7
Reverso Pumps, Inc. www.reversopumps.com | [email protected] | Ph: (954) 522-0882
Diesel Fuel
Pick-Up Tube
Return to Tank
Tank Vent
Moist
Air
Lowest Point
Of Tank
Accumulated
Water
Sludge
Flow In
Flow Out
Piping Installation
Use quality approved fuel line materials with at least 3/4” inner diameter line. Smaller plumbing
will place excessive load on the motor and shorten its life. A full port ball valve should be installed
on the inlet and outlet ports of the AFP (Automated Fuel Polishing).
Note: It is recommended to install a foot valve to keep the system primed, especially if the system
is located above the lowest possible fuel level in the tank.
If the AFP is mounted below tank top level, a priming tee should be installed on the highest point of the suction line
to be able to easily prime the systems delivery line. The return line(s) (discharge) should be connected to the outlet
of the pump “OUT” port and enter the tank as far as possible from the pick up tube. For optimal performance, ensure
that the outlet, discharge or return, line(s) are free and nothing is restricting their flow.
The pickup tube/line(s) (suction)
should originate from the lowest point
of the tank and should be connected
directly to the IN port. For optimal
performance, ensure that the inlet
(suction) line(s) is free and nothing is
restricting flow.
The suction line of the AFP must be independent and separate from the suction line of the engine. Do not integrate
into engine fuel system.
3
/
4
” ID
Installation Precaution