MAN-000037-00 REV C
45
TROUBLESHOOTING
Occasional faults may occur in certain conditions. Please follow the suggested steps.
A. Charger Does Not Power Up
When the charger is first turned on, the LCD should illuminate and display one of the
idle mode messages, typically the
CONNECT BATTERY
screen.
If the LCD is not illuminated after power is applied, perform the following checks:
a. Verify that the service disconnect switch (if provided) and the main panel breaker is
in the
ON
position.
b. Cycle the switch to the
OFF
position, wait 30 seconds, and then return it to the
ON
position.
c. If the charger display still does not illuminate, carefully verify the source circuit and
wiring to the charger and correct any problems. If appropriate, check that all fuses
in the service disconnect switch box on the wall are intact, and also that the supply
voltage for all three phases (AC mains line-to-line) is 480 V ± 10%, and matches to
10 VAC or better.
d. If the fault persists, contact the Dealer or Power Designers Sibex.
DANGEROUS VOLTAGES AND CURRENTS ARE PRESENT IN THE AC MAINS WHEN
ENERGIZED. ONLY TRAINED PERSONNEL SHOULD PERFORM THESE CHECKS,
USING PROPER EQUIPMENT AND PROCEDURES.
DO NOT ATTEMPT TO SERVICE THE CHARGER!
CAUTION
WARNING
Summary of Contents for RV16
Page 1: ...MAN 000037 00 REV C RV16 and RV24 Models Installation Operation Manual ...
Page 55: ...MAN 000037 00 REV C 54 RV24 Models Recommended mounting hardware 5 16 ...
Page 56: ...MAN 000037 00 REV C 55 Appendix B Post Stand Dimensions and Assembly instructions RV16 Models ...
Page 57: ...MAN 000037 00 REV C 56 RV24 Models ...
Page 58: ...MAN 000037 00 REV C 57 ...