Installation
Indications,
functions and options
Messages
Commissioning
Operation and function
Note
If the drainback option is activated, the cooling functions and the antifreeze
function will not be available.
The H-DAY (holiday function) menu will also not be available and cannot be
selected by means of the microbutton
⛁
.
Note
The drainback option is only available in systems with 1 store and 1 collector
field and if no cooling function is activated.
Note
If the drainback function ODB is activated, the factory settings of the
parameters DT O, DT F und DT S will be adapted to values suiting drain-
back systems:
DT O = 10 K
DT F = 4 K
DT S = 15 K
Additionally, the adjustment range and the factory setting of the collector
emergency shutdown CEM will change:
Adjustment range: 80 … 120 °C; Factory setting: 95 °C
Adjustments previously made in these channels will be overridden and have
to be entered again if the drainback option is deactivated later on.
Note
If the holiday function is activated, the drainback option will not be available.
Booster function
This function is used for additionally switching on a second pump when filling the
system. When solar loading starts, R2 is energised in parallel to R1. After the filling
time has elapsed, R2 switches off.
Note
The booster function is available in system 1 only.
Successive loading option
Successive loading means that the priority store will be loaded up to its maximum
temperature. If it is reached, the second store will be loaded. If the temperature of
the first store falls below the store set temperature, the second store will no longer
be loaded, regardless of whether the switch-on conditions of the priority store or
of the subordinate store are fulfilled or not.
If both store have been loaded to their set temperature, the same process described
above will take place until the stores heave reached their maximum temperature.
OBST
Booster function
Selection: OFF / ON
Factory setting: OFF
a
a
b
b
c
c
d
d
e
f
BACK
PUSH
OSuC
Successive loading option
Selection: OFF / ON
Factory setting: OFF
OSE
PUSH
DTSE
Temperature diff.
Spreaded loading
Adjustment range: 20 … 90 K
Factory setting: 40 K
OSE
Spreaded loading option
Selection: OFF / ON
Factory setting: OFF
OK
OFF
ON
BACK
PUSH
7