .8
1 .6
5 .0
3001–4000
916–1220
3 .0
8 .5
1 .5
4 .8
4001- 5000
1221–1525
2 .8
8 .1
1 .5
4 .6
5001–6000
1526–1830
2 .7
7 .7
1 .4
4 .4
6001–7000
1831–2135
2 .6
7 .4
1 .3
4 .2
7001–8000
2136–2440
2 .5
7 .1
1 .3
4 .0
8001–9000
2441–2745
2 .4
6 .7
1 .2
3 .8
9001–10,000
2746–3045
2 .4
6 .7
1 .3
3 .6
ADJUSTMENTS—CONTINUED
Measure and Adjust Manifold (Outlet) Gas Pressure—Continued
Measure and Adjust Manifold Gas Pressure—Elevation
≤
2,000 Feet (
≤
610 Meters)—Continued
Figure 18. Gas Valves
⚠ CAUTION ⚠
DO NOT bottom out the gas valve regulator screw. This can result in excessive overfire and heat
exchanger failure due to unregulated manifold pressure.
5 . If manometer reading does not indicate that valve outlet pressure is in accordance with
, remove cap
) and adjust pressure by turning regulator screw IN (clockwise) to increase
pressure or OUT (counterclockwise) to decrease pressure .
6 . When manometer reading indicates that outlet pressure is in accordance with
, disconnect manometer
and install cap(s) on regulator screw(s) .
SINGLE-STAGE VALVE
1/8-INCH INLET
PRESSURE TAP
1/8-INCH OUTLET
PRESSURE TAP
1/8-INCH OUTLET
PRESSURE TAP
TWO-STAGE VALVE
1/8-INCH INLET
PRESSURE TAP
HIGH FIRE
REGULATOR
ADJUSTING
SCREW
LOW FIRE
REGULATOR
ADJUSTING
SCREW
REGULATOR
ADJUSTING
SCREW