17
RP-HRPD-IOM (07-22) 132210-B
Figure 11. Bypass Duct Dimensions
1 . Refer to
to determine pressure drop and allowable CFM for furnace being installed . For
example: model RP unit size
150
@ 5
0°F
temperature rise = pressure drop of
0.38
and CFM of
2,210
.
2 . Subtract allowable CFM from blower CFM to determine how much air must be diverted through bypass duct . For
example: blower CFM of
3,000
− allowable CFM of
2,210
= bypass CFM of
790
.
3 . Refer to
to determine bypass duct size as follows:
a . Go to column closest to pressure drop through heater .
b . Move down to CFM closest (round up) to CFM determined in step 2 .
c . Move to left column to determine required bypass duct size . For example: in pressure drop column
0.40
, move
down to bypass CFM row
900
and move left to dimension A column
3 inches
.
Table 11. Bypass Duct Size
Dimension A
(Inches (mm))
*
Pressure Drop Through Furnace
0.10
0.15
0.20
0.25
0.30
0.35
0.40
0.45
0.50
Bypass CFM
3 (76)
490
530
610
700
780
830
900
960
1010
4 (102)
630
750
870
980
1090
1160
1250
1310
1400
5 (127)
850
1010
1190
1300
1410
1520
1640
1730
1810
6 (152)
1050
1290
1480
1650
1800
1940
2090
2200
2320
7 (178)
1250
1510
1760
1960
2180
2320
2500
2650
2800
8 (203)
1490
1810
2100
2350
2560
2760
2940
3110
3290
9 (229)
1700
2100
2400
2700
2970
3200
3400
3600
3800
10 (254)
1920
2350
2760
3090
3650
4020
4300
4550
4800
*
See
.
NOTE: Not all capacities are covered above . If your installation is not covered, consult your distributor or the factory representative to
determine the appropriate size of the bypass duct .
Venting Connections
•
Locate power-vented furnaces so that flue discharge is not directed at fresh air inlets . The flue discharge openings
are located on the side of the furnace just above the control access panel . The position of this opening discourages
recirculation of combustion products and provides for furnace operation in all normal weather conditions .
• Optional vertical flue discharge (option CC3):
These power vented furnaces are certified with 4 feet of vertical
pipe connected as shown in
, DETAIL A . The distance is measured from the top of the unit to the bottom
of the vent cap . The vent pipe and supports are field-supplied . Optional vertical vent piping provides compliance
with local codes that require either 10-foot horizontal or 4-foot vertical clearance between the flue outlet and the
fresh air intake of the heating system and/or building . The option package (PN 45021) includes the 5-inch vent
cap, the adapter assembly, and the seal plate as shown in
, DETAIL B . Attach venter seal plate and
oval adapter assembly with sheet metal screws . Use venter seal plate as drill template .