12.2.5 Analog Output Configuration
Step 1: Set AO1 output mode
Code
Name
Setting range
Default
Min.
Attri.
E2.25 AO1 output mode
0: 0...10 V
1: 0...20 mA
0
–
Run
Step 2: Select AO1 output signal
Code
Name
Setting range
Default
Min.
Attri.
E2.26 AO1 output setting
0...99
0
–
Run
E2.40 Rated voltage
1P 200 VAC: 200...240 V
3P 400 VAC: 380...480 V
220
380
1
Stop
●
0: Output frequency
Represents the actual output frequency between 0.00…[E0.08] Hz.
●
1: Setting frequency
Represents the setting frequency between 0.00…[E0.08] Hz.
●
2: Output current
Represents the 0…2 x [rated current].
●
4: Output voltage
Represents 0...1.2 x [rated voltage], which is defined by parameter E2.40.
●
5: Output power, represents 0…1.2 x [rated power]
●
6: Analog input, represents AI1 input value
●
7: Analog input, represents AI2 input value
●
8: EAI analog input, represents the analog input value from I/O card
●
11: Motor temperature sensor power supply
Provides current source for motor temperature sensor, see
thermal protection with temperature sensor" on page 208
.
●
99: Inactive
Step 3: Set AO1 filter time and output curve
Code
Name
Setting range
Default
Min.
Attri.
E2.27 AO1 gain
0.0...10.00
1.00
0.01
Run
E2.50 Output curve 1 minimum
0.0 %...[E2.52]
0.0
0.1
Run
E2.51 Output curve 1 minimum value
0.00...100.00 %
0.00
0.01
Run