Technical data
28
Operating instructions SVCD(S)
123456278
-
419A58
Elektrotechnische Anlagen GmbH
1
3.3
Rated data
3.3.1
Power feedback unit
REVCON
®
-type
SVCD(S)
230V
SVCD(S)
400V
SVCD(S)
460V
SVCD(S)
500V
SVCD(S)
690V
Nominal range of the
interlinked mains voltage
U
N
[V]
220
≤
U
N
≤
240
380
≤
U
N
≤
415
440
≤
U
N
≤
480
500
600
≤
U
N
≤
700
Tolerance of the
interlinked mains voltage
U
N
[V]
198
≤
U
N
≤
264
342
≤
U
N
≤
456
396
≤
U
N
≤
528
450
≤
U
N
≤
550
540
≤
U
N
≤
770
Mains frequency
f
N
[Hz]
40 - 60
±
10 %
Overload capability
(see table 3.3.2.1 to 3.3.2.3)
Efficiency
η
[%]
Ca. 97 % (3 % therm. losses)
Power factor
cos
ϕ
∼
1
Fundamental frequency
component
g
∼
0,7- 0,95
*
Required airflow
m³ / h
a)
SVCD(S) 4-230, 7-230, 10-230, 13-230
SVCD(S) 7-400, 13-400, 18-400, 24-400
SVCD(S) 18-460
SVCD(S) 18-500
SVCD(S) 12-690
:
200
b)
SVCD(S) 17-230
SVCD(S) 30-400
SVCD(S) 30-460
SVCD(S) 30-500
SVCD(S) 24-690
:
350
c)
SVCD(S) 25-230, 40-230
SVCD(S) 50-400, 70-400
SVCD(S) 50-460, 70-460
SVCD(S) 50-500, 70-500
SVCD(S) 70-690
:
450
d)
SVCD(S) 55-230, 70-230, 85-230, 115-230
SVCD(S) 100-400, 125-400, 150-400, 200-400
SVCD(S) 100-460, 120-460, 150-460, 200-460
SVCD(S) 100-500, 120-500, 150-500, 200-500
SVCD(S) 110-690
:
700
e)
SVCD(S) 145-230
SVCD(S) 200-690
SVCD(S) 250-400
SVCD(S) 250-690
:
800
Power derating
[%/K]
[%/m]
40°C < Ta < 45°C
1
3%/K
1000m a.m.s.l.< h
≤
4000m a.m.s.l.
1
5%/1000m
Table 3.3.1.1
*
Depending on the size of the unit (nominal power and nominal voltage)