As soon as the temperature at the collector is 4 °C, the
frost protection function operates the loading circuit bet-
ween the collector and the store in order to protect the
medium in the loading circuit against freezing or coagulation.
If the collector temperature exceeds 5 °C, this function is
switched-off.
The pump output uses maximum pump speed.
Adjustment channel for the heat transfer fluid used.
Antifreeze type
antifr. type
selection „Tyfo LS“, „Ethylene“, „Propylene“, „Water“
factory setting: „Tyfo LS“
Antifreeze ratio
antifreeze ratio
adjustment range 20 ... 70 %
factory setting 40 %
Adjustment channel for the glycol concentration in the heat
transfer fluid. The concentration of proylene-glycol in the
water-glycol mixture should not exceed 50 %.
Frost protection
Frost protection
selection: „Yes“, „No“
factory setting: „No“
Tube collector function
tube collector
selection: „Yes“, „No“
factory setting: „No“
interval
adjustment range 1 ... 60 min
factory setting 30 min
runtime
adjustment range 5 ... 500 s
factory setting 30 s
start
adjustment range 00:00 ... 23:59
factory setting 07:00
stop
adjustment range 00:00 ... 23:59
factory setting 19:00
This function helps overcome non-ideal sensor position
with some tube collectors and compensates for the delayed
temperature measurement.
This function operates within a given time frame (“start“
and “stop“). It activates the collector circuit pump for 30
seconds (adjustable via the parameter “runtime“) every 30
minutes at collector standstill (adjustable via the parameter
“interval“).
If the collector sensor is defective or if the collector is blo-
cked, this function is suppressed or switched-off.
The collector circuit is operated at minimum pump speed.
Pump speed is controlled according to flow temperature
(to keep the flow temperature constant). Therefore, the
dependence on the temperature difference is released. The
flow set temperature can be adjusted via the adjustment
value “Tflowset“. If the temperature sensor in the flow is
defective, the pump is operated at 100 %.
Target temperature
target temperature
selection „Yes“, „No“
factory setting: „No“
Tflowset
adjustment range 0 ... 80 °C
factory setting 60 °C