PRECAUTIONS & WARNINGS

The  precautions  mentioned  below  must  be  strictly  followed  during  operation
of the device:
-  all  works  concerning  electrical  installation  (disassembly,  repair  etc.)  should 
be made by the qualified staff, who possess the qualifications due to the domestic 
and local norms, regarding electrical installations
-  do  not  use  the  unit  for  direct  exhaustion  of  kitchen  vapors  -  this  may  result 
in clogging of the exchanger and filters by fats and greases
- the unit should not work without installed G3 and F9 filters - this can lead to dirt 
and clogging of the enthalpy exchanger
- if there is a risk of frosting, preheater should be used
- before service or exchange of the device it is obligatory to cut off the current 
supply
- do not limit or cover the inlet and outlet of the device
- do not install, service the device with wet hands or barefoot
- the device should be kept out of reach of children and animals
- after operating time of the device, please utilize it concerning the local norms 
and regulations
- it is recommended to clean the device periodically:
·

 

unit's casing clean from dirt (at least once per year)

·

 

G3 filter blow with compressed air to remove dirt and dust (at least once per 

quarter)
·

 

enthalpy heat exchanger clean from dirts (at least once per two year)

-  for  installation  of  the  device  in  a  place  where  is  high  dust  concentration,
the periodic cleaning of filter and exchanger should be performed much more 
often, not allowing the items to 'clog’
-failure  to  comply  with  cleaning  obligations  may  have  a  negative  effect 
on technical parameters of the device and lead to loss of warranty
- if the device is not used for a longer time and lead to loss of warranty disconnect 
the power supply

6. 

CONTROLS

6.1 CHARACTERISTIC

Energy  recovery  unit  INSPIRO  BASIC  series  has  controller  in  the  set,  which 
optimise the unit operation. Communication with the cotroller is possible with 
control  panel  BASIC  -  detailed  description  of  control  panel  operation  can  be 
found in point 6.3.

The main functions of the 

unit

:

- speed selection 

– 

regulation of supply and exhaust fans airflows - 3 different 

speeds

 - weekly schedule

 –  it is possible to set a weekly work schedule of the unit 

-bypass

–the function allows to supply outside air directly (i. e. without energy 

recovery) if there is no heating / cooiling demand

- filter alarm - 

after working over 1000 hours in total, the icon of filter alarm

 is displayed on the LCD screen - it remindes about necessity of filter cleaning

- BMS communication

 – the unit can be integrated with the BMS building control 

3. 

ASSEMBLY

3.1. GENERAL PRINCIPLES

- device is designed for hanging mounting
-  mounting  elements  not  included  in  the  kit,  you  should  buy  them  yourself 
and make sure they are suitable for this type of installation
- the device must be installed horizontally
- it is not possible to mount the unit upside down
- protect the openings of the unit against the ingress of dust during installation
-  the  minimum  gap  in  which  the  device  will  be  installed  is  at  least  320  mm 
(for INSPIRO BASIC 200 - INSPIRO BASIC 600) or 450 mm (for INSPIRO BASIC 
800)
- the device should be installed in a way that allows easy access to the inspection 
door and the electrical box
- exemplary installation with energy recovery unit is shown in the figure below

3.2 

DUCTING

-  connection  between  ducts  and  the  openings  of  the  device  must  be  secured 
with tape or sealed in accordance with domestic or local norms
-  outside  ducts  (i.  e.  fresh  and  exhaust  air)  should  be  thermally  insulated 
and carried out with a drop of 1 - 2% toward the outside in order to prevent water 
entering into the unit
- the energy recovery unit and ducts cannot run close of flues (e. g. form boiler)
- it is not allowed to make ducts in the way shown below:

-  fire  dampers  must  be  installed  in  accordance  with  domestic  or  local  fire 
regulations
- the device must not be exposed to an ambient temperature above 40 ° C
-  the  unit  should  be  protected  against  the  influence  of  frost  /  water 
(i.  e.  appropriate  insulation,  preventing  lowering  the  temperature  in  the  room 
below 0 ° C, pre-heater, etc.)
-  outside  ducts  should  be  ended  by  intake  and  exhaust  outlets,  located 
in accordance with domestic or local norms
- before start up ensure there are no obstructions to or in the ducts
- operation of heater should be synchronous with the unit
- duct silencers can be used to minimize noise in the room

4. INSTALLATION INSTRUCTIONS

4.1. CONNECTION OF THE DEIVCE TO THE ELECTRICAL SYSTEM

-  all  works  concerning  electrical  installation  should  be  made  by  the  qualified 
personnel (who possess required authorizations to install electrical equipment), 
based on wiring schematic diagram 

(see point 7)

-  the  recommended  cross  sectional  area  of  the  supply  wires  is  1.5 

m

m² 

and the control wires 1 

m

- the electrical installation of the building shall have a residual current device
- it is recommended to check the electric installation and controls before the first 
start

Excossive bending angle

Reduce the diameter 

of the junction part 

Too many bending parts

6.2 

COMMISSIONING

 

 

 1) Check the fans operation – in order to do that the following should be done:

- pressing button            set the manual mode

- using arrows            and           change the fans speed

2) Check the bypass operation  – in order to do that the following should be done:

- press and hold button            during 2 seconds to switch between energy recovery

 and bypass mode

ATTENTION! 

For INSPIRO BASIC 800 fans switch off for several seconds when 

the bypass damper is moving.

M

and then:

After checking all wires and conections, switch on the device with button

Summary of Contents for INSPIRO BASIC 200

Page 1: ...Technical documentation Energy Recovery Unit INSPIRO BASIC MODELS INSPIRO BASIC 200 INSPIRO BASIC 300 INSPIRO BASIC 400 INSPIRO BASIC 600 INSPIRO BASIC 800 EN...

Page 2: ...device out of line The installation should be carried out by the professional installers who possessthe qualifications to install these types of devices The installers are responsiblefor making the in...

Page 3: ...l airflow m h Maximum enthalpy efficiency Maximum temperature efficiency Supply voltage V Supply frequency Hz Motor power W Protection degree IP Net weight kg Noise dB A 200 63 75 220 240 50 105 X2 23...

Page 4: ...INSPIRO BASIC 400 INSPIRO BASIC 600 INSPIRO BASIC 800...

Page 5: ...the kit you should buy them yourself andmakesuretheyaresuitableforthistypeofinstallation thedevicemustbeinstalledhorizontally itisnotpossibletomounttheunitupsidedown protecttheopeningsoftheunitagains...

Page 6: ...n for 10 seconds the system will also savesettingsautomatically 1 6 3CONTROLPANELBASIC Thecontrolpanelissuppliedwith1mcable whichcanbeextendedifnecessary 1POWERON OFF 2MODE 3FUNCTIONBUTTON 4UP 5DOWN 6...

Page 7: ...7 CONNECTIONS SCHEMES INSPIRO BASIC 200 INSPIRO BASIC 600 INSPIRO BASIC 800...

Page 8: ...forthedefectivedevicewithinaspecifiedtimelimit VII Warranty does not cover the parts of the device subject to normal maintenanceandthefollowingcases a mechanicaldamageoftheproduct b defectsanddamagest...

Page 9: ...Warranty card Reventon Group Sp z o o Ltd 556 Wyzwolenia Street 43 340 Kozy Poland...

Page 10: ...Reventon Group Sp z o o Ltd 556 Wyzwolenia Street 43 340 Kozy Poland www reventongroup eu...

Reviews: