Technical data
Operating instructions SVCD(S)
33
123456278
-
419A58
Elektrotechnische Anlagen GmbH
1
REVCON
®
- type
Max. fuse AC
Connection terminal and max.
cross section of the supply line *
SVCD(S) 18-460-1-0
Siba 5012406.50 50A 690 V 14x51mm
ES
25mm²
SVCD(S) 30-460-1-115
Siba 5014006.80 80A 690 V 22x58mm
ES
25mm²
SVCD(S) 50-460-1-115
Siba 5007406.125 125A 690 V 22x58mm
ES
25mm²
SVCD(S) 70-460-1-115
Siba 2018920.160 160A 690V NH 00
ES
50mm²
SVCD(S) 100-460-1-115
Siba 2018920.250 250A 690V NH 00
CS M12
150mm²
SVCD(S) 120-460-1-115
Siba 2018920.315 315A 690V NH 00
CS M12
150mm²
SVCD(S) 150-460-1-115
Siba 2018920.350 350A 690V NH 00
CS M12
150mm²
SVCD(S) 200-460-1-115
Siba 2071332.400 400A 1100 V NH 1
CS M16
240mm²
Table 3.3.3.1.3
REVCON
®
- type
Max. fuse AC
Connection terminal and max.
cross section of the supply line *
SVCD(S) 18-500-1-0
Siba 5012406.50 50A 690 V 14x51mm
ES
25mm²
SVCD(S) 30-500-1-230
Siba 5014006.80 80A 690 V 22x58mm
ES
25mm²
SVCD(S) 50-500-1-230
Siba 5007406.125 125A 690 V 22x58mm
ES
25mm²
SVCD(S) 70-500-1-230
Siba 2018920.160 160A 690V NH 00
ES
50mm²
SVCD(S) 100-500-1-230
Siba 2018920.250 250A 690V NH 00
CS M12
150mm²
SVCD(S) 120-500-1-230
Siba 2018920.250 250A 690V NH 00
CS M12
150mm²
SVCD(S) 150-500-1-230
Siba 2018920.350 350A 690V NH 00
CS M12
150mm²
SVCD(S) 200-500-1-230
Siba 2071332.400 400A 1100 V NH 1
CS M16
240mm²
Table 3.3.3.1.4
REVCON
®
- type
Max. fuse AC
Connection terminal and max.
cross section of the supply line *
SVCD(S) 12-690-1-230
Siba 5012434.16 16A 690 V 14x51mm
ES
25mm²
SVCD(S) 24-690-1-230
Siba 5014006.32 32A 690 V 22x58mm
ES
25mm²
SVCD(S) 50-690-1-230
Siba 50140 06.63 63A 690 V 22x58mm
ES
25mm²
SVCD(S) 70-690-1-230
Siba 50140 06.100 100A 690 V 22x58mm
ES
25mm²
SVCD(S) 110-690-1-230
Siba 2018920.160 160A 690V NH 00
CS M12
150mm²
SVCD(S) 150-690-1-230
Siba 2018920.200 200A 690V NH 00
CS M12
150mm²
SVCD(S) 200-690-1-230
Siba 2018920.315 315A 690V NH 00
CS M12
150mm²
SVCD(S) 250-690-1-230
Siba 2018920.350 350A 690V NH 00
CS M12
150mm²
Table 3.3.3.1.5
ES
≅
end sleeve for strands
CS
≅
cable socket with drill hole for M6 / M8 / M10
* At the copper lugs of the commutation choke
** At the fuse holder respective disconnector